background image

Low initial cost, reliable  operating effi ciency
deliver substantial return on investment

Bryan EB Series Boiler Specifi