25
SEN
J20-1
J20-2
SEN
SET
Jumper
J20-3
SET
C08461
Fig. 34 -- RTU--MP T--56 Sensor Connections
Connect T--59 -- The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 35
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU--MP J20--1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
OR
SET
SEN
OPB
COM- PWR+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR
WIRING
POWER
WIRING
BRN (COM)
NOTE: Must use a separate isolated transformer.
C07132
Fig. 35 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer controls —
Outdoor Air Enthalpy Control (PNO 33CSENTHSW) --
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 36.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 36. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
7
ESL
CTB
ECON
LOW
GND
24V
Enthalpy
Switch
GRA
BLK
RED
Factory Wiring Harness
ECONO
MOTOR
C09026
Fig. 36 -- Enthalpy Switch (33CSENTHSW) Connections
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
ESL
LOW
GND
24V
GRA
BLK
RED
ECONO
MOTOR
–
4-20
Main
+
VDC
Out
–
4-20 Main
Out
+
24-36
VDC In
C09027
Fig. 37 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
2. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (--) spade connector on the return air en-
thalpy sensor and the (--) terminal on the enthalpy
controller.
580J
***D
Содержание 580J***D series
Страница 3: ...3 C09128 Fig 1 Unit Dimensional Drawing 17 and 20 Size Units 580J D ...
Страница 4: ...4 C09129 Fig 1 Unit Dimensional Drawing 17 and 20 Size Units cont 580J D ...
Страница 5: ...5 C09130 Fig 2 Unit Dimensional Drawing 24 and 28 Size Units 580J D ...
Страница 9: ...9 C09052 Fig 5 Roof Curb Details 17 and 20 Size Units 580J D ...
Страница 10: ...10 C09100 Fig 6 Roof Curb Details 24 and 28 Size Units 580J D ...
Страница 22: ...22 C09115 Fig 29 RTU MP System Control Wiring Diagram 580J D ...