![Bryant 524J 07 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/bryant/524j-07/524j-07_installation-start-up-and-service-instructions-manual_2822289009.webp)
9
LEGEND
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
Table 2 — 524J***A Physical Data, SI — Cooling Units
UNIT 524J***A
07A
08A
12A
14A
16A
NOMINAL CAPACITY (kW)
21
26
35
43
52
OPERATING WEIGHT (kg)
Base Unit with TXV
181
183
193
315
323
Plenum
80
80
80
102
102
FANS
Qty...Diam. (mm)
1...381
1...381
1...381
2...381
2...381
Nominal Airflow (L/s)
1133
1604
1888
2360
2831
Airflow Range (L/s)
850-1416
1203-2006
1416-2360
1770-2949
2124-3539
Nominal Motor Hp (Standard Motor)
208/230-1-60
0.97
1.79
—
—
—
208/230-3-60 and 460-3-60
1.79
1.79
1.79
2.16
2.16
575-3-60
0.75
1.49
1.49
2.24
2.24
Motor Speed (r/s)
208/230-1-60
28.8
28.8
—
—
—
208/230-3-60 and 460-3-60
28.8
28.8
28.8
28.8
28.8
575-3-60
28.8
28.8
28.8
28.8
28.8
REFRIGERANT
R-410A
Operating charge (kg) (approx per
circuit)*
1.36
1.36
0.68/0.68
0.90/0.90
1.13/1.13
DIRECT - EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine - Wave Fins
Max Working Pressure (kPag)
4481
4481
4481
4481
4481
Face Area (sq m)
0.62
0.77
0.93
0.93
1.64
No. of Splits
1
1
2
2
2
No. of Circuits per Split
12
15
9
12
16
Split Type...Percentage
—
—
Face...50/50
Face...50/50
Face...50/50
Rows...Fins/m
4...591
4...591
4...591
4...591
4...591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)
1...1-1/8
1...1-1/8
2...1-1/8
2...1-1/8
2...1-1/8
DX Coil — Liquid Refrigerant
(ODF)
1...5/8
1...5/8
2...5/8
2...5/8
2...5/8
Steam Coil, In (MPT)
1...2-1/2
1...2-1/2
1...2-1/2
1...2-1/2
1...2-1/2
Steam Coil, Out (MPT)
1...1-1/2
1...1-1/2
1…1-1/2
1…1-1/2
1…1-1/2
Hot Water Coil, In (MPT)
1...1-1/2
1...1-1/2
1...1-1/2
1...2
1...2
Hot Water Coil, Out (MPT)
1...1-1/2
1...1-1/2
1...1-1/2
1...2
1...2
Condensate (PVC)
1...1-5/8 ODM / 1-1/4 IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (mm)
4...406 x 610 x 51
4...406 x 508 x 51
4...406 x 610 x 51
Access Location
Either Side
STEAM COIL†
Max Working Pressure (kPag at
126°C)
138
138
138
138
138
Total Face Area (sq m)
0.62
0.62
0.62
1.24
1.24
Rows...Fins/m
1...355
1...355
1...355
1...394
1...394
HOT WATER COIL†
Max Working Pressure (kPag)
1034
1034
1034
1034
1034
Total Face Area (sq m)
0.62
0.62
0.62
1.24
1.24
Rows...Fins/m
2...335
2...335
2...335
2...335
2...335
Water Volume
(L)
31.4
31.4
31.4
52.6
52.6
(m
3
)
0.031
0.031
0.031
0.052
0.052
DX
— Direct Expansion
IDF
— Inside Diameter, Female
ODF
— Outside Diameter, Female
ODM
— Outside Diameter, Male
TXV
— Thermostatic Expansion Valve
Содержание 524J 07
Страница 4: ...4 Fig 2 Dimensions Sizes 07 12 ...
Страница 5: ...5 Fig 2 Dimensions Sizes 07 12 cont ...
Страница 6: ...6 Fig 3 Dimensions Size 14 and 16 ...
Страница 7: ...7 Fig 3 Dimensions Size 14 and 16 cont ...
Страница 23: ...23 Fig 17 Typical Fan Discharge Connections for Multiple Fan Units Fig 18 Duct Flange Installation ...