DIAGNOSIS AND SOLUTION (CONT)
Open circuit or short circuit of temperature sensor diagnosis and solution (E4/E5/F1/F2/F3)
Error Code
E4/E5/F1/F2/F3
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure.
Supposed causes
·
Wiring mistake
·
Sensor faulty
·
PCB faulty
Troubleshooting
Check the connection
between the temperature
sensor and PCB.
Correct the connection
No
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Replace the sensor
No
Yes
Fig. 33 – Check the connection