background image

© 2004 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231

—16—

Printed in U.S.A.

ii368r361

Catalog No. 5336–800

Содержание 368RAN Series A

Страница 1: ...INITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING CARBON MONO...

Страница 2: ...esult in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injur...

Страница 3: ...tion debris from all HVAC system components after construction is completed This furnace is approved for reduced clearances to combustible construction therefore it may be installed in a closet or sim...

Страница 4: ...n and dilution of flue gases This determi nation must be made on an individual installation basis and must take into consideration the overall volume of unconfined space the number of windows and vent...

Страница 5: ...and Air Conditioning Systems or Canadian equivalent The supply duct work should be attached to flanged front opening provided at discharge end of furnace The return air duct work should be attached to...

Страница 6: ...tion length of 3 3 4 in The oil pump is set to operate on a single line system To operate on a two line system the by pass plug must be installed F Oil Connections CAUTION UNIT DAMAGE HAZARD Failure t...

Страница 7: ...ply line is open 6 RESET BUTTON on primary control is pushed down 7 Flame observation door is closed 8 Thermostat is set for heating mode and set above room temperature If all of the above items have...

Страница 8: ...Fig 3 Wiring Diagram A04182 8...

Страница 9: ...Wiring with 1 Speed Air Conditioner Fig 5 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04184 A04185 Fig 6 24 VAC Oil Furnace Wiring with 1 Speed Heat Pump A04186 Fig 7 24 VAC Oil Furnace W...

Страница 10: ...ic board ACCORDING TO OIL INPUT SELECTED AND A C SIZE See Tables 11A 11B and 11C or Tables 12A 12B and 12C WARNING FIRE HAZARD AND UNIT RELIABILITY Failure to follow this warning could result in prope...

Страница 11: ...R1 JW6 R3 D20 D1 D3 D04 D02 D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LE...

Страница 12: ...TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME II OIL BURNER For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsur...

Страница 13: ...de with no 24 VAC input to DH the CFM STD is reduced by 15 COOLING MODE OR HEAT PUMP HEATING MODE 2 SPEED LOW 24 VAC INPUT R TO G Y1 AND O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD...

Страница 14: ...COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD with SW3 ADJ Dip Switch A Position CFM HIGH with SW3 ADJ Dip Switch B Position CFM LOW with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 5 0 9...

Страница 15: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products i...

Страница 16: ...2004 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A ii368r361 Catalog No 5336 800...

Отзывы: