Bryant 38GRQ Скачать руководство пользователя страница 2

2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air- conditioning equipment
can be hazardous due to system pressures, electrical components,

and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should

install, start- up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by

trained service personnel.
When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep

quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult

local building codes and current editions of the National Electrical

Code (NEC) NFPA 70. In Canada, refer to current editions of the
Canadian electrical code CSA 22.1.

Recognize safety information. This is the safety- alert symbol

!

!

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.Understand

these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety- alert symbol. DANGER

identifies the most serious hazards which

will

result in severe

personal injury or death. WARNING signifies hazards which

could

result in personal injury or death. CAUTION is used to identify

unsafe practices which

may

result in minor personal injury or

product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe

in the ground. If any section of pipe is buried, there must be

a 6 in. (152 mm) vertical rise to the valve connections on

the outdoor units. If more than the recommended length is

buried, refrigerant may migrate to the cooler buried section

during extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start- up.

GENERAL

These instructions cover the installation, start- up and servicing of

outdoor and indoor units ductless systems.

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit. See Fig. 4 for

minimum required distances between unit and walls or ceilings.

Piping
IMPORTANT

:

Both refrigerant lines must be insulated

separately.

S

Minimum refrigerant line length between the indoor and outdoor

units is 10 ft. (3 m).

S

The following maximum lengths are allowed.

Table 2— Maximum Lengths

System Size

9K

(208- 23 V)

12K

(208- 230 V)

18K

(208- 230 V)

Piping

Min. Piping Length

ft (m)

10 (3)

10 (3)

10 (3)

Standard Piping Length

ft (m)

25 (7.6)

25 (7.6)

25 (7.6)

Max. outdoor- indoor height difference

ft (m)

32.8 (9.9)

32.8 (9.9)

32.8 (9.9)

Max. Piping Length with no additional refrigerant charge

ft (m)

25 (7.6)

25 (7.6)

25 (7.6)

Max. Piping Length

ft (m)

82 (25)

82 (25)

82 (25)

Additional refrigerant charge (between Standard – Max piping length)

Oz/ft

(g/M)

0.2 (18.6)

0.2 (18.6)

0.2 (18.6)

Gas Pipe (size - connection type)

in

1/4

flare

connection

1/4

flare

connection

1/4

flare

connection

Liquid Pipe (size - connection type)

in

1/2

flare

connection

1/2

flare

connection

5/8

flare

connection

Refrigerant

Refrigerant Type

R410A

R410A

R410A

Charge Amount

Lbs

(kg)

3.1 (1.4)

3.1 (1.4)

3.1 (1.4)

* Charge is for piping that runs up to 25 ft. (7.6 m)

** For piping runs greater than 25 ft. (7.6 m), add specified amount of charge per foot of extra piping, up to the allowable length.

*** EXV - Electronic Expansion Device, Capillary tubes are used as metering devices

Содержание 38GRQ

Страница 1: ...OOR UNIT INSTALLATION 7 Install Mounting Plate 7 Drill Hole in Wall for Interconnecting Piping Drain and Wiring 7 OUTDOOR UNIT INSTALLATION 8 Piping Connections to Outdoor Unit 8 INSTALL ALL POWER INTERCONNECTING WIRING AND PIPING TO INDOOR UNIT 9 SYSTEM VACUUM AND CHARGE 9 START UP 11 WIRING DIAGRAMS 12 TROUBLESHOOTING 13 The following parts are included in your indoor unit Please contact your de...

Страница 2: ...ust be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not bury more than 36 in 914 mm of refrigerant pipe in the ground If any section of pipe is buried there must be a 6 in 152 mm vertical rise to the valve con...

Страница 3: ...ate shielded copper conductor only with a minimum 300 volt rating and 2 64 inch thick insulation must be used as the communication wire from the outdoor unit to the indoor unit Please use a separate shielded 16GA stranded control wire CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Wires should be sized based on NEC and local co...

Страница 4: ...4 DIMENSIONS INDOOR Fig 1 Indoor Unit Dimensions Table 4 Indoor Unit Dimensions Model W H D Q 09 12K 37 4 5 12 3 5 8 2 1 6 18K 37 4 5 12 3 5 8 2 3 4 ...

Страница 5: ...5 DIMENSIONS OUTDOOR Fig 2 Outdoor Unit Sizes 9 and 12 Fig 3 Outdoor Unit Size 18 ...

Страница 6: ... min 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearances CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Outdoor Unit Clearances Table 5 Outdoor Clearances UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Страница 7: ...n Fig 6 3 If the wall is block brick concrete or similar material drill 2 5 mm diameter holes and insert anchors for the appropriate mounting screws 4 Attach the mounting plate to the wall Fig 6 09 and 12K Mounting Plate Spacing Wall Wall Mark middle Level Rear piping hole Rear piping hole See Hole Size Tables See Hole Size Tables 6 in 6 in Fig 7 18K Mounting Plate Spacing DRILL HOLE IN WALL FOR I...

Страница 8: ...d make flare connection 4 Apply a small amount of refrigerant oil to the flare connection on the tubing 5 Properly align tubing in with service valve 6 Tighten flare nut and finish installation using two wrenches as shown in Fig 11 A07354 Fig 11 Tighten Flare Nut Strong wind A07350 Fig 12 High Wind Installation Outdoor Unit Wiring Connections 1 Mount outdoor power disconnect 2 Run power wiring fro...

Страница 9: ...tion then fasten piping and wiring to the wall as required Completely seal the hole in the wall Fig 16 Remove Knockouts Mounting plate Fixing hook Mounting plate A12408 Fig 17 Hang Indoor Unit UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump CAUTION Refrigerant tubes and indoor coil should be eva...

Страница 10: ...in any liquid water Refer to Fig 21 and proceed as follows 1 Pump system down to 28 in of mercury and allow pump to continue operating for an additional 15 minutes 2 Close service valves and shut off vacuum pump 3 Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close service valve and allow system to stand for 1 hr During this time dry nitrogen will b...

Страница 11: ...hts work properly 3 Does the air deflection louver function properly 4 Does the drain work OUTDOOR UNIT 1 Are there unusual noises or vibrations during operation Explain Following Items To Customer With The Aid Of The Owner s Manual 1 How to turn air conditioner on and off selecting COOLING HEATING and other operating modes setting a desired temperature setting the timer to automatically start and...

Страница 12: ...2 8 0 2 C D V w o L 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 C D V w o L 0 6 1 0 3 2 8 0 2 k c o l B l a n i m r e T t i n U r o o d n I 8 1 e z i S k c o l B l a n i m r e T t i n U r o o d t u O 8 1 e z i S Power to Indoor Unit Control to Indoor Unit Power to Indoor Unit Main Power Supply Main Power Supply 208 230 1 60 Connection Diagram CONNECTING CABLE OUTDOOR TO...

Страница 13: ...protection of outdoor unit Other malfunction E5 Module current protection Other malfunction H5 Module temperature protection Other malfunction P8 Freeze prevention protection Other malfunction E2 High power protection Other malfunction L9 Lacking inverse phase protection of compressor Other malfunction U2 PFC current malfunction Other malfunction HC High DC bus bar voltage protection Other malfunc...

Страница 14: ...BDP S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Edition Date 06 15 Catalog No GRQ 619FB 01SI Replaces NEW ...

Отзывы: