Table 2 – Airflow adjustments heating mode_ECM
motor
SW1-HEAT
INPUT
DIP Switch Positions
USGPH
1
2
POSITION
OFF
OFF
A
0.70
ON
OFF
B
0.60
OFF
ON
C
0.50
ON
ON
D
ALL
Table 3 – Airflow adjustments air conditioning
mode_ECM motor
SW2-COOL
INPUT
DIP Switch Positions
USGPH
1
2
POSITION
OFF
OFF
A
3.0
ON
OFF
B
2.5
OFF
ON
C
2.0
ON
ON
D
1.5
Table 4 – Airflow adjustments all modes_ECM
motor
SW3-ADJ (Adjustment)
CFM HTG.
CFM A/C.
DIP Switch Positions
% Increase
% Increase
1
2
POSITION
or decrease
or decrease
OFF
OFF
A
0%
0%
ON
OFF
B
10%
10%
OFF
ON
C
-10%
-10%
ON
ON
D
N/A
0%
Table 5 – Delay adjustments all modes_ECM motor
SW4-Delay
INPUT
DIP Switch Positions
USGPH
1
2
POSITION
OFF
OFF
A
0.70
ON
OFF
B
0.60
OFF
ON
C
0.50
ON
ON
D
ALL
2.13
INSTALLATION OF
ACCESSORIES
WARNING
E
LECTRICAL SHOCK HAZARD
.
Turn OFF electrical power at the fuse box or service panel
before making any electrical connections and ensure a proper
ground connection is made before connecting line voltage.
Failure to do so can result in death or bodily injury.
2.13.1
Humidifier (HUM)
The electronic board supplies 120 VAC for a humidifier on the HUM
terminal. It supplies 120 VAC electric power when the burner is in
operation.
A 24 VAC signal can also be supplied from the W and C terminals on
the blower electronic board to activate a switching relay.
Also refer to the instructions supplied with the accessory.
2.13.2
Electronic Air Cleaner (EAC)
The EAC terminal on the electronic board supplies 120 VAC when the
blower is operating in the heating or air conditioning mode. This signal
can be used to activate an electronic air cleaner that is not equipped
with an air flow switch. If the cleaner is equipped with an air flow
switch, the S terminal on the PSC electronic board or one of the 120
VAC terminals on the ECM electronic board can be used to provide a
constant supply of 120 VAC.
Also refer to the instructions supplied with the accessory.
2.13.3
Air Conditioner (or Heat Pump)
An air conditioning coil may be installed on the supply air side ONLY.
WARNING
P
OISONOUS CARBON MONOXIDE GAS HAZARD
.
Install the evaporator coil on the supply side of the furnace
ducting ONLY.
An evaporator coil installed on the return air side of the ducting
can cause condensation to form inside the heat exchanger,
resulting in heat exchanger failure. This in turn, can result in
death, bodily injury and/or property damage.
A clearance of 15 cm (6") is required between the bottom of the coil
drain pan and the top of the heat exchanger. If a heat pump is installed,
a “dual-energy” thermostat, or other control is required, in order to
prevent the simultaneous operation of the furnace and the heat pump. It
also prevents a direct transition from heating by way of the heat pump to
heating with oil. Refer to the thermostat instructions or those of another
control used for the proper wiring.
If a coil blower compartment is used, install air tight, motorized and
automatic air dampers.
Cold air coming from the coil and passing
across the furnace can cause condensation and shorten the life of the
heat exchanger.
3
OPERATION
3.1
START-UP
CAUTION
DO NOT START THE BURNER UNLESS THE BLOWER ACCESS
DOOR IS SECURED IN PLACE.
Before starting up the unit, be sure to check that the following
8
Содержание 098 Series
Страница 17: ...Figure 9 Furnace Dimensions 16...
Страница 18: ...Figure 10 Wiring diagram 4 speed motor PSC 17...
Страница 19: ...Figure 11 Wiring diagram variable speed mortor ECM 18...
Страница 20: ...Figure 12 Parts list with 4 speed motor PSC 19...
Страница 22: ...Figure 13 Parts list with variable speed motor ECM B50074I 21...
Страница 41: ...Figure 9 Dimensions de la fournaise 17...
Страница 42: ...Figure 10 Diagramme lectrique Moteur 4 vitesses PSC 18...
Страница 43: ...Figure 11 Diagramme lectrique Moteur vitesse variable ECM 19...
Страница 44: ...Figure 12 Liste de pi ces Moteur 4 vitesses PSC 20...
Страница 46: ...Figure 13 Liste de pi ces Moteur vitesse variable ECM B50074I 22...