ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

 

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes the chance of liquid slugging. 

Usage Guideline:

Required in low ambient applications.
Required in long line applications.
Suggested in all commercial applications.

6.

 

Evaporator Freeze Thermostat

 

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7.

 

Liquid-Line Solenoid Valve (LLS)  

 

This device serves two purposes. It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor oper-
ation. It maintains a column of refrigerant liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle
refrigerant migration. 

 

Note:

 

 When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in air conditioner long line applications with a piston indoor metering device to prevent off cycle refrigerant migration. A hard shut 
off TXV can be used instead of an LLS in single flow air conditioner applications. See Long Line Application Guideline.

8.

 

MotorMaster®—Low-Ambient Controller

 

A fan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ±
10°F (37.8°C ± –12°C).

Usage Guideline:

A MotorMaster®—Low Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications.

9.

 

Outdoor Air Temperature Sensor

 

Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Bryant thermostats listed in this publication.

10.

 

Sound Hood

 

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft to quiet areas—bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft apart.

11.

 

Support Feet

 

Four stick-on plastic feet that raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing
corrosion.

Usage Guideline:

Suggested in the following applications:

Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.

12.

 

Thermostatic Expansion Valve (TXV) 

 

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.

 

Note:

 

 When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings. 
Hard shut off TXV or LLS required in air conditioner long line applications
Required for use on all zoning systems.

13.

 

Time-Delay Relay 

 

An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.

 

Note:

 

 Most indoor unit controls include this feature.  For those that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory..

 

A-WTD. SOUND POWER (dBA)

 

NOTE: 

 

Tested in accordance with ARI standard 270.95. (Not listed with ARI.)

 

UNIT SIZE-

SERIES

STANDARD 

RATING

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

125

250

500

1000

2000

4000

8000

 

024-G

72

61.0

60.5

63.5

66.5

63.0

57.0

49.5

030-F

70

57.5

60.0

64.0

66.0

62.0

58.5

53.5

036-F, G

72

58.5

60.5

65.0

65.0

62.0

59.0

52.5

042-F

72

55.5

62.5

66

65.5

63.5

62.0

55.5

048-F

76

62.0

67.5

70.0

69.5

67.5

66.0

60.5

060-H

78

66.0

68.0

71.5

72.5

70.5

65.0

59.5

Содержание 550A

Страница 1: ...erant the correct choice when considering long term serviceability Highly Reliable Performance Is delivered through the supe rior design of the system and componentry The reliability of the 550A models has been proven to provide the lowest inci dence of warranty service of any product in the Bryant family in the past three years of service Long term reliability is assured through the use of both h...

Страница 2: ...DIA HOLE WITH 1 1 8 DIA KNOCKOUT AND 1 3 8 DIA KNOCKOUT 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 C F N G A B M DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 024 G 27 13 16 30 33 5 1 16 9 11 16 15 15 16 22 3 8 5 8 8 3 16 17 19 3 4 13 2 15 16 26 x 32 030 F 27 13 16 30 33 5 1 16 9 11 16 15 15 16 22 3 8 3 4 8 3 16 18 1 2 19 3 4 13 2 15 16 26 x ...

Страница 3: ... RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT REGISTERED ISO 9001 2000 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY STAR partner Bryant Heating Cooling Systems has determined that this prod uct meets the ENERGY STAR guidelines for energy efficiency Refer to the combination ratings in the Product Data Sheet for s...

Страница 4: ...tector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA Start Assist PTC Type Standard KAACS0201PTC TXV Hard Shutoff KSATX0201PUR KSATX0301PUR Piston Body KSAPX0101PIS Filter Drier Suction Line KH45LG140 RCD Evaporator Freeze Thermostat KAAFT0101AAA Liquid Line Solenoid Valve KAALS0201LLS Winter Start Control KAAWS0101AAA Low Ambient Pressure Switch KSALA03...

Страница 5: ...ype Scroll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 8 75 10 13 11 50 CONDENSER COIL FAN Coil Face Area Sq Ft 18 2 18 2 18 2 Fins per In Rows Circuits 25 1 3 20 2 5 20 2 5 Fan Motor HP PSC RPM 1 5 825 1 4 1125 1 4 1125 Volts Hertz Phase 208 230 60 1 Condenser Airflow CFM 2800 3400 3400 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAAC...

