DETAILED COOLING CAPACITIES*

 

See notes on page 18.

 

EVAPORATOR

AIR

CONDENSER ENTERING AIR TEMPERATURES °F

85

95

105

115

125

CFM

EWB

Capacity

MBtuh†

Total

System

Kw**

Capacity

MBtuh†

Total

System

Kw**

Capacity

MBtuh†

Total

System

Kw**

Capacity

MBtuh†

Total

System

Kw**

Capacity

MBtuh†

Total

System

Kw**

Total

Sens‡

Total

Sens‡

Total

Sens‡

Total

Sens‡

Total

Sens‡

 

594D018-E Outdoor Section With CK5A/CK5BA024 Indoor Section

 

525

72

19.6

9.74

1.48

18.9

9.46

1.66

18.1

9.17

1.85

17.4

8.90

2.00

16.6

8.60

2.33

67

18.0

12.4

1.46

17.3

12.1

1.63

16.6

11.8

1.82

15.9

11.5

2.00

15.1

11.2

2.28

62

16.5

14.9

1.44

15.9

14.6

1.61

15.2

14.3

1.80

14.5

13.9

2.00

13.8

13.5

2.25

57

15.9

15.9

1.43

15.4

15.4

1.60

14.8

14.8

1.79

14.2

14.2

2.00

13.6

13.6

2.26

600

72

19.9

10.1

1.51

19.2

9.86

1.69

18.4

9.57

1.88

17.6

9.30

2.10

16.7

9.01

2.36

67

18.3

13.1

1.49

17.6

12.8

1.66

16.9

12.5

1.86

16.1

12.2

2.00

15.3

11.9

2.30

62

16.8

15.9

1.46

16.2

15.6

1.65

15.5

15.2

1.84

14.8

14.7

2.00

14.1

14.1

2.28

57

16.4

16.4

1.46

15.9

15.9

1.64

15.3

15.3

1.83

14.7

14.7

2.00

14.1

14.1

2.29

675

72

20.1

10.5

1.54

19.3

10.2

1.72

18.6

9.98

1.92

17.7

9.68

2.10

16.9

9.38

2.38

67

18.6

13.8

1.52

17.9

13.5

1.70

17.1

13.2

1.89

16.3

12.9

2.10

15.4

12.6

2.33

62

17.1

16.7

1.51

16.4

16.3

1.68

15.8

15.8

1.87

15.1

15.1

2.00

14.4

14.4

2.31

57

16.9

16.9

1.49

16.4

16.4

1.68

15.8

15.8

1.87

15.1

15.1

2.00

14.5

14.5

2.32

Multipliers for Determining the Performance With Other Indoor Sections

 

Indoor

Section

Size

Cooling

Indoor

Section

Size

Cooling 

Capacity

Power

Capacity

Power

 

CC5A/CD5AA

018

0.98

1.00

FK4CNF

001

1.02

0.91

024

1.00

1.00

002

1.02

0.91

CC5A/CD5AW

024

1.00

1.00

 

COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE

 

CE3AA

024

1.00

1.00

CC5A/CD5AA

018

0.97

0.90

CK3BA

024

1.00

1.00

024

1.00

0.90

CK5A/CK5BA

018

0.98

1.00

CK5A/CK5BA

018

0.97

0.90

024

1.00

1.00

024

1.00

0.90

CK5A/CK5BW

024

1.00

1.00

 

COILS + 355MAV042060 VARIABLE SPEED FURNACE

 

F(A,B)4AN(F,C)

018

0.95

0.98

CC5A/CD5AW

024

1.00

0.93

024

1.00

0.99

CK5A/CK5BW

024

1.00

0.93

FC4BNF

024

1.00

1.01

 

COILS + 355MAV042080 VARIABLE SPEED FURNACE

 

FF1(B,C,D)NA

018

0.97

0.96

CC5A/CD5AW

024

1.00

0.92

024

1.00

1.00

CK5A/CK5AW

024

1.00

0.92

FG3AAA

024

0.97

1.00

Содержание 594D

Страница 1: ...ting refrigerant pressures EASY SERVICEABILITY One panel provides access to elec trical controls and compressor Removal of wire dome grille gives access to fan motor while removal of top gives access to coil COMPRESSOR PROTECTION Each model is protected with internal temperature and current sensitive overloads An inter nal pressure relief valve provides high pressure protection to the refrigerant ...

Страница 2: ... IN DIA TIEDOWN KNOCKOUTS 2 PLACES IN BASEPAN 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 L C F N G A B M K E D C L A97001 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H K L M N 018 E 23 13 16 22 1 2 26 3 16 4 1 8 7 1 8 13 13 16 18 3 8 5 8 12 14 5 8 10 2 3 8 20 x 27 024 E 27 13 16 22 1 2 26 3 16 4 1 8 7 1 8 15 15 16 22 3 8 5 8 12 14 5 8 11 2 3 8 20 x 27 ...

Страница 3: ... 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 E 55 024 E 59 030 E 67 036 E 73 042 E 78 048 E F 84 060 E 93 UNIT SIZE SOUND LEVEL dBA OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 018 72 54 5 63 0 65 5 66 0 63 5 59 0 51 5 024 74 51 5 61 0 62 5 65 5 62 0 58 5 52 5 030 74 57 0 64 0 67 0 69 0 64 0 60 0 52 5 036 76 59 0 66 0 67 0 69 5 66 5 62 5 56 0 042 76 58 0 65 0 6...

Страница 4: ...er KAACF0601SML KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA Start Assist PTC Type KAACS0201PTC TXV Kit RPB KAATX0201RPB KAATX0301RPB KAATX0401RPB KAATX0501RPB TXV Kits Hard Shutoff KSATX0601HSO Low Pressure Switch KAALP0101LPS High Pressure Switch KSAHI0101HPS Filter Drier P502 8083S RCD Evapor...

Страница 5: ...reak Refrigerant R 22 Amount Lb 6 68 6 34 9 25 CONDENSER COIL AND FAN Coil Face Area Sq Ft 15 2 18 3 Fins per In Rows Circuits 25 1 3 25 1 4 Fan Motor HP Type RPM 1 5 PSC 825 1 4 PSC 1100 Volts Hertz Phase 208 230 60 1 Condenser Airflow CFM 3000 3300 OPTIONAL EQUIPMENT Support Feet Kit KSASF0101AAA Coastal Filter KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Standard Cran...

Страница 6: ...ions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evaporator Freeze Thermostat An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze up conditions SUGGESTED USE All units where Winter Start Control has been added Use with ...

Страница 7: ...tures below 55 F All commercial installations 14 Outdoor Air Temperature Sensor A device that allows the temperature at a remote location outdoors to be displayed at the thermostat SUGGESTED USE All corporate programmable thermostats 15 Support Feet Four stick on plastic feet which raise the unit 4 in above the mounting pad This allows sand dirt and other debris to be flushed from the unit base mi...

Страница 8: ...24 23 000 NONE 10 80 11 00 11 00 9 70 CK3BA030 23 000 NONE 10 80 11 00 11 00 9 80 CK5A CK5BA024 23 000 NONE 10 80 11 00 11 00 9 70 CK5A CK5BA030 23 000 NONE 10 80 11 00 11 00 9 80 CK5A CK5BW024 23 000 NONE 10 80 11 00 11 00 9 70 CK5A CK5BW030 23 200 NONE 10 80 11 00 11 00 9 80 F A B 4AN F C 024 23 000 TDR 11 00 11 00 9 80 F A B 4AN F C 030 23 400 TDR 11 40 11 40 10 00 FC4BNF024 23 000 TDR TXV 11 0...

Страница 9: ...000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BA042 35 000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BW036 35 000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BW042 34 800 NONE 11 00 11 20 11 20 10 05 F A B 4AN F B C 042 35 000 TDR 11 20 11 20 10 10 F A B 4AN F C 036 34 400 TDR 11 00 11 00 9 80 FC4BNB054 36 600 TDR TXV 12 00 10 80 FC4BNF036 34 400 TDR TXV 11 00 9 80 FC4BN F B 042 35 000 TDR TXV 11 20 10 10 FC4BNF03...

Страница 10: ...1 000 TDR 12 00 12 00 11 15 COILS 355MAV060100 VARIABLE SPEED FURNACE CD5AA048 41 000 TDR 12 50 12 50 11 15 CK5A CK5BA048 41 000 TDR 12 50 12 50 11 15 048 E F CC5A CD5AA060 46 800 NONE 10 60 11 00 11 00 9 65 CC5A CD5AC048 45 000 NONE 10 50 10 80 10 80 9 50 CC5A CD5AW048 46 000 NONE 10 50 11 00 11 00 9 60 CC5A CD5AW060 48 000 NONE 10 80 11 20 11 20 9 85 CD5AA048 46 500 NONE 10 50 11 00 11 00 9 60 C...

Страница 11: ...TDR 11 00 11 00 9 75 CK5A CK5BA048 46 000 TDR 11 00 11 00 9 75 COILS 355MAV060080 VARIABLE SPEED FURNACE CC5A CD5AA060 46 000 TDR 11 00 11 00 9 70 CC5A CD5AW060 47 000 TDR 11 20 11 20 9 95 CD5AA048 46 000 TDR 11 00 11 00 9 60 CK3BA048 46 000 TDR 11 00 11 00 9 70 CK5A CK5BA060 46 500 TDR 11 00 11 00 9 90 CK5A CK5BX060 47 000 TDR 11 20 11 20 10 15 CK5A CK5BA048 46 000 TDR 11 00 11 00 9 70 COILS 355M...

Страница 12: ... 46 15 9 15 9 1 64 15 3 15 3 1 83 14 7 14 7 2 00 14 1 14 1 2 29 675 72 20 1 10 5 1 54 19 3 10 2 1 72 18 6 9 98 1 92 17 7 9 68 2 10 16 9 9 38 2 38 67 18 6 13 8 1 52 17 9 13 5 1 70 17 1 13 2 1 89 16 3 12 9 2 10 15 4 12 6 2 33 62 17 1 16 7 1 51 16 4 16 3 1 68 15 8 15 8 1 87 15 1 15 1 2 00 14 4 14 4 2 31 57 16 9 16 9 1 49 16 4 16 4 1 68 15 8 15 8 1 87 15 1 15 1 2 00 14 5 14 5 2 32 Multipliers for Dete...

Страница 13: ...5 2 42 24 2 13 1 2 67 23 1 12 7 2 9 21 9 12 3 3 25 67 24 2 18 2 2 17 23 2 17 8 2 39 22 2 17 4 2 63 21 2 17 0 2 9 20 1 16 6 3 21 62 22 3 22 0 2 14 21 4 21 4 2 36 20 6 20 6 2 60 19 8 19 8 2 8 19 0 19 0 3 18 57 22 1 22 1 2 14 21 5 21 5 2 37 20 6 20 6 2 60 19 8 19 8 2 8 19 0 19 0 3 18 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size...

Страница 14: ... 67 30 6 22 8 2 66 29 4 22 3 3 05 28 0 21 7 3 54 26 4 21 1 4 1 24 3 20 3 5 15 62 28 2 27 6 2 67 27 0 26 8 3 07 25 8 25 8 3 56 24 5 24 5 4 1 22 6 22 6 5 34 57 27 9 27 9 2 68 26 9 26 9 3 08 25 8 25 8 3 58 24 6 24 6 4 1 22 8 22 8 5 18 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA ...

Страница 15: ... 91 30 1 30 1 4 3 28 6 28 6 4 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CE3AA 042 0 99 0 95 042 1 00 1 00 CK5A CK5BA 042 0 99 0 94 CC5A CD5AW 042 0 99 1 00 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CD5AW 036 1 00 1 00 CC5A CD5AA 042 0 99 0 94 CE3AA 036 ...

Страница 16: ...1 41 5 30 9 4 09 39 7 30 2 4 51 37 9 29 5 4 9 36 1 28 8 5 53 62 39 6 38 3 3 68 38 1 38 3 4 05 36 5 36 3 4 48 35 0 35 0 4 9 33 6 33 6 5 49 57 39 0 39 0 3 67 37 7 37 7 4 05 36 4 36 4 4 48 35 0 35 0 4 9 33 6 33 6 5 50 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 FK4...

Страница 17: ...9 COILS 333 B J AV060120 VARIABLE SPEED FURNACE CC5A CD5AW 048 0 98 1 00 CC5A CD5AA 060 0 99 0 95 060 1 03 1 00 CC5A CD5AW 048 0 98 0 95 CD5AA 048 0 99 1 00 060 1 00 0 95 CE3AA 048 0 99 1 00 CK3BA 060 0 99 0 95 060 1 03 1 00 CK5A CK5BA 060 0 99 0 95 CF5AA 048 0 99 0 99 CK5A CK5BW 048 0 98 0 95 CK3BA 048 0 99 1 00 CK5A CK5BX 060 1 00 0 95 060 1 00 1 00 COILS 355MAV042080 VARIABLE SPEED FURNACE CK5A...

Страница 18: ...2 29 4 6 35 54 9 28 2 6 7 50 9 26 8 7 13 67 57 8 39 6 5 36 55 4 38 6 5 79 52 5 37 5 6 21 49 0 36 1 6 5 44 8 34 4 6 76 62 52 4 47 6 5 28 49 9 46 4 5 68 46 9 44 8 6 02 43 4 42 8 6 2 39 7 39 7 6 37 57 50 2 50 2 5 20 48 2 48 2 5 59 45 9 45 9 5 93 43 2 43 2 6 2 40 1 40 1 6 37 2000 72 64 7 32 8 5 44 62 1 31 8 5 91 59 3 30 8 6 38 56 0 29 7 6 8 52 1 28 3 7 22 67 59 0 42 0 5 38 56 5 41 0 5 82 53 6 39 9 6 2...

Страница 19: ...KW 1 30 1 48 1 66 1 87 2 09 2 33 2 60 55 TCG 33 5 32 5 31 4 30 0 28 6 27 1 25 6 SDT 92 7 101 0 110 0 120 0 129 0 138 0 147 0 KW 1 32 1 49 1 69 1 90 2 13 2 38 2 65 594D030 E 30 TCG 28 3 27 0 25 7 24 2 22 8 21 2 19 7 SDT 80 4 90 3 100 0 110 0 120 0 130 0 140 0 KW 1 47 1 72 1 99 2 30 2 63 2 99 3 34 35 TCG 31 0 29 6 28 2 26 7 25 1 23 5 21 8 SDT 82 0 91 9 102 0 112 0 122 0 132 0 142 0 KW 1 46 1 71 1 99...

Страница 20: ...65 4 13 4 64 5 17 35 TCG 50 4 48 1 45 7 43 2 40 7 38 1 35 5 SDT 81 9 91 6 101 0 111 0 121 0 131 0 140 0 KW 2 49 2 85 3 25 3 69 4 18 4 71 5 25 40 TCG 55 1 52 6 50 1 47 4 44 7 41 9 39 1 SDT 83 9 93 4 103 0 113 0 123 0 132 0 142 0 KW 2 52 2 88 3 29 3 74 4 23 4 77 5 34 45 TCG 60 0 57 4 54 7 51 9 49 0 46 0 43 0 SDT 86 0 95 5 105 0 115 0 124 0 134 0 144 0 KW 2 55 2 92 3 33 3 79 4 29 4 84 5 43 50 TCG 65 ...

Страница 21: ...n 50 ft consult Residential Split System Long Line Application Guidelines available from equipment distributor 7 Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft 8 Not more than 3 ft of refrigerant tube should be buried in the ground If necessary to bury tubes under a sidewalk provide a minimum 6 in vertical rise to the valve connections at the unit For buried l...

Страница 22: ... 22 MATCHED SYSTEM A98599 ...

Страница 23: ... 23 ...

Страница 24: ...nit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 594D 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant ...

Отзывы: