81
PERFORMANCE DATA (cont)
COOLING CAPACITIES, STANDARD UNITS (cont)
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 – BF) x (db – 80)
551B120 (10 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator — CFM/BF
3000/0.31
3200/0.34
4000/0.46
5000/0.61
Temp (F) Air Entering Evaporator — Ewb
78
72
67
62
78
72
67
62
78
72
67
62
78
72
67
62
75
TC
152.7
140.3
129.4
115.0
153.1
141.2
130.4
118.1
154.9
145.2
134.0
122.1
158.1
147.5
136.6
125.3
SHC
46.7
65.6
82.2
97.4
47.3
66.7
84.4
101.5
49.8
71.3
93.1
113.5
51.0
77.9
103.7
124.7
kW
7.34
7.35
7.21
7.12
7.54
7.37
7.23
7.13
7.71
7.46
7.31
7.17
8.10
7.51
7.37
7.22
85
TC
150.5
137.7
125.3
110.0
151.5
138.9
126.6
113.6
142.6
130.6
117.7
144.6
133.3
122.3
SHC
44.7
65.0
81.2
95.2
44.9
66.3
83.6
99.7
71.0
92.8
112.0
76.9
103.1
122.2
kW
8.28
8.29
8.13
8.02
8.51
8.32
8.16
8.03
8.40
8.24
8.09
8.45
8.31
8.16
95
TC
147.7
133.8
120.7
103.0
135.1
121.9
107.2
138.8
125.8
112.8
141.7
128.5
118.5
SHC
43.9
63.9
79.6
92.2
65.2
82.0
97.0
70.6
91.5
109.7
76.9
102.5
118.4
kW
9.33
9.33
9.16
8.98
9.35
9.18
9.00
9.44
9.27
9.07
9.51
9.33
9.19
105
TC
128.7
115.4
96.5
129.8
116.6
99.7
133.7
120.3
107.1
136.7
122.8
114.5
SHC
62.3
77.6
89.4
63.6
80.2
93.5
69.4
89.6
106.8
76.0
100.6
114.3
kW
10.46
10.28
10.00
10.47
10.30
10.07
10.57
10.38
10.21
10.66
10.43
10.31
115
TC
123.2
109.1
90.8
124.3
110.3
92.2
127.9
114.4
100.8
130.9
116.8
110.1
SHC
60.4
75.1
86.6
61.9
77.8
90.0
67.6
87.6
100.7
74.6
98.7
109.9
kW
11.66
11.47
11.20
11.68
11.51
11.25
11.77
11.60
11.41
11.89
11.66
11.58
125
TC
117.5
101.8
86.2
118.5
103.0
87.4
121.6
107.1
96.0
124.1
110.3
104.8
SHC
58.5
72.5
84.5
60.0
75.0
87.3
65.8
85.1
96.0
72.5
96.9
104.8
kW
12.99
12.77
12.50
13.02
12.81
12.55
13.10
12.92
12.74
13.19
13.01
12.91
551B150 (12
1
/
2
TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator — CFM/BF
3750/0.08
4300/0.09
5000/0.11
6250/0.13
Temp (F) Air Entering Evaporator — Ewb
72
67
62
72
67
62
72
67
62
72
67
62
75
TC
167.1
154.3
142.0
169.8
157.7
144.8
173.5
160.6
148.4
176.5
164.5
153.3
SHC
82.5
103.5
123.6
85.8
109.7
132.0
90.3
117.7
141.9
98.2
130.7
153.1
kW
9.44
9.18
8.95
9.50
9.26
9.01
9.60
9.33
9.07
9.68
9.43
9.17
85
TC
162.3
149.3
135.6
165.1
152.5
139.6
168.8
155.3
143.5
172.1
159.2
149.3
SHC
80.9
101.4
120.9
84.4
107.9
129.9
89.6
115.8
139.8
97.6
129.3
149.1
kW
10.49
10.18
9.97
10.55
10.27
10.02
10.67
10.32
10.11
10.75
10.43
10.21
95
TC
156.5
143.7
126.3
159.6
146.8
131.3
162.3
149.8
136.5
166.5
153.2
144.5
SHC
79.1
99.5
116.5
83.0
106.1
126.0
87.6
114.2
135.8
95.8
127.7
144.4
kW
11.60
11.30
11.01
11.69
11.39
11.10
11.75
11.47
11.20
11.87
11.56
11.35
105
TC
150.0
136.2
115.7
153.0
139.3
120.9
155.6
142.5
128.5
158.8
145.9
138.8
SHC
76.5
96.7
111.2
80.8
103.5
120.0
85.7
112.3
128.4
93.6
125.9
138.7
kW
12.76
12.42
12.09
12.83
12.52
12.20
12.91
12.62
12.32
12.96
12.72
12.52
115
TC
141.8
122.2
104.4
144.3
126.1
110.8
147.7
129.4
118.9
150.7
135.2
130.1
SHC
73.6
91.2
104.2
77.9
98.5
110.8
83.4
107.3
118.4
91.8
121.9
129.9
kW
13.85
13.55
13.22
13.94
13.64
13.35
14.05
13.73
13.50
14.14
13.86
13.70
125
TC
132.5
108.6
93.9
134.8
111.4
100.7
137.6
114.4
106.6
140.3
122.9
120.1
SHC
70.9
85.7
93.8
74.9
92.9
100.7
80.2
101.4
106.5
89.0
116.3
120.1
kW
15.04
14.66
14.44
15.14
14.75
14.55
15.23
14.85
14.72
15.29
14.94
14.84
BF
—
Bypass Factor
Edb —
Entering Dry Bulb
Ewb —
Entering Wet Bulb
kW
—
Compressor Motor Power Input
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
t
ldb
= t
edb
–
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of
air leaving indoor coil (h
lwb
)
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
0TF
Q
0
04-
01
2
5
5
1
B
03
6-
15
0
Содержание 551A
Страница 14: ...14 TYPICAL WIRING SCHEMATIC Single Fan Units Sizes 036 073 ...
Страница 16: ...16 TYPICAL WIRING SCHEMATIC Sizes 155 300 ...
Страница 29: ...29 BASE UNIT DIMENSIONS 558F036 072 0TFQ004 012 558F036 150 ...
Страница 30: ...30 BASE UNIT DIMENSIONS 558F073 0TFQ004 012 558F036 150 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 558F090 102 120 150 0TFQ004 012 558F036 150 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 558F091 121 0TFQ004 012 558F036 150 ...
Страница 74: ...74 BASE UNIT DIMENSIONS 551B036 072 0TFQ004 012 551B036 150 ...
Страница 75: ...75 BASE UNIT DIMENSIONS 551B090 150 0TFQ004 012 551B036 150 ...
Страница 133: ...133 BASE UNIT DIMENSIONS 558F180 210 0TFQ004 012 558F180 300 ...
Страница 134: ...134 BASE UNIT DIMENSIONS 558F240 0TFQ004 012 558F180 300 ...
Страница 135: ...135 BASE UNIT DIMENSIONS 558F300 0TFQ004 012 558F180 300 ...
Страница 153: ...153 BASE UNIT DIMENSIONS 551A155 180 0TFQ004 012 551A155 180 ...