Every thermostat is calibrated before it leaves the factory. Un-
der normal circumstances there will never be a need to recali-
brate the thermostat again. To accommodate s

pecial needs,

the thermostat may be recalibrated following these steps:

1. While holding the Mode button in, press the fan button

for 5 seconds. After all the icons in the display appear,
release the buttons.

2. Press the Up and Down arrow buttons simultaneously,

twice.

3. Press the up or down buttons until the flashing number

equals the current room temperature.

4. Press the Mode button to return to normal operation.

Sample Wiring Diagrams

HEAT PUMP

Sample Wiring Diagrams

HEAT-COOL/

COOLING ONLY

STEP #3

TEST OPERATION

A.

Turn the power on to the HVAC (heating, ventilation,
and air conditioning) system.

B.

Press the

MODE button until the

HEAT

icon appears

on the display. Press the Up or Down buttons until the
set temperature is 10 degrees

above

room tempera-

ture. The unit should turn on and supply heat.

C.

Press the

MODE button until the

COOL

icon appears

on the display. Press the Up or Down buttons until the
set temperature is 10 degrees

below

room tempera-

ture. The unit should turn on.

NOTE:

Most equipment has a time delay between cy-

cles. This feature is defeatable on the thermostat.
Consult the Owner's Manual under Setup: Cycles per
hour.

D.

Press the

MODE button repeatedly until

OFF

is dis-

played on the thermostat.

TROUBLESHOOTING

SYMPTOM

CAUSE

REMEDY

When not using a com-
mon wire the air condi-
tioning equipment tries
repeatedly to turn on,
but cannot. At times
the display dims or dis-
appears.

There is not enough power
available to “power share”.

Connect a 270 ohm,
10 watt power resistor

at

the unit

as shown below.

For Problem A/C

For Problem Heat

The air conditioning
does not attempt to
turn on.

The compressor timer lock-
out may prevent the air
conditioner from turning
on, for a period of time.

Consult the Owner’s
Manual in the Setup sec-
tion to defeat the cycles
per hour and compressor
timeguard.

The display is blank.

Lack of proper power.

Make sure power is
turned on to the HVAC
unit and there is 24 vac
between

R

and

H2

.

If the HVAC unit is cool-
ing only, check there is
24 vac between

R

and

C

.

The air conditioning
does not attempt to
turn on.

The cooling set point is set
too high.

Press the down arrow
until the cooling set point
is 10 degrees lower than
the room temperature.

The heating does not
attempt to turn on.

The heating set point is set
too low.

Press the up arrow until
the heating set point is
10 degrees higher than
the room temperature.

The strip heater turns
off well before reaching
set point.

Heat pump is incorrectly
selected “

on

” in the

Advanced Setup.

Select heat pump “

off”

during Advanced Setup
programming. Consult
the Owner’s Manual.

CALIBRATION

R

H2

Y

C

TR300-10w

R H2

Y

C

TR300-10w

RS

RS+V

RS-GND

3 conductor 18 gage
unshielded cable from
the thermostat to the
remote sensor.

Y

G1

R

C

H1

CK1

CK2

O

G2

RS+5
RS
RS GND

H2

8 Conductor 18 gage
unshielded cable from the
thermostat to the equipment.

COMMON

POWER

LO FAN

COMPRESSOR

REVERSING

VALVE

AUX HEAT

HIGH FAN

O

H2

G1

R

C

Y

G2

H1

DEFROST

RS

RS+V

RS-GND

3 conductor 18 gage
unshielded cable from
the thermostat to the
remote sensor.

8 Conductor 18 gage

unshielded cable from the
thermostat to the equipment.

COMMON

24 v POWER

LO FAN

COMPRESSOR

AUX HEAT

HIGH FAN

O

H2

G1

R

C

Y

G2

Y

G1

R

C

H1

CK1

CK2

O

G2

RS+5
RS
RS GND

H2

NOTE

: For cooling only, the H2 connection is not required.