background image

(4.) Insert brush end of cable in burner inlet opening of

cell, and proceed to clean 2 lower passes of cell in

same manner as 2 upper passes.

(5.) Repeat foregoing procedures until each cell in

furnace has been cleaned.

(6.) Using vacuum cleaner, remove residue from each

cell.

(7.) Using vacuum cleaner with soft brush attachment,

clean burner assembly.

(8.) Clean flame sensor with fine steel wool.
(9.) Reinstall burner assembly. Center burners in cell

openings.

9. Remove old sealant from cell panel and inducer backing

plate flange and apply new sealant to flange and reinstall on

cell panel, making sure all screws are secure.

NOTE:

A releasing agent such as PAM cooking spray or equiva-

lent (must not contain corn or canola oil, aromatic or halogenated

hydrocarbons or inadequate seal may occur) and RTV sealant

(G.E. 162, 6702, or Dow-Corning 738) are needed before starting

installation. DO NOT substitute any other type of RTV sealant.

G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.

10. Reinstall elbow and inducer assembly.
11. Reconnect wires to the following components (Use connec-

tion diagram on wiring label, if wires were not marked for

reconnection locations.):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.

12. Reinstall internal vent pipe, if applicable.
13. Reinstall vent connector on furnace vent elbow. Securely

fasten vent connector to vent elbow with 2 field-supplied,

corrosion-resistant, sheet metal screws located 180° apart.

14. Replace blower access door only.
15. Set thermostat above room temperature and check furnace

for proper operation.

16. Verify blower airflow and speed changes between heating

and cooling.

17. Check for gas leaks.

WARNING:

Never use a match or other open flame to

check for gas leaks. Use a soap-and-water solution. A

failure to follow this warning could result in fire, personal

injury, or death.

18. Replace outer access door.

IV. ELECTRICAL CONTROLS AND WIRING

CAUTION:

There may be more than 1 electrical supply

to the unit. Check accessories and cooling unit for

additional electrical supplies.

The electrical ground and polarity for 115-v wiring must be

properly maintained. Refer to Fig. 6 for field wiring information

and to Fig. 7 for furnace wiring information.

NOTE:

If the polarity is not correct, the STATUS LED on the

control will flash rapidly and prevent the furnace from heating.

The control system also requires an earth ground for proper

operation of the control and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp fuse located

on the control. (See Fig. 8.) Any shorts of the 24-v wiring during

installation, service, or maintenance will cause this fuse to blow. If

fuse replacement is required, use ONLY a 3-amp fuse. The control

LED will display status code 24 when fuse needs to be replaced.
With power to the unit disconnected, check all electrical connec-

tions for tightness. Tighten all screws on electrical connections. If

any smoky or burned connections are found, disassemble the

connection, clean all parts, and wire conductors, and reassemble

properly and securely.
Reconnect electrical power to the unit and observe unit through 1

complete operating cycle. Electrical controls are difficult to check

without proper instrumentation; if there are any discrepancies in

the operating cycle, contact your dealer and request service.

Fig. 4—Position of Igniter to Burner

A00265

A00266

Fig. 5—Cleaning Heat Exchanger Cell

A91252

—5—

Содержание 312AAV L Series

Страница 1: ...nd the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WA...

Страница 2: ...uum cleaners or other cleaning tools 2 Soap powders bleaches waxes or other cleaning compounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning fluids or other vola...

Страница 3: ...furnace casing and away from blower compartment 8 Remove 2 screws holding blower assembly to blower deck and slide blower assembly out of furnace 9 Clean blower wheel and motor using a vacuum with so...

Страница 4: ...y combustion air incorrect size or damaged manifold orifice s improper gas or a restricted heat exchanger Action must be taken to correct the problem If it becomes necessary to clean the heat exchange...

Страница 5: ...proper operation 16 Verify blower airflow and speed changes between heating and cooling 17 Check for gas leaks WARNING Never use a match or other open flame to check for gas leaks Use a soap and wate...

Страница 6: ...LED status 4 If furnace is operating properly and continuously lit LED indicates proper operation replace outer access door 5 Component Test can also be initiated by performing the following a Remove...

Страница 7: ...nds 15 Blower off delay gas heating selections are 90 120 150 180 seconds cooling or heat pump 90 seconds or 5 seconds when DHUM is on LEGEND ACR AIR CONDITIONING RELAY SPST N O ACRDJ AIR CONDITIONING...

Страница 8: ...omponent After replacing any component verify correct operation sequence Fig 8 Furnace Control A00380 LHT OFF DLY ON OFF W2 BLW 24 V THERMOSTAT TERMINALS SETUP SWITCHES LOW HEAT ONLY AND BLOWER OFF DE...

Страница 9: ...for Short circuit in secondary voltage 24VAC wiring 31 HIGH HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED Check for Control relay may be defective Refer to 32 32 LOW HEAT PRESSURE SWITCH DID...

Страница 10: ...speed and run for the entire component test then shift to low speed for 10 seconds The HSI blower motor low heat speed blower motor high heat speed and blower motor cool speed will run for 10 15 sec e...

Страница 11: ...PEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 SECONDARY VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwo...

Страница 12: ...2000 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 12 Printed in U S A SP0468 Catalog No 5331 201...

Отзывы: