10
Routine Cleaning of Coil Surfaces
Periodic cleaning with Totaline
environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Bryant Replacement
Components Division as
p/n: P902- 0301 for one-gallon
(3.8L) container, and P902- 0305 for a 5-gallon (18.9L)
container
. It is recommended that all coils, including
standard aluminum, pre
−
coated, copper/copper or
E
−
coated coils be cleaned with the Totaline
environmentally sound coil cleaner as described below.
Coil cleaning should be part of the unit’s regularly
scheduled maintenance procedures to ensure long life of
the coil. Failure to clean the coils may result in reduced
durability in the environment.
Avoid use of:
coil brighteners
acid cleaning prior to painting
high pressure washers
poor quality water for cleaning
Totaline
environmentally sound coil cleaner is a non-
flammable, hypo allergenic, non bacterial, USDA accept-
ed biodegradable agent that will not harm the coil or sur-
rounding components such as electrical wiring, painted
metal surfaces, or insulation. Use of non
−
recommended
coil cleaners is strongly discouraged since coil and unit
durability could be affected.
Two
−
Row Coils
Clean coil as follows:
1. Turn off unit power and tag the disconnect.
2. Remove the top panel screws on the condenser end of
the unit.
3. Remove the condenser coil corner post. See Fig. 12.
To hold the top panel open, place the coil corner post
between the top panel and center post. See Fig. 13.
C08205
Fig. 12
−
Cleaning Condenser Coil
C08206
Fig. 13
−
Propping Up Top Panel
4. Remove the screws securing the coil to the compres-
sor plate and compressor access panel.
5. Remove the fastener holding the coil sections togeth-
er at the return end of the condenser coil. Carefully
separate the outer coil section 3 to 4 in. from the in-
ner coil section. See Fig. 14.
C08207
Fig. 14
−
Separating Coil Sections
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
7. Secure the inner and outer coil rows together with a
field
−
supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Install the coil corner post and replace all
screws.
EVAPORATOR COILS
The evaporator coil uses the traditional round- tube,
plate-fin (RTPF) technology. Tube and fin construction
consists of various optional materials and coatings (see
APPENDIX I. MODEL NUMBER NOMENCLATURE).
Coils are multiple-row. On two-compressor units, the
evaporator coil is a face split design, meaning the two
refrigerant circuits are independent in the coil. The bottom
portion of the coil will always be circuit A, with the top of
the coil being circuit B.
Содержание 580J D17
Страница 80: ...80 APPENDIX IV WIRING DIAGRAMS cont C160041 Fig 72 580J D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 81: ...81 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 73 580J D17 D28 Power Diagram 208 230 3 60 ...
Страница 82: ...82 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 74 580J D17 D28 Power Diagram 460 3 60 ...
Страница 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 75 580J D17 D28 Power Diagram 575 3 60 ...
Страница 84: ...84 APPENDIX IV WIRING DIAGRAMS cont C160050 Fig 76 580J D17 D28 Control Diagram with Perfect Humidity ...
Страница 86: ...86 APPENDIX IV WIRING DIAGRAMS cont C160047 Fig 78 580J D17 D28 Power Diagram 460 3 60 with Perfect Humidity ...
Страница 87: ...87 APPENDIX IV WIRING DIAGRAMS cont C160048 Fig 79 580J D17 D28 Power Diagram 575 3 60 with Perfect Humidity ...
Страница 88: ...88 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 80 RTU OPEN Wiring Diagram ...
Страница 89: ...89 APPENDIX IV WIRING DIAGRAMS cont C160045 Fig 81 RTU OPEN Wiring Diagram with Perfect Humidity ...