Страница 6: ...evice which gives a soft boost to the reciprocating compressor at each start up Usage Guideline Suggested in installations with marginal power supply DESCRIPTION ACCESSORY Evolution Control Deluxe 7 Day Programmable Wall mounted system control SYSTXBBUID01 Evolution Zone Control Deluxe Zoning 7 Day Programmable Wall mounted control for a multi zone system SYSTXBBUIZ01 Evolution 4 Zone Damper Contr...

Страница 7: ... to enable special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Bryant thermostats listed in this publication 10 Sound Hood Wraparound sound reducing cover for the compressor Reduces the sound level by about 2 dBA Usage Guideline Suggested when unit is installed closer than 15 ft to quiet areas bedrooms etc Suggested when unit is installed between two house...

Страница 8: ...14 00 12 35 CC5A CD5AW024 22 400 TDR 14 00 14 00 12 20 CC5A CD5AW030 22 800 TDR 14 00 14 00 12 35 CE3AA024 22 400 TDR 14 00 14 00 12 25 CE3AA030 22 800 TDR 14 00 14 00 12 45 CK3BA024 22 400 TDR 14 00 14 00 12 50 CK3BA030 22 800 TDR 14 00 14 00 12 55 CK5A CK5BA024 22 400 TDR 14 00 14 00 12 35 CK5A CK5BA030 22 800 TDR 14 00 14 00 12 45 CK5A CK5BW024 22 400 TDR 14 00 14 00 12 35 CK5A CK5BW030 22 800 ...

Страница 9: ...CK5A CK5BW024 22 400 TDR 14 00 14 00 12 40 CK5A CK5BW030 22 800 TDR 14 00 14 00 12 50 CK5PW024 22 400 TDR TXV 14 00 12 30 CK5PW030 22 800 TDR TXV 14 00 12 45 COILS 355MAV060100 VARIABLE SPEED FURNACE CC5A CD5AW024 22 400 TDR 14 00 14 00 12 25 CC5A CD5AW030 22 800 TDR 14 00 14 00 12 40 CE3AA024 22 400 TDR 14 00 14 00 12 25 CE3AA030 22 800 TDR 14 00 14 00 12 50 CK3BA024 22 400 TDR 14 00 14 00 12 55 ...

Страница 10: ... 14 00 12 20 CK5PW030 28 600 TDR TXV 13 50 11 80 CK5PW036 29 000 TDR TXV 14 00 12 20 COILS 315 A J AV060110 VARIABLE SPEED FURNACE CC5A CD5AA036 29 000 TDR 14 00 14 00 12 40 CC5A CD5AW030 28 000 TDR 13 50 13 50 12 05 CC5A CD5AW036 29 000 TDR 14 00 14 00 12 45 CE3AA030 28 600 TDR 13 50 13 50 12 15 CE3AA036 29 000 TDR 14 00 14 00 12 30 CK3BA030 28 600 TDR 13 50 13 50 12 20 CK3BA036 29 000 TDR 14 00 ...

Страница 11: ...A B 4 A B N F B C 042 35 000 TDR 13 00 13 00 11 25 F A B 4 A B N F C 036 35 000 TDR 12 50 12 50 11 15 FE4ANF002 35 000 TDR TXV 13 00 11 75 FE4ANF003 35 000 TDR TXV 13 50 12 05 FE4ANF005 36 000 TDR TXV 14 00 12 20 FG3AAA036 35 000 NONE 12 20 12 20 10 95 FK4 C D NF002 35 000 TDR TXV 13 00 11 75 FK4 C D NF003 35 000 TDR TXV 13 50 12 05 FK4 C D NF005 36 000 TDR TXV 14 00 12 20 FV4 A B NF002 35 000 TDR...

Страница 12: ...AW036 35 000 TDR 14 00 14 00 12 10 CC5A CD5AW042 35 000 TDR 14 00 14 00 12 25 CE3AA036 35 000 TDR 13 50 13 50 12 00 CE3AA042 35 000 TDR 14 00 14 00 12 30 CK3BA042 35 000 TDR 14 00 14 00 12 30 CK5A CK5BA042 35 000 TDR 14 00 14 00 12 30 CK5A CK5BT042 35 000 TDR 14 00 14 00 12 30 CK5A CK5BW036 35 000 TDR 14 00 14 00 12 15 CK5PA042 35 000 TDR TXV 14 00 12 25 CK5PT042 35 000 TDR TXV 14 00 12 25 CK5PW03...

Страница 13: ... 13 50 13 50 12 00 CK5A CK5BW036 35 000 TDR 13 50 13 50 11 85 CK5PA042 35 000 TDR TXV 13 50 12 00 CK5PT042 35 000 TDR TXV 13 50 12 00 CK5PW036 35 000 TDR TXV 13 50 11 85 036 G CC5A CD5AA036 35 000 NONE 13 00 13 00 11 25 CC5A CD5AA042 35 000 NONE 13 00 13 00 11 25 CC5A CD5AW036 35 000 NONE 13 00 13 00 11 25 CC5A CD5AW042 34 600 NONE 12 50 12 50 11 10 CE3AA036 34 600 NONE 12 50 12 50 11 15 CE3AA042 ...

Страница 14: ...11 90 CE3AA042 34 600 TDR 14 00 14 00 12 15 CK3BA036 34 600 TDR 14 00 14 00 12 10 CK3BA042 34 600 TDR 14 00 14 00 12 15 CK5A CK5BA036 34 600 TDR 14 00 14 00 12 10 CK5A CK5BA042 34 600 TDR 14 00 14 00 12 15 CK5A CK5BE042 34 600 TDR 14 00 14 00 12 20 CK5A CK5BT036 34 600 TDR 14 00 14 00 12 10 CK5A CK5BT042 34 600 TDR 14 00 14 00 12 15 CK5A CK5BW036 34 600 TDR 14 00 14 00 12 15 CK5PA036 34 600 TDR TX...

Страница 15: ...11 80 CK3BA042 34 600 TDR 13 50 13 50 11 85 CK5A CK5BA036 34 600 TDR 13 50 13 50 11 80 CK5A CK5BA042 34 600 TDR 13 50 13 50 11 85 CK5A CK5BE042 34 600 TDR 13 50 13 50 11 90 CK5A CK5BT036 34 600 TDR 13 50 13 50 11 80 CK5A CK5BT042 34 600 TDR 13 50 13 50 11 85 CK5A CK5BW036 34 600 TDR 13 50 13 50 11 85 CK5PA036 34 600 TDR TXV 13 50 11 75 CK5PA042 34 600 TDR TXV 13 50 11 85 CK5PE042 34 600 TDR TXV 13...

Страница 16: ...NONE 13 00 13 00 11 30 CK5PA042 40 500 TXV 13 00 11 20 CK5PA048 40 500 TXV 13 00 11 30 CK5PE042 39 500 TXV 12 50 11 30 CK5PT042 40 500 TXV 13 00 11 20 CK5PT048 40 500 TXV 13 00 11 30 CK5PW048 40 500 TXV 13 00 11 30 F A B 4 A B N F B C 042 40 500 TDR 12 50 12 50 11 25 F A B 4 A B N F B C 048 41 000 TDR 13 00 13 00 11 45 FE4ANB006 41 500 TDR TXV 14 00 12 90 FE4ANF003 39 500 TDR TXV 13 00 11 95 FE4AN...

Страница 17: ... 12 05 CC5A CD5AW042 40 000 TDR 13 50 13 50 11 90 CC5A CD5AW048 40 500 TDR 14 00 14 00 12 20 CD5AA048 40 500 TDR 14 00 14 00 12 20 CE3AA042 40 500 TDR 13 50 13 50 12 05 CE3AA048 41 000 TDR 13 50 13 50 12 10 CK3BA042 40 500 TDR 13 50 13 50 12 05 CK3BA048 40 500 TDR 14 00 14 00 12 20 CK5A CK5BA042 40 500 TDR 13 50 13 50 12 05 CK5A CK5BA048 40 500 TDR 14 00 14 00 12 20 CK5A CK5BT042 40 500 TDR 13 50 ...

Страница 18: ... 46 000 NONE 13 00 13 00 11 50 CD5PX060 47 500 TXV 13 50 11 90 CE3AA048 46 500 NONE 13 00 13 00 11 65 CE3AA060 47 000 NONE 13 00 13 00 11 85 CF5AA048 46 000 NONE 12 50 12 50 11 55 CK3BA048 46 000 NONE 13 00 13 00 11 55 CK3BA060 46 500 NONE 13 00 13 00 11 65 CK5A CK5BA048 46 000 NONE 13 00 13 00 11 55 CK5A CK5BA060 46 500 NONE 13 00 13 00 11 65 CK5A CK5BT048 46 000 NONE 13 00 13 00 11 55 CK5A CK5BT...

Страница 19: ...DR TXV 13 50 12 10 CK5PX060 47 500 TDR TXV 14 00 12 70 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CC5A CD5AA060 46 000 TDR 13 50 13 50 12 25 CC5A CD5AC048 45 000 TDR 13 50 13 50 12 10 CC5A CD5AW048 46 000 TDR 13 50 13 50 12 25 CC5A CD5AW060 47 000 TDR 14 00 14 00 12 55 CD5AA048 46 000 TDR 13 50 13 50 12 25 CD5PX060 47 500 TDR TXV 14 00 12 65 CE3AA048 46 500 TDR 13 50 13 50 12 20 CE3AA060 47 000...

Страница 20: ... TDR 13 00 13 00 11 60 CK3BA060 46 500 TDR 13 00 13 00 11 80 CK5A CK5BA060 46 500 TDR 13 00 13 00 11 80 CK5A CK5BT060 46 500 TDR 13 00 13 00 11 80 CK5A CK5BW048 46 000 TDR 13 00 13 00 11 60 CK5A CK5BX060 47 500 TDR 13 50 13 50 12 15 CK5PA060 46 500 TDR TXV 13 00 11 80 CK5PT060 46 500 TDR TXV 13 00 11 80 CK5PW048 46 000 TDR TXV 13 00 11 60 CK5PX060 47 500 TDR TXV 13 50 12 15 UNIT SIZE SERIES INDOOR...

Страница 21: ...6135 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 12 50 10 90 CD5PX060 58 000 TDR TXV 13 00 11 30 CE3AA060 58 000 TDR 13 00 11 30 CK3BA060 57 500 TDR 13 00 11 25 CK5A CK5BA060 57 500 TDR 13 00 11 25 CK5A CK5BT060 57 500 TDR 13 00 11 25 CK5A CK5BX060 58 500 TDR 13 00 11 40 CK5PA060 57 500 TDR TXV 13 00 11 25 CK5PT060 57 500 TDR TXV 13 00 11 25 CK5PX060 58 500 TDR TXV 13 00 11 40 COILS 315 A J AV...

Страница 22: ...iency Ratio TDR Time Delay Relay TXV Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for electric air conditioners Ratings for other com binations are determined under DOE computer simulation procedu...

Страница 23: ... 25 31 13 85 2 11 24 19 13 62 2 37 22 71 13 17 2 64 20 99 12 62 2 95 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 0 99 1 00 CK3BA 024 0 97 0 88 030 1 00 1 00 030 0 99 0 89 CC5A CD5AW 024 0 99 1 00 CK5A CK5BA 024 0 97 0 89 030 1 00 1 00 030 0 99 0 90 CE3AA 024 0 99 0 99 CK5...

Страница 24: ...07 19 80 19 80 2 32 18 58 18 58 2 59 17 27 17 27 2 87 67 25 15 17 80 1 64 24 64 18 20 1 85 23 38 18 01 2 09 21 84 17 50 2 35 20 17 16 86 2 63 18 42 16 15 2 91 72 25 90 13 52 1 65 25 81 13 75 1 87 25 31 13 85 2 11 24 19 13 62 2 37 22 71 13 17 2 64 20 99 12 62 2 95 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity ...

Страница 25: ... 25 1 25 1 2 49 23 8 23 8 2 75 21 2 21 2 3 04 57 29 5 29 5 1 85 28 2 28 2 2 04 26 6 26 6 2 25 25 3 25 3 2 49 23 5 23 5 2 75 21 1 21 1 3 04 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 CK5A CK5BT 036 1 00 0 93 036 1 00 1 00 CK5A CK5BW 030 0 97 0 92 CC5A CD5AW 030 ...

Страница 26: ...33 0 17 1 2 08 31 7 16 7 2 30 30 1 16 3 2 54 28 5 15 9 2 82 26 5 15 4 3 15 67 32 2 23 3 1 87 30 8 22 9 2 06 29 3 22 4 2 27 27 7 22 0 2 51 25 7 21 3 2 78 22 7 20 2 3 07 63 30 3 23 1 1 86 29 0 22 7 2 05 26 3 21 6 2 25 24 1 20 6 2 47 21 8 19 6 2 73 19 6 18 7 3 01 62 29 9 29 0 1 86 28 1 27 9 2 04 26 6 26 6 2 25 25 1 25 1 2 49 23 8 23 8 2 75 21 2 21 2 3 04 57 29 5 29 5 1 85 28 2 28 2 2 04 26 6 26 6 2 2...

Страница 27: ... 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CK5PT 036 1 00 0 94 042 1 00 1 00 COILS 315 A J AV048090 VARIABLE SPEED FURNACE CC5A CD5AW 036 1 00 1 00 CC5A CD5AA 036 1 00 0 93 CE3AA 0...

Страница 28: ...3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 315 A J AV066135 VARIABLE SPEED FURNACE CE3AA 036 1 00 0 99 CC5A CD5AA 042 1 00 0 92 042 1 00 0 97 CC5A CD5AW 036 1 00 0 93 CK3BA 036 1 00 0 97 042 1 00 0 92 042 1 00 0 97 CE3AA 036 1 00 0 94 CK5A CK5BA 036 1 00 0 9...

Страница 29: ... 31 1 24 1 2 66 28 3 23 0 2 93 26 0 22 0 3 24 23 3 20 9 3 56 62 34 8 32 4 2 17 32 4 31 2 2 39 30 0 29 7 2 65 27 9 27 9 2 93 26 8 26 8 3 25 24 6 24 6 3 58 57 32 7 32 7 2 15 31 0 31 0 2 38 29 9 29 9 2 64 28 7 28 7 2 94 27 3 27 3 3 25 24 8 24 8 3 58 1350 72 41 4 20 9 2 25 40 2 20 6 2 50 38 2 19 9 2 76 36 4 19 4 3 06 34 2 18 8 3 38 31 7 18 2 3 75 67 39 0 27 8 2 24 37 4 27 3 2 48 35 5 26 7 2 74 33 5 26...

Страница 30: ...7 34 8 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 COILS 315 A J AV036070 VARIABLE SPEED FURNACE 042 1 00 1 00 CC5A CD5AA 036 0 98 0 93 CC5A CD5AW 036 1 00 1 00 CE3AA 036 0 97 0...

Страница 31: ... 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BE 042 0 99 0 91 CE3AA 036 0 97 0 94 CK5A CK5BT 036 0 99 0 92 042 0 99 0 93 042 0 99 0 92 CK3BA 042 0 99 0 94 CK5A CK5BW 036 0 99 0 92 CK5A CK5BA 042...

Страница 32: ...63 36 9 27 8 2 23 34 5 26 8 2 46 31 9 25 7 2 71 29 4 24 6 2 99 26 9 23 6 3 30 24 2 22 4 3 62 62 35 8 34 5 2 22 33 2 32 9 2 45 31 1 31 1 2 70 30 0 30 0 3 00 28 6 28 6 3 32 25 8 25 8 3 65 57 34 8 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Co...

Страница 33: ... 38 9 38 5 2 83 36 5 36 5 3 13 35 4 35 4 3 49 32 7 32 7 3 86 30 7 30 7 4 29 57 40 7 40 7 2 56 39 0 39 0 2 83 37 6 37 6 3 15 35 8 35 8 3 49 33 5 33 5 3 87 30 7 30 7 4 29 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 01 CD5AA 048 1 00 0 94 CC5A CD5AC 048 0 99 1 01 CE3A...

Страница 34: ... 24 62 41 6 40 2 2 57 38 9 38 5 2 83 36 5 36 5 3 13 35 4 35 4 3 49 32 7 32 7 3 86 30 7 30 7 4 29 57 40 7 40 7 2 56 39 0 39 0 2 83 37 6 37 6 3 15 35 8 35 8 3 49 33 5 33 5 3 87 30 7 30 7 4 29 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 315 A J AV066135 VARIABLE SPEED FURNACE CK5PA 0...

