To wire in the field:
• J5-8 = 24 VAC source for dry contact
• J5-7 = Signal input
Smoke Detector/Fire Shutdown (FSD) — This control is in-
stalled on 580J units equipped with factory-installed Smoke
Detector(s). The smoke detector controller implements the unit
shutdown through its NC contact set connected to the unit’s
CTB input. The FSD function is initiated via the smoke detec-
tor’s Alarm NO contact set. The RTU Open controller commu-
nicates the smoke detector’s tripped status to the BAS building
control. See Fig. 43 and 44, the RTU Open System Control
wiring schematics.
The Fire Shutdown Switch configuration, MENU
Con-
fig
Inputs
input 5, identifies the normally open status of
this input when there is no fire alarm.
Connecting Discrete Inputs
Filter Status —
The filter status accessory is a field-
installed accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status by setting MENU
Config
Inputs
input 3, 5,
8, or 9 to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of installa-
tion. Refer to Fig. 42-44 for wire terminations at J5.
Fan Status —
The fan status accessory is a field-installed ac-
cessory. This accessory detects when the indoor fan is blowing
air. When installing this accessory, the unit must be configured
for fan status by setting MENU
Config
Inputs
input 3, 5,
8, or 9 to Fan Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of installa-
tion. Refer to Fig. 42 and Fig. 43 or 44 for wire terminations at
J5.
Remote Occupancy —
The remote occupancy accessory is a
field-installed accessory. This accessory overrides the unoccu-
pied mode and puts the unit in occupied mode. When installing
this accessory, the unit must be configured for remote occupan-
cy by setting MENU
Config
Inputs
input 3, 5, 8, or 9 to
Remote Occupancy and normally open (N/O) or normally
closed (N/C).
Also set MENU
Schedules
occupancy source to DI on/
off. Input 8 or 9 is recommended for easy of installa-
tion. Refer to Fig. 42 and Table 25 for wire terminations at J5.
Power Exhaust (output) —
The relay used by the RTU Open
board to control power exhaust is a dry contact which means it
does not have 24vac. This 24vac must be connected to the relay
to allow it to operate the power exhaust relay in the PE acces-
sory. A 24vac source must be provided to J11-2 on the RTU
Open control board. This can be provided by the unit’s trans-
former from various sources. The “R” terminal on the unit’s
low voltage terminal board (LVTB) is a logical source. Refer to
Fig. 42-44 for wire terminations at J11.
RTU OPEN COMMUNICATION WIRING-PROTOCOLS
General — Protocols are the communication languages spoken
by control devices. The main purpose of a protocol is to com-
municate information in the most efficient method possible.
Different protocols exist to provide different kinds of informa-
tion for different applications. In the BAS application, many
different protocols are used, depending on manufacturer. Proto-
cols do not change the function of a controller; just make the
front end user different.
The RTU Open can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the board’s
network address. See Fig. 57 and 58 for protocol switch set-
tings and address switches. The third party connection to the
RTU Open is through plug J19. See Fig. 59 for wiring.
NOTE: Power must be cycled after changing the SW1-3
switch settings.
Contact your Bryant applications engineer for more detailed
information on protocols, 3rd party wiring, and networking.
Fig. 57 — RTU Open SW3 Dip Switch Settings
UNU
S
ED
(OFF)
(ON)
COMM
OPTION
PORT
S
ET TO M
S
TP
(MA
S
TER)
S
ET TO
38
.4k
BAUD
PROTOCOL
S
ELECTOR DIP
S
WITCHE
S
Baud Rate Selection
BAUD RATE
DS2
DS1
9,600
OFF
OFF
19,200
ON
OFF
38,400
OFF
ON
76,800
ON
ON
SW3 PROTOCOL SELECTION
LEGEND
NOTE: BACnet MS/TP SW3 example shown.
PROTOCOL
DS8
DS7
DS6
DS5
DS4
DS3
DS2
DS1
BACnet MS/TP (Master)
Unused
OFF
OFF
OFF
ON
OFF
Select Baud
Select Baud
Modbus (Slave)
Unused
OFF
OFF
ON
ON
OFF
Select Baud
Select Baud
N2 Slave
Unused
OFF
OFF
OFF
ON
ON
OFF
OFF
LonWorks
Unused
ON
ON
OFF
ON
OFF
OFF
ON
DS
— DIP Switch
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......