33
SPAN
ZERO
4-20
mA
VAC
or
VDC
GND 0-5V
or
0-10V
1
2
3
4
5
6
ON
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-)4 to 20 mA Current Loop Output
to RTU Open
Relative Humidity Sensor
(Polarized Male Connector)
C12756
Fig. 52 -- Duct Relative Humidity Sensor Typical Wiring
Humidistat:
Use of a field--supplied humidistat provides
the RTU Open insight to the relative humidity in the
space. The humidistat reads the RH level in the space and
compares it to its setpoint to operate a dry contact. The
humidistat is a dedicated input on the configurable input 9
and tells the RTU Open when the RH level is HIGH or
LOW. The normal condition for humidity is LOW. A
normally open humidistat is the factory default control for
the Perfect Humidity
t
option.
To wire in the field:
S
J5--8 = 24 VAC source for dry contact
S
J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 582J units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU Open
controller communicates the smoke detector’s tripped
status to the BAS building control. See Figs. 39 and 40,
the RTU Open System Control wiring schematics.
The
Fire
Shutdown
Switch
configuration,
MENU
Config
Inputs
input 5
, identifies the normally
open status of this input when there is no fire alarm.
Connecting Discrete Inputs —
Filter Status:
The filter status accessory is a
field--installed accessory. This accessory detects plugged
filters. When installing this accessory, the unit must be
configured
for
filter
status
by
setting
MENU
Config
Inputs
input 3, 5, 8, or 9
to Filter
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 38 and Fig. 39 or Fig. 40 for wire terminations at J5.
Fan Status:
The fan status accessory is a field--installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
be
configured
for
fan
status
by
setting
MENU
Config
Inputs
input 3, 5, 8, or 9
to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 38 and Figs. 39 or 40 for wire terminations at J5.
Remote Occupancy:
The remote occupancy accessory is
a field--installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configured
for
remote
occupancy
by
setting
MENU
Config
Inputs
input 3, 5, 8, or 9
to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set
MENU
Schedules
occupancy source
to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 38 and Table 6 for wire
terminations at J5.
Power Exhaust (output):
The relay used by the RTU
Open board to control power exhaust is a dry contact
which means it does not have 24vac. This 24vac must be
connected to the relay to allow it to operate the power
exhaust relay in the PE accessory. A 24vac source must be
provided to J11--2 on the RTU Open control board. This
can be provided by the unit’s transformer from various
sources. The “R” terminal on the unit’s low voltage
terminal board (LVTB) is a logical source. Refer to Fig.
38 and Figs. 39 or 40 for wire terminations at J11.
582J
Содержание 582J 04 Series
Страница 5: ...5 C14270 Fig 2 Unit Dimensional Drawing 582J ...
Страница 6: ...6 C14271 Fig 2 Unit Dimensional Drawing cont 582J ...
Страница 12: ...12 C14272 Fig 6 Rigging Label 582J ...
Страница 27: ...27 C14247 Fig 39 RTU Open System Control Wiring Diagram 582J ...
Страница 28: ...28 C14248 Fig 40 RTU Open System Control Wiring Diagram with Perfect Humidityt 582J ...