Страница 35: ... 34 8 3 06 32 7 32 7 3 39 31 2 31 2 3 78 29 5 29 5 4 21 57 38 1 38 1 2 48 36 2 36 2 2 74 35 0 35 0 3 05 33 6 33 6 3 40 32 2 32 2 3 79 29 3 29 3 4 20 1575 72 47 5 23 9 2 61 46 2 23 7 2 90 44 4 23 2 3 22 41 8 22 4 3 56 39 5 21 8 3 95 36 8 21 1 4 40 67 44 9 31 9 2 58 43 0 31 5 2 86 41 1 31 1 3 18 38 8 30 3 3 53 36 3 29 6 3 92 32 0 28 0 4 32 63 42 5 32 0 2 57 40 5 31 4 2 85 37 6 30 1 3 15 35 0 29 1 3 ...

Страница 36: ...6 46 6 2 97 44 8 44 8 3 28 42 5 42 5 3 63 41 1 41 1 4 02 39 0 39 0 4 45 36 7 36 7 4 92 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 00 CK3BA 048 0 99 0 95 CC5A CD5AC 048 0 97 0 98 CK5A CK5BA 048 0 99 0 95 CC5A CD5AW 048 0 99 0 99 CK5A CK5BT 048 0 99 0 95 060 1 01 0 ...

Страница 37: ...62 47 8 45 0 2 97 45 7 44 1 3 29 43 1 42 6 3 63 40 5 40 5 4 02 39 0 39 0 4 45 36 7 36 7 4 92 57 46 6 46 6 2 97 44 8 44 8 3 28 42 5 42 5 3 63 41 1 41 1 4 02 39 0 39 0 4 45 36 7 36 7 4 92 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 0 99 0 94 CC5A CD5AC 048 0 97 0 99 060 1 0...

Страница 38: ... 36 14 5 52 61 05 34 63 6 06 56 50 32 98 6 63 51 36 31 14 7 25 2250 57 62 16 62 16 4 54 59 57 59 57 5 00 56 86 56 86 5 50 53 93 53 93 6 06 50 56 50 56 6 65 46 69 46 69 7 29 62 62 34 61 20 4 54 59 51 59 51 5 00 56 85 56 85 5 50 53 92 53 92 6 06 50 55 50 55 6 65 46 69 46 69 7 29 67 67 52 50 93 4 60 64 07 49 53 5 06 60 43 48 08 5 55 56 59 46 55 6 09 52 42 44 91 6 67 47 72 43 08 7 31 72 73 65 40 55 4 ...

Страница 39: ... 0 2 96 20 4 146 0 3 34 40 TCG SDT KW 36 1 76 7 1 42 34 2 86 5 1 61 32 3 96 3 1 82 30 5 106 0 2 06 28 6 116 0 2 32 26 6 126 0 2 62 24 6 136 0 2 96 22 5 146 0 3 33 45 TCG SDT KW 39 5 77 8 1 43 37 5 87 5 1 61 35 4 97 2 1 82 33 4 107 0 2 06 31 3 117 0 2 33 29 2 127 0 2 62 27 1 137 0 2 96 24 7 147 0 3 33 50 TCG SDT KW 43 1 79 2 1 44 40 9 88 8 1 63 38 7 98 4 1 83 36 5 108 0 2 07 34 3 118 0 2 33 32 0 12...

Страница 40: ... 0 2 10 47 9 82 0 2 39 45 2 92 0 2 71 42 6 102 0 3 08 39 9 112 0 3 49 37 2 122 0 3 96 34 4 132 0 4 48 31 5 142 0 5 06 40 TCG SDT KW 55 7 72 3 2 10 52 8 82 1 2 38 49 9 92 0 2 70 47 0 102 0 3 06 44 1 112 0 3 47 41 1 122 0 3 93 38 1 132 0 4 45 34 9 142 0 5 02 45 TCG SDT KW 60 9 73 6 2 13 57 8 83 2 2 40 54 7 92 7 2 71 51 7 102 0 3 06 48 6 112 0 3 46 45 4 122 0 3 91 42 1 132 0 4 42 38 5 142 0 4 99 50 T...

Страница 41: ... differential consult the Residential Split System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron R 410A Refrigerant available from equipment distributor 7 If any refrigerant tubing is buried provide a 6 in vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in may be buried without further consideration Do not bury refri...

Страница 42: ... 42 ...

Страница 43: ... 43 ...

Страница 44: ...bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Air Cooled Split System Air Conditioner 550A 2 to 5 Tons Nominal Fan blades will be statically and dynamically balanced C...

Отзывы: