Step 7 — Convert to Horizontal and Connect
Ductwork (when required) —
Unit is shipped in the ver-
tical duct configuration. Unit without factory-installed econo-
mizer or return air smoke detector option may be field-convert-
ed to horizontal ducted configuration. To convert to horizontal
configuration, remove screws from side duct opening covers
and remove covers. Using the same screws, install covers on
vertical duct openings with the insulation-side down. Seals
around duct openings must be tight. See Fig. 7.
Fig. 7 — Horizontal Conversion Panels
Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges. In-
sulate and weatherproof all external ductwork, joints, and roof
or building openings with counter flashing and mastic in accor-
dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
Step 8 — Install Outside Air Hood
ECONOMIZER AND TWO POSITION DAMPER HOOD
PACKAGE REMOVAL AND SETUP — FACTORY
OPTION
NOTE: Economizer and two position damper are not avail-
able as factory installed options for single phase (-J voltage
code) models.
1. The hood is shipped in knock-down form and must be
field assembled. The indoor coil access panel is used
as the hood top while the hood sides, divider and filter
are packaged together, attached to a metal support tray
using plastic stretch wrap, and shipped in the return air
compartment behind the indoor coil access panel. The
hood assembly’s metal tray is attached to the basepan
and also attached to the damper using two plastic tie-
wraps.
2. To gain access to the hood, remove the filter access panel.
See Fig. 8.
Fig. 8 — Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the base-
pan and remove. Locate and cut the (2) plastic tie-wraps
securing the assembly to the damper. (See Fig. 9.) Be
careful to not damage any wiring or cut tie-wraps secur-
ing any wiring.
Fig. 9 — Economizer and Two-Position Damper Hood
Parts Location
4. Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps out-
lined in
Economizer Hood and Two–Position Hood
, be-
low.
ECONOMIZER HOOD AND TWO-POSITION HOOD
NOTE: If the power exhaust accessory is to be installed on
the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the
power exhaust hood assembly.
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
REMOVABLE HORIZONTAL
S
UPPLY DUCT OPENING COVER
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
FILTER ACCESS PANEL
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......