Supply (Indoor) Fan Motor Protection
PERSONAL INJURY HAZARD
Failure to follow this WARNING can result in
personal injury.
Disconnect all electrical power when servicing the fan
motor. Apply appropriate lockout/tagout procedures.
!
WARNING
Motors with 2.9 and 3.7 bhp are equipped with an internal
overtemperature or protection device. The type of device
depends on the motor size. See Table 7.
The High Static option supply fan motor is equipped with
a pilot
−
circuit Thermix combination overtemperature/
overcurrent protection device. This device resets
automatically. Do not bypass this switch to correct
trouble. Determine the cause and correct it.
The Thermik device is a snap
−
action overtemperature
protection device that is embedded in the motor windings.
The Thermik can be identified by two blue wires
extending out of the motor control box. It is a pilot
−
circuit
device that is wired into the unit’s 24V control circuit.
When this switch reaches its trip setpoint, it opens the
24V control circuit and causes all unit operation to cease.
This device resets automatically when the motor windings
cool. Do not bypass this switch to correct trouble.
Determine the cause and correct it.
The External Overload Breaker is an overcurrent device
used on motors with a horsepower rating of 4.7 hp or
greater. This is a specially
−
calibrated circuit breaker that
is UL recognized as a motor overload controller. When
the current to the motor exceeds the circuit breaker
setpoint, the device opens all motor power leads to the
motor, shutting the motor down. Reset requires a manual
reset at the overload switch. This device (designated
IFCB) is located on the side of the supply fan housing,
behind the fan access panel. The Must Hold and Must Trip
values are listed on the side of the External Overload
Breaker.
Troubleshooting Supply Fan Motor Overload
Trips
The supply fan used in 580J units is a forward
−
curved
centrifugal wheel. At a constant wheel speed, this wheel
has a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit
−
duct
system increases and to INCREASE when the static
pressure in the unit
−
duct system decreases (and fan
airflow rate increases). Motor overload conditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer
−
open mode, or a leak develops in the duct
system that allows a bypass back to unit return opening.
Table 7 – Overcurrent Device Type
Motor Size (bhp)
Overload Device
Reset
1.7
Internal Linebreak
Automatic
2.4
Internal Linebreak
Automatic
2.9
Thermik
Automatic
3.7
Thermik
Automatic
4.7
External (circuit breaker)
Manual
Condenser Fan Motor Protection
The condenser fan motor is internally protected against
overtemperature.
Control Circuit, 24
−
V
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on the control
transformer TRAN. Reset is manual.
RTU
−
OPEN CONTROL SYSTEM
The RTU (Roof Top Unit) Open controller is an integrated
component of the Bryant rooftop unit. Its internal
application programming provides optimum performance
and energy efficiency. RTU Open enables the unit to run
in 100% stand
−
alone control mode, Bryant’s I
−
Vu Open
network, or a Third Party Building Automation System
(BAS). On
−
board DIP switches allow you to select your
protocol (and baud rate) of choice among the four most
popular protocols in use today: BACnet, Modbus, Johnson
N2 and LonWorks.
The RTU Open control is factory
−
mounted in the 580J
unit’s main control box, to the left of the Light
Commercial Terminal Board (LCTB). See Fig. 44.
Factory wiring is completed through harnesses connected
to the LCTB. Field connections for RTU Open sensors
will be made at the Phoenix connectors on the RTU Open
board. The factory
−
installed RTU Open control includes
the supply
−
air temperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er2 package.
Sensory/Accessory Installation
There are a variety of sensors and accessories available
for the RTU
−
OPEN. Some of these can be factory or field
installed, while others are only field installable. The
RTU
−
OPEN controller may also require connection to a
building network system or building zoning system. All
field control wiring that connects to the RTU
−
OPEN must
be routed through the raceway built into the corner post of
the unit or secured to the unit control box with electrical
conduit. The unit raceway provides the UL required
clearance between high and low
−
voltage wiring. Pass the
control wires through the hole provided in the corner post,
then feed the wires thorough the raceway to the
RTU
−
OPEN. Connect the wires to the removable Phoenix
connectors and then reconnect the connectors to the board.
Содержание 580J D17
Страница 80: ...80 APPENDIX IV WIRING DIAGRAMS cont C160041 Fig 72 580J D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 81: ...81 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 73 580J D17 D28 Power Diagram 208 230 3 60 ...
Страница 82: ...82 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 74 580J D17 D28 Power Diagram 460 3 60 ...
Страница 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 75 580J D17 D28 Power Diagram 575 3 60 ...
Страница 84: ...84 APPENDIX IV WIRING DIAGRAMS cont C160050 Fig 76 580J D17 D28 Control Diagram with Perfect Humidity ...
Страница 86: ...86 APPENDIX IV WIRING DIAGRAMS cont C160047 Fig 78 580J D17 D28 Power Diagram 460 3 60 with Perfect Humidity ...
Страница 87: ...87 APPENDIX IV WIRING DIAGRAMS cont C160048 Fig 79 580J D17 D28 Power Diagram 575 3 60 with Perfect Humidity ...
Страница 88: ...88 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 80 RTU OPEN Wiring Diagram ...
Страница 89: ...89 APPENDIX IV WIRING DIAGRAMS cont C160045 Fig 81 RTU OPEN Wiring Diagram with Perfect Humidity ...