Date:
8-4-2010
Revision: 0
Form:
2396
42
Code Description
Recommended
Troubleshooting of Lockout Codes
Code
68
ILK ON
This lockout occurs when the interlock string is closed before the
blower starts. The airflow switch is the only device in the
interlock string that will open when in standby. Probable causes
are.
1. Air pressure in the boiler room has become negative.
2. Excessive downdraft in the stack.
3. Blower is spinning before being commanded by the
hydronic control. Make sure blower is not running in
standby.
4. Airflow switch is stuck closed.
L
69
Pilot test hold
1. Verify Run/Test is changed to Run.
2. Reset Module.
3. If fault repeats, replace module.
H
70
Wait for leakage
test completion
1. Internal Fault. Reset Module.
2. If fault repeats, replace module.
H
71-77 RESERVED
78 Demand
Lost
in
Run
1. Check wiring and correct any possible errors.
2. If previous steps are correct and fault persists, replace the
module.
H
79
Outlet high limit
1. Check wiring and correct any possible errors.
2. Replace the Outlet high limit.
3. If previous steps are correct and fault persists, replace the
module.
H or L
80
DHW high limit
1. Check wiring and correct any possible errors.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists, replace the
module.
H or L
81
Delta T limit
1. Check Inlet and Outlet sensors and pump circuits for proper
operation.
2. Recheck the Delta T Limit to confirm proper setting.
3. If previous steps are correct and fault persists, replace the
module.
H or L
82
Stack limit
1. Check wiring and correct any possible errors.
2. Replace the Stack high limit.
3. If previous steps are correct and fault persists, replace the
module.
H or L
83-90 RESERVED
91
Inlet sensor fault
1. Check wiring and correct any possible errors.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists, replace the
module.
H
92
Outlet sensor fault
1. Check wiring and correct any possible errors.
2. Replace the Outlet sensor.
3. If previous steps are correct and fault persists, replace the
module.
H
93
DHW sensor fault
1. Check wiring and correct any possible errors.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists, replace the
module.
H
94
Header sensor fault 1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace the
module.
H
95
Stack sensor fault
1. Check wiring and correct any possible errors.
H
Содержание Triple-Flex 150
Страница 16: ...Date 8 4 2010 Revision 0 Form 2396 10 Section 2 Start Up and Operation Triple Flex High Efficiency Boilers ...
Страница 56: ...Date 8 4 2010 Revision 0 Form 2396 50 Section 3 Care and Maintenance ...
Страница 61: ...Date 8 4 2010 Revision 0 Form 2396 55 Section 4 Lead Lag ...
Страница 64: ...Date 8 4 2010 Revision 0 Form 2396 4 3 SYSTEM WIRING HOOKUP Figure 40 LL Multi Boiler Field Wiring 58 ...