background image

III. COMPLETE REFRIGERANT PIPING CONNECTIONS

Suction connection is sweat with plastic cap; liquid connec-
tion is sweat with plastic cap. Refer to Table 2 for the proper
line sizes. Follow standard piping practices.

Table 2 — Refrigerant Piping Sizes

LINEAR LENGTH OF PIPING — ft

UNIT
575A

0-25

25-50

50-75

75-100

Line Size (in. OD)

L

S

L

S

L

S

L

S

090

1

2

1

1

8

5

8

1

1

8

5

8

1

3

8

3

4

1

3

8

LEGEND

L — Liquid Line

OD — Outside Diameter

S — Suction Line

NOTES:
1. Pipe sizes are based on a 2° F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length shown for each

column, plus a 50% allowance for fittings.

3. Charge units with R-22 in accordance with unit installation

instructions.

A. Size Refrigerant Lines

Consider length of piping required between 575A unit and
524A-H unit, amount of liquid lift, and compressor oil re-
turn. See Table 3. Refer to 524A installation instructions for
additional information.

Table 3 — Liquid Line Data

UNIT
575A

MAX

ALLOWABLE

LIQUID LIFT (ft)

LIQUID LINE

090

Heating

Cooling

Max Allowable
Pressure Drop

(psi)

Max Allowable

Temp Loss

(F)

75

65

7

2

LEGEND

db — Dry Bulb
wb — Wet Bulb

NOTES:
1. The liquid lift in cooling mode is based on 80/67 F (db/wb ) entering

indoor-air temperature and a 95 F outdoor-air temperature, with R-22
refrigerant, at an indoor airflow of 3000 cfm.

2. The liquid lift in heating mode is based on 70/60 F (db/wb) entering

indoor-air temperature and a 47/43 F (db/wb) outdoor-air tempera-
ture, with R-22 refrigerant, at an indoor airflow of 3000 cfm.

B. Filter Drier and Moisture Indicator

See Fig. 5. The filter drier is factory supplied and field-
installed in the liquid line. Moisture indicator is field-
supplied and should be installed just after liquid line shutoff
valve. Do not use a receiver; there is none provided with unit
and one should not be used.

NOTE:

Unit is shipped with R-22 holding charge. System pres-

sure must be relieved before removing caps. Recover refrig-
erant prior to brazing.

Pass nitrogen or other inert gas through piping while braz-
ing to prevent formation of copper oxide.

C. Liquid Line Solenoid Valve

A field-supplied liquid line solenoid valve (LLSV) is recom-
mended when piping system length exceeds 75 feet. The LLSV
must be of the biflow type, suited for use in heat pump
systems.

NOTE:

Part number EF23JS214 (Sporlan model CB14S2,

5

8

-in. ODF/

7

8

-in. ODM) is recommended and is available from

the Replacement Components Division. This solenoid re-
quires field-supplied Sporlan MKC-2 coils.

Wire the solenoid in parallel with the compressor contactor
coil.

Install the LLSV near the outdoor unit. The flow arrow must
be pointed toward the outdoor unit.

D. Safety Relief

A fusible plug is located on top of the accumulator. See Fig. 6.
Note that all safety relief components are factory installed.
Do not cap fusible plug. If local code requires additional
safety device(s), install as directed.

E. Suction Piping at Indoor Coil and TXV Sensing Bulb
Location

Suction piping must be designed so that refrigerant is thor-
oughly mixed after it leaves the indoor coil suction header.
The thermostatic expansion valve (TXV) sensing bulb must
also be correctly located. This ensures that the TXV sensing
bulb receives reliable readings. Install the suction piping as
follows:

1. Install a minimum of two 90-degree elbows upstream of

the TXV bulb location.

2. Locate the TXV bulb on a vertical riser where possible.

If a horizontal location is necessary, secure the bulb at
approximately the 4 o’clock position or the 8 o’clock po-
sition. See Fig. 7.

3. Make sure that the piping system has no inherent oil

traps, and that the piping layout does not allow oil to
migrate into an idle indoor coil.

4. Complete refrigerant piping from indoor coil to outdoor

coil before opening liquid and suction lines at the 575A
unit. See Tables 1 and 2 for piping selection data.

—4—

Содержание 575A

Страница 1: ...al installation requirements WARNING Before installing or servicing system al ways turn off main power to system There may be more than one disconnect switch Electrical shock can cause personal injury INSTALLATION The 575A090 unit uses a semi hermetic compressor See Table 1 for physical data The 575A090 outdoor unit is approved for use only with the 524A H090 indoor unit Use only approved indoor u...

Страница 2: ...arance is optional c Overhead 60 in 1524 mm to assure proper outdoor fan operation d Between units control box side 42 in 1067 mm per National Electrical Code NEC e Between unit and ungrounded surfaces control box side 36 in 914 mm per NEC f Between unit and block or concrete walls and other grounded surfaces control box side 42 in 1067 mm per NEC 5 With the exception of the clearance for the outd...

Страница 3: ...red if top crating is left on unit All panels must be in place when rigging See Fig 3 As further protection for coil faces plywood sheets may be placed against sides of unit behind cables Run cables to a central suspension point so that angle from the horizontal plane is not less than 45 degrees Raise and set unit down carefully If it is necessary to roll unit into position mount unit on rails usi...

Страница 4: ...ed NOTE Unit is shipped with R 22 holding charge System pres sure must be relieved before removing caps Recover refrig erant prior to brazing Pass nitrogen or other inert gas through piping while braz ing to prevent formation of copper oxide C Liquid Line Solenoid Valve A field supplied liquid line solenoid valve LLSV is recom mended when piping system length exceeds 75 feet The LLSV must be of th...

Страница 5: ...n are general points of connection guides only and are not intended for or to include all details for a spe cific installation 4 Liquid line solenoid valve solenoid drop control is recom mended to prevent refrigerant migration to the compressor A bi flow type solenoid valve is required 5 Filter drier must be of the biflow type suitable for heat pump duty 6 Internal factory supplied TXV and bypass ...

Страница 6: ... for field wire connections Use factory supplied splices or UL approved copper aluminum connector When installing units provide a disconnect per NEC All field wiring must comply with NEC and local requirements Install field wiring as follows 1 Install conduit through side panel openings 2 Install power lines to connections as shown in Fig 8 Wrap connections with electrical tape Voltage to compress...

Страница 7: ...balance 100 457 1 53 This amount of phase imbalance is satisfactory as it is below the maximum allowable 2 IMPORTANT If the supply voltage phase imbalance is more than 2 contact your local electric utility company immediately Table 5 Accessory Electric Heater Data UNIT 524A H NOMINAL kW V PH HZ HEATER PART NO HEATER AMPS MCA MOCP 090 5 240 3 60 CAELHEAT001A00 12 0 25 6 30 480 3 60 CAELHEAT002A00 6...

Страница 8: ...operate for at least 24 hours be fore start up 6 Note that compressor oil level is visible in the sight glass 7 Check for leaks in refrigerant system by using soap bubbles and or electronic leak detector 8 Check voltage imbalance as shown in Table 4 Note 2 9 Check that both outdoor and indoor units are properly mounted in accordance with installation instructions and applicable codes II EVACUATE A...

Страница 9: ...lows through from the liquid header side outlets into the transfer header where it flows upward 4 Refrigerant leaves the transfer header through side con nections in 4 locations and enters the middle coil cir cuits 4 coil circuits above check valve A 5 Refrigerant leaves the 4 middle coil circuits and enters the top portion of vapor header The refrigerant moves up to the top 2 remaining coil circu...

Страница 10: ... Observe that compressor outdoor fan indoor fan motor and electric heaters if equipped start Observe that heating cycle shuts down when control set ting is satisfied 4 When using an automatic changeover room thermostat place both SYSTEM and FAN switches in AUTO posi tions Observe that unit operates in Cooling mode when temperature control is set to call for cooling below room temperature and unit ...

Страница 11: ... place coil corner post between top panel and side panel See Fig 15 4 Remove bracket holding coil sections together at return end of outdoor coil Carefully separate the outer coil sec tion 3 to 4 in from the inner coil section See Fig 16 5 Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and de bris Clean the outer surfaces with a stiff brush in...

Страница 12: ... unit 2 Remove refrigerant from system using refrigerant re moval methods described in Refrigerant Service Tech niques manual 3 Disconnect compressor wiring at compressor terminal box Disconnect high pressure switch 4 Remove bolts from discharge service valve and suction flange CAUTION Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to se...

Страница 13: ...TROUBLESHOOTING CHART HEATING CYCLE LEGEND N C Normally Closed 13 ...

Страница 14: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND TXV Thermostatic Expansion Valve Copyright 1995 Carrier Corporation CATALOG NO BDP 3357 502 ...

Страница 15: ...N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN CONFIRMED Y N PIPING IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED Y N HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR OUTDOOR COIL INDOOR COIL TXV Thermostatic Expansion Valve SOLENOID VALVES FILTER DRIER ...

Страница 16: ...ESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR AIR TEMP LEAVING OUTDOOR AIR TEMP INDOOR ENTERING AIR DB dry bulb TEMP INDOOR ENTERING AIR WB wet bulb TEMP INDOOR LEAVING AIR DB TEMP INDOOR LEAVING AIR WB TEMP COMPRESSOR AMPS L1 L2 L3 NOTES CUT ALONG DOTTED LINE Copyright 1995 Carrier Corporation CATALOG NO BDP 3357 502 CL 2 ...

Отзывы: