Bryant 330AAV Скачать руководство пользователя страница 4

I.

LOCATION

A.

General

CAUTION:

Do not use this furnace during construction

when adhesives, sealers, and/or new carpets are being
installed and curing. If the furnace is required during
construction, use clean outside air for combustion and
ventilation. Compounds of chlorine and fluorine, when
burned in combustion air, form acids which will cause
corrosion of the heat exchangers and metal vent system.
Some of these compounds are released from paneling and
dry wall adhesives, paints, thinners, masonry cleaning
materials, and many other solvents commonly used in the
construction process.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.

CAUTION:

Do not install furnace in a corrosive or

contaminated atmosphere. Make sure all combustion and
circulating air requirements are met.

This furnace must be installed so the electrical components are
protected from water.

Locate furnace as near the center of the air distribution system and
chimney or vent as possible. The furnace should be installed as
level as possible. When a furnace is installed so that supply ducts
carry air to areas outside the space containing the furnace, return
air must also be handled by a duct(s) sealed to the furnace casing
and terminating outside the space containing the furnace.

Provide ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown on unit clearance
label. This furnace shall not be installed directly on carpeting, tile,
or any combustible material other than wood flooring.

B.

Location Relative to Cooling Equipment

The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchangers. When
installed parallel with a furnace, dampers or other means used to

control the flow of air must prevent chilled air from entering
furnace. If dampers are manually operated, they must be equipped
with means to prevent operation of either unit unless damper is in
full-heat or full-cool position.

C.

Hazardous Locations

II.

AIR FOR COMBUSTION AND VENTILATION

Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3, Air for Combustion and
Ventilation, of the NFGC or applicable provisions of the local
building codes.

Canadian installations must be in accordance with NSCNGPIC
and all authorities having jurisdiction.

CAUTION:

Air for combustion must not be contami-

nated by halogen compounds, which include fluoride,
chloride, bromide, and iodide. These elements are found
in aerosol sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household products.

All fuel-burning equipment must be supplied with air for combus-
tion of fuel. Sufficient air MUST be provided to ensure there will
not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between furnace cabinet
and return-air duct to prevent pulling air from burner area and draft
safeguard opening into the circulating air.

CAUTION:

The operation of exhaust fans, kitchen ven-

tilation fans, clothes dryers, or fireplaces could create a
negative air pressure condition at the furnace. Make-up
air must be provided for these devices, in addition to that
required by the furnace.

Combustion air requirements are determined by whether furnace is
in an UNCONFINED or CONFINED space.

A.

Unconfined Space

An unconfined space must have at least 50 cu ft for each 1000
Btuh of input for all appliances (such as furnaces, clothes dryer,
water heaters, etc.) in the space.

NOTE:

These furnaces are designed for a minimum continu-

ous return-air temperature of 60°F or intermittent operation
down to 55°F such as when used with a night setback
thermostat. Return-air temperature must not exceed a maxi-
mum of 85°F. Failure to follow these return-air temperature
limits may affect reliability of heat exchangers, motors, and
controls.

A99075

FRONT

RETURN
AIR

MAX 85

°

F

MIN 55

°

F

°

F

°

F

WARNING:

When furnace is installed in a residential

garage, it must be installed so that burners and ignition
sources are located a minimum of 18 in. above floor. The
furnace must be located or protected to avoid physical
damage by vehicles. When furnace is installed in a public
garage, airplane hangar, or other building having a
hazardous atmosphere, unit must be installed in accor-
dance with requirements of National Fire Protection
Association, Inc.

A93044

18-IN. MINIMUM

TO BURNERS

—4—

Содержание 330AAV

Страница 1: ...labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States refer to the National Fuel Gas Code NFGC NFPA No 54 1999 ANSI Z223...

Страница 2: ...6 12 11 16 4 134 042080 17 1 2 15 7 8 16 4 150 048080 21 19 3 8 19 1 2 4 154 036100 17 1 2 15 7 8 16 4 160 048100 21 19 3 8 19 1 2 4 166 060100 24 1 2 22 7 8 23 4 184 048120 21 19 3 8 19 1 2 5 178 060...

Страница 3: ...require these instructions as a minimum for a safe installation CAUTION Application of this furnace should be in doors with special attention given to vent sizing and material gas input rate air tempe...

Страница 4: ...on and ventilation air must be provided in accordance with Section 5 3 Air for Combustion and Ventilation of the NFGC or applicable provisions of the local building codes Canadian installations must b...

Страница 5: ...with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacent to fu...

Страница 6: ...sories All accesso ries MUST be connected external to furnace main casing IV RETURN AIR CONNECTIONS CAUTION For airflow requirements above 1800 CFM see Air Delivery table in Product Data literature fo...

Страница 7: ...le in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install...

Страница 8: ...een gas control manifold and manual shutoff valve WARNING Use the proper length of pipes and ad equate piping support to avoid stress on the gas control manifold A failure to follow this warning can c...

Страница 9: ...24 v humidifier connection The terminals are energized with 24v 0 5 amp maximum when the gas valve is energized Fig 9 Heating and Cooling Application Wiring Diagram 1 Stage Thermostat and Condensing U...

Страница 10: ...and high gas heat for optimum comfort Setup switch 2 SW 2 must be in the factory shipped OFF position See Fig 12 and Tables 6 and 7 for setup switch information If a 2 stage heating thermostat is to b...

Страница 11: ...ec tion is based on stored history of thermostat cycle times When wall thermostat calls for heat R W W1 circuit closes The furnace control performs a self check verifies the low heat and high heat pre...

Страница 12: ...high gas heat and vice versa a Switching from low to high gas heat If thermostat R W W1 circuit for low gas heat is closed and R W2 circuit for high gas heat closes the control CPU switches the induc...

Страница 13: ...et thermal overload switches 4 Blower motor speed selections are for average conditions See Installation Instructions for details on optimumspeed selection 5 Replace only with a 3 AMP fuse 6 Auxiliary...

Страница 14: ...r motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2 The EAC terminals EAC 1 and EAC 2 are ener gized with 115v when the blower motor BLWM is operating on either coolin...

Страница 15: ...al gas supplier b Obtain yearly specific gravity average from local gas supplier c Verify furnace model Table 9 can only be used for model 330AAV Furnaces d Find installation altitude in Table 9 NOTE...

Страница 16: ...t connections See Fig 12 This keeps furnace locked in high heat operation Repeat items h through k for high heat operation EXAMPLE High heat operation at 0 2000 ft altitude Furnace input from rating p...

Страница 17: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Страница 18: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Страница 19: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Страница 20: ...TE CU FT HR SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 13 14 360 327 300 277 257 720 655 600 555 514...

Страница 21: ...normal start up allow furnace to operate for 2 minutes then block flue outlet 100 percent Furnace should cycle off within 2 minutes d Remove blockage and reconnect vent connector to furnace flue coll...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Отзывы: