Design and construction features
that assure reliable performance

Water Boiler

Combination thermometer and altitude
gauge, ASME Code rated boiler relief
valve, water temperature control (240°F
max std.), high limit control, probe
LWCO.

Steam Boiler

Combination low water cutoff and pump
control, auxiliary low water cutoff with
manual reset, high limit pressure con-
trol, ASME-rated safety valve, water
glass set.

Atmospheric equipment

Electronic combustion safety control,
automatic operating gas valve, safety
gas valve, pilot solenoid valve, electric
ignition assembly, main manual gas
shut-off valve, pilot shut-off valve,

When ordering, please specify:

1. Boiler size

2. Supply and return

temperatures required

3. Boiler relief valve setting

4. Type of fuel: natural or LP

5. If gas, type, BTU content,

specific gravity and
pressure available

6. Optional extra equipment

or construction

7. Special approvals required

(UL, CSD-1, FM, or IRI)

8. Altitude

Bryan K Series Boilers Standard and Optional Equipment

STANDARD EQUIPMENT
FURNISHED

A.

Heavy steel boiler frame, built and stamped in accordance with the ASME boiler code.
Hot water boilers constructed as standard for operating pressures to 160 psi. Also
available for higher operating pressures. Steam boilers constructed as standard for
operating pressures of 15 psi or 150
psi. Also available for higher operat-
ing pressures. Large steam release
area for dry steam.

B.

Water leg downcomers to insure rapid
internal circulation and temperature
equalization.

C.

Bryan flexible water tubes, easily re-
placeable, requiring no welding or
rolling. Tubes installed from one side.

D

. Boiler tube access panel bolted tightly

and sealed to boiler frame. Con-
structed of 2" insul-wool high tem-
perature insulation in steel framework.
Tubes installed from one side for easy
accessible service and inspection.

E.

Boiler jacket, heavy gauge zinc coated,
with attractive enamel finish. Boiler
jacket insulated with 1½" fiberglass to
insure cool jacket.

F.

Atmospheric gas burner controls — alloy steel
atmospheric burner. Quiet electric ignition and operation.
No moving parts or complicated adjustments.

G.

All controls, gauges, relief valve(s) are factory installed and wired and easily
accessible for servicing.

H.

Control panel: all controls installed and connected to terminal strip.

OPTIONAL
CONSTRUCTION:

Steam boiler

Optional construction to ASME
Power Boiler Code requirements for
pressure exceeding 150 psi to maxi-
mum of 300 psi design pressure.

Hot water boiler

Optional construction to ASME
Power Boiler Code requirements
for temperatures exceeding 240°
F and/or pressure exceeding 160
psi to maximum of 285° F operat-
ing and 300° F  design tempera-
ture and 250 psi.

OPTIONAL EQUIPMENT,
EXTRA COST:

1. Manual reset high limit control

2. Manual reset low water cutoff

3. Auxiliary low water cutoff (water)

4. Combination low water cutoff

and feeder

5. Alarm bells or horns

6. UL, CSD-1, FM, IRI or other

insurance approved control
systems

7. Low fire start, Hi-Lo or

modulation fire control

8. Indicating lights, as desired

G

F

E

D

H

A

C

B

9. Lead-lag systems for two or

more boilers with or without
outdoor reset control

10. Heat exchanger coils for

domestic water

pilot and main gas pressure regulators,
barometric draft controller, all controls
installed and wired standard voltage
120/1/60.

Содержание Knockdown K-350

Страница 1: ...iler K500 W GI Form No 4950 1 03 Originators of the Flexible Water Tube design Bryan Flexible Water Tube K Series Steam Water Boilers 3 500 000 to 6 500 000 BTUH Atmospheric gas fired Steam Boiler K 350 S150 GI ...

Страница 2: ...ntsoftheASME Boiler and Pressure Vessel Code Efficient Flexible Water Tube design The Bryan bent water tube provides rapid internal circulation for maximum heat transfer and operating efficiency Easily replaceable tubes Tubes are easily removable and replaceable without welding or rolling Requires little service space No Thermal Shock The flexibility of the bent water tube design elimi nates all p...

Страница 3: ...iring no welding or rolling Tubesinstalledfromoneside D Boilertubeaccesspanelboltedtightly and sealed to boiler frame Con structed of 2 insul wool high tem peratureinsulationinsteelframework Tubesinstalledfromonesideforeasy accessibleserviceandinspection E Boilerjacket heavygaugezinccoated with attractive enamel finish Boiler jacketinsulatedwith1 fiberglassto insure cool jacket F Atmospheric gas b...

Страница 4: ...hone 765 473 6651 Internet www bryanboilers com Fax 765 473 3074 E mail bryanboilers iquest net NOTE Gas train and control location dimensinos will vary depending on job specifications and conditions Dimensions and specifications are subject to change without notice Consult factory for certified dimensions STEAM BOILER DIMENSIONS inches cm A B C D E F G H I J K L BOILER Length Flue Flue Overall Ga...

Отзывы: