background image

component failure. To initiate the component test proce-
dure, ensure that there are no thermostat inputs to the
control and all time delays have expired. Short the
TWIN/TEST terminal to ground or C

OM

for 1 to 4 sec. (See

Fig. 11.)

NOTE:

The component test feature will not operate if the control

is receiving any thermostat signals or until all time delays have
expired.

The component test sequence is as follows:

a. The furnace control checks itself, operates the inducer

motor on low speed for 7 sec and on high speed for 7 sec,
then stops.

b. The hot surface ignitor is energized for 15 sec, then

de-energized.

c. The blower motor operates on low-gas-heat/heat pump

low-heat/low-cool/continuous fan speed for 7 sec, then
stops.

d. The blower motor operates on high-gas heat for 7 sec,

then stops.

e. The blower motor operates on heat pump high-heat/high-

cool speed for 7 sec, then stops.

The gas valve and humidifier terminal HUM are not
energized for safety reasons.

NOTE:

The EAC terminals are energized when the blower is

energized.

2. After all connections have been made, purge gas lines and

check for leaks.

WARNING:

Never purge a line into a combustion

chamber. Never use matches, candles, flame, or other
sources of ignition for the purpose of checking leakage.
Use a soap-and-water solution to check for leakage. A
failure to follow this warning can cause a fire, explosion,
personal injury, or death.

3. To operate furnace, follow procedures on operating instruc-

tions label attached to furnace.

4. With furnace operating, set thermostat below room tem-

perature and observe that furnace goes off. Set thermostat
above room temperature and observe that furnace restarts.

D.

Adjustments

1. Set gas input rate.

Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft.

In the U.S.A., input rating for altitudes above 2000 ft must
be reduced by 4 percent for each 1000 ft above sea level.

In Canada, input rating must be derated by 10 percent for
altitudes of 2000 ft to 4500 ft above sea level.

Furnace input rate must be within

±

2 percent of input on

furnace rating plate.

2. Determine natural gas orifice size and manifold pressure for

correct input.

a. Obtain yearly heat value average (at installed altitude)

from local gas supplier.

b. Obtain yearly specific gravity average from local gas

supplier.

c. Verify furnace model. Table 9 can only be used for

model 330AAV Furnaces.

d. Find installation altitude in Table 9.

NOTE:

For Canada altitudes of 2000 to 4500 ft, use U.S.A.

altitudes of 2001 to 3000 ft in Table 9.

e. Find closest natural gas heat value and specific gravity in

Table 9.

f. Follow heat value and specific gravity lines to point of

intersection to find orifice size and low- and high-heat
manifold pressure settings for proper operation.

EXAMPLE: (0—2000 ft altitude)
Heating value = 1075 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45

Manifold pressure: 3.4-in. wc for high heat

1.4-in. wc for low heat

* Furnace is shipped with No. 45 orifices. In this example,
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.

g. Check and verify burner orifice size in furnace. NEVER

ASSUME ORIFICE SIZE; ALWAYS CHECK AND
VERIFY.

3. Adjust manifold pressure to obtain input rate.

a. Remove caps that conceal adjustment screws for low-

and high-heat gas valve regulators. (See Fig. 14.)

b. Move setup switch SW-2 on control center to ON

position. (See Fig. 12.) This keeps furnace locked in
low-heat operation.

c. Jumper R and W/W1 thermostat connections on control

center to start furnace.

d. Turn low-heat adjusting screw (5/64 hex Allen wrench)

counterclockwise (out) to decrease input rate or clock-
wise (in) to increase input rate.

NOTE:

DO NOT set low-heat manifold pressure less than 1.3-in.

wc or more than 1.7-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.

CAUTION:

DO NOT bottom out gas valve regulator

adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.

NOTE:

If orifice hole appears damaged or it is suspected to have

been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.

e. Move setup switch SW-2 to OFF position after complet-

ing low-heat adjustment.

f. Jumper R and W2 thermostat connections on control

center. (See Fig. 11.) This keeps furnace locked in
high-heat operation.

g. Turn high-heat adjusting screw (5/64 hex Allen wrench)

counterclockwise (out) to decrease input rate or clock-
wise (in) to increase rate.

NOTE:

DO NOT set high-heat manifold pressure less than 3.2-in.

wc or more than 3.8-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.

h. When correct input is obtained, replace caps that conceal

gas valve regulator adjustment screws. Main burner
flame should be clear blue, almost transparent. (See Fig.
15.)

i. Remove jumper R to W2.

4. Verify natural gas input rate by clocking gas meter.

—14—

Содержание 330AAV B Series

Страница 1: ...vailable during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals...

Страница 2: ...mbustible wood flooring in alcoves attics TABLE 1 DIMENSIONS IN UNIT SIZE A D E FLUE COLLAR SHIP WT 036040 14 3 16 12 9 16 12 11 16 4 124 024060 14 3 16 12 9 16 12 11 16 4 132 036060 14 3 16 12 9 16 1...

Страница 3: ...justment alter ation service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qua...

Страница 4: ...accordance with NSCNGPIC and all authorities having jurisdiction CAUTION Air for combustion must not be contami nated by halogen compounds which include fluoride chloride bromide and iodide These ele...

Страница 5: ...onal injury or death III FILTER ARRANGEMENT The factory supplied filter s is shipped in the blower compart ment Determine location for filter and move filter retaining hardware if necessary before att...

Страница 6: ...with national and local codes Refer to the NFGC NFPA 54 1996 ANSI Z223 1 1996 Canadian installations must be installed in accordance with NSC NGPIC and all authorities having jurisdiction The gas sup...

Страница 7: ...RNING Use the proper length of pipes to avoid stress on the gas control manifold A failure to follow this warning can cause a gas leak resulting in a fire explosion personal injury or death CAUTION Us...

Страница 8: ...Accessories 1 Electronic air cleaner EAC A terminal block EAC 1 hot and EAC 2 neutral is provided for EAC connection See Fig 11 The terminals are energized with 115v 1 amp maximum during blower motor...

Страница 9: ...ition at end of furnace installation This overrides built in control process for selecting high and low fire and allows the 2 stage thermostat to select gas heating modes The W2 from thermostat must b...

Страница 10: ...e low heat gas valve solenoid GV permits gas flow to the burners where it is ignited After 5 sec the ignitor HSI is de energized and a 2 sec flame proving period begins If high heat gas valve solenoid...

Страница 11: ...e start up and shutdown functions and delays described in item 1 above apply to 2 stage heating mode as well except for switching from low to high gas heat and vice versa a Switching from low to high...

Страница 12: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Страница 13: ...d Y Y2 circuits start the fur nace blower motor BLWM on high cool speed NOTE The furnace control CPU controls blower motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2...

Страница 14: ...9 NOTE For Canada altitudes of 2000 to 4500 ft use U S A altitudes of 2001 to 3000 ft in Table 9 e Find closest natural gas heat value and specific gravity in Table 9 f Follow heat value and specific...

Страница 15: ...f the furnace input rate NOTE Measured gas inputs high heat and low heat must be within 2 percent of that stated on furnace rating plate when installed at sea level or derated per that stated above wh...

Страница 16: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Страница 17: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Страница 18: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Страница 19: ...ment Return SW 2 to final de sired location after completing the reading See thermo stat manufacturer s instructions for adjusting heat antici pator TABLE 10 GAS RATE CU FT HR SECONDS FOR 1 REVOLUTION...

Страница 20: ...Wait 5 minutes and then reset draft safeguard switch 3 Check flow sensing pressure switches This control proves operation of draft inducer blower a Turn off 115 v power to furnace b Remove gas control...

Отзывы: