Status Code 13
LIMIT (LS) OR FLAME ROLLOUT (FRS) SWITCH LOCKOUT—THIS STATUS CODE INDICATES THAT LIMIT SWITCH OPENED
5 TIMES FOR AT LEAST 3 MINUTES EACH TIME DURING 1 THERMOSTAT CYCLE. THE 2-STAGE FURNACE CONTROL WILL
AUTO-RESET IN 3 HR. FLAME ROLLOUT SWITCH FRS REQUIRES MANUAL-RESET.
STEP
ACTION
YES
NO
GO TO
1.
Remove blower door. Make sure thermostat is NOT calling for heat. This action
resets control.
—
—
2
2.
Depress door switch. Use piece of tape to hold switch closed.
—
—
3
3.
Set thermostat to call for heat or jumper R and W/W1 thermostat terminals.
—
—
4
4.
Does blower motor turn on within 1 minute of ignition?
28
5
—
5.
Remove tape from door switch, turn power off at main disconnect, and remove
jumper across R and W/W1.
—
—
6
6.
Does blower wheel rub against blower housing?
7
9
—
7.
Fix problem.
—
—
8
8.
Go to page number indicated in Index for CLEANUP AND START-UP IN-
STRUCTIONS.
—
—
INDEX
9.
Does blower wheel turn freely?
10
11
—
10.
Is blower wheel firmly mounted on motor shaft?
12
7
—
11.
Replace blower motor. On variable-speed ICM blower motors, inspect electron-
ics portion of failed motor for water damage. If present, find source of water and
fix. Check A-coil and/or humidifier.
—
—
8
12.
Turn power back on. Depress door switch. Use a piece of tape to hold switch
closed, then jumper R and W/W1 thermostat terminals.
—
—
13
13.
Does furnace have a variable-speed ICM blower motor?
14
21
—
14.
Do you have 115 vac across BLACK and WHITE power leads at blower motor.
16
15
—
15.
You have an open wire or bad terminal on either the BLACK or WHITE wire
between 2-stage furnace control and blower motor, or the power choke (if
equipped) failed. Fix problem.
—
—
8
16.
Wait 1 minute after burners ignite before proceeding to step 17.
—
—
17
STEP
TERMINAL CONNECTIONS*
VOLTAGE
ACTION
17.
HUM
WHITE (+)
to
C
OM
-24V
(-)
24 vac
If voltages are correct, go to Step 18. If not, replace 2-stage
furnace control.
PL4-2
BLUE (+)
to
PL4-3
BLACK (-)
-5 vdc to -13 vdc
PL4-5
RED (+)
to
PL4-3
BLACK (-)
24 vac
18.
PL7-12
BLUE (+)
to
PL7-10
BLACK (-)
-5 vdc to -13 vdc
If voltages are correct, go to Step 19. If not, repair or replace
ICM blower harness.
PL7-13
RED (+)
to
PL7-10
BLACK (-)
24 vac
19.
PL7-11
GREEN (+)
to
PL7-8
BLACK (-)
5 vdc to 10 vdc
If voltages are correct, go to Step 20. If not, replace EZ-
SELECT airflow control.
PL7-14
RED (+)
to
PL7-9
BLACK (-)
24 vac
20.
PL9-2
WHITE (+)
to
PL9-3
BLACK (-)
24 vac
If voltages are correct, replace ICM blower motor. If not, repair
or replace ICM blower harness.
PL9-15
GREEN (+)
to
PL9-3
BLACK (-)
5 vdc to 10 vdc
PL9-12
RED (+)
to
PL9-1
BLACK (-)
24 vac
STEP
ACTION
YES
NO
GO TO
21.
Do you have 115 vac across LO-GAS-HEAT and high voltage COMMON?
23
22
—
22.
Replace 2-stage furnace control.
—
—
8
23.
Remove tape from door switch and turn power off at main disconnect.
—
—
24
24.
Note location of all blower leads, then disconnect blower motor leads from
2-stage furnace control and capacitor.
—
—
25
25.
Do you have continuity between the following motor leads:
• RED to WHITE
• YELLOW to WHITE
• BROWN to BROWN
• BLUE to WHITE
• BLACK to WHITE
• BROWN to WHITE
26
27
—