Fig. 31 — Low-Voltage Connections
Unit Without Thru-Base Connection Kit — Pass the ther-
mostat control wires through the hole provided in the corner
post; then feed the wires through the raceway built into the
corner post to the control box. Pull the wires over to the ter-
minal strip on the upper-left corner of the Controls Connec-
tion Board. See Fig. 32.
NOTE: If thru-the-bottom connections accessory is used,
refer to the accessory installation instructions for informa-
tion on routing power and control wiring.
Fig. 32 — Field Control Wiring Raceway
Heat Anticipator Settings — Set heat anticipator settings at
0.14 amp for the first stage and 0.14 amp for second-stage heat-
ing, when available.
Perfect Humidity
™
Control Connections
Perfect Humidity – Space RH Controller
NOTE: Perfect Humidity is a factory installed option which
is available for 07 models only.
The Perfect Humidity dehumidification system requires a
field-supplied and installed space relative humidity control de-
vice. This device may be a separate humidistat control (contact
closes on rise in space RH above control setpoint) or a combi-
nation thermostat-humidistat control device such as Bryant’s
Edge
®
Pro Thermidistat with isolated contact set for dehumidi-
fication control.
To Connect the field-installed humidistat (See Fig. 33)
1. Route the humidistat 2-conductor cable (field-sup-
plied) through the hole provided in the unit corner
post.
2. Feed wires through the raceway built into the corner post
(see Fig. 32) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3. Use wire nuts to connect humidistat cable to two PINK
leads in the low–voltage wiring as shown in Fig. 34.
To connect the Edge Programmable Thermidistat
(T6-PRH01-A):
(See Fig. 35)
1. Route the Edge Programmable Thermostat multi-
conductor cable (field-supplied) through the hole
provided in the unit corner post.
2. Feed wires through the raceway built into the corner post
(see Fig. 32) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3. The Edge Programmable Thermostat has dry contacts at
terminals D1 and D2 for dehumidification operation (see
Fig. 35). The dry contacts must be wired between CTB
terminal R and the PINK lead to the LTLO switch with
field-supplied wire nuts. Refer to the installation instruc-
tions included with the Bryant Edge Programmable Ther-
midistat device for more information.
Fig. 33 — Accessory Field-Installed Humidistat
X
C
G
W2
C
W2
G
W1
O/B/Y2
Y2
R
W1
R
Y1
Y1
T
H
E
R
M
O
S
T
A
T
(Note 1)
(Note 2)
Centr
a
l
Termin
a
l
Bo
a
rd
Typic
a
l
Thermo
s
t
a
t
Connection
s
NOTE
S
:
1. Typic
a
l m
u
lti-f
u
nction m
a
rking. Follow m
a
n
u
f
a
ct
u
rer
’s
config
u
r
a
tion
in
s
tr
u
ction
s
to
s
elect Y2. Do not config
u
re for O o
u
tp
u
t.
2. Y2 to Y2 connection re
qu
ired on
s
ingle-
s
t
a
ge cooling
u
nit
s
when
integr
a
ted economizer f
u
nction i
s
de
s
ired.
Field-Wiring
RACEWAY
HOLE IN END PANEL (HIDDEN)
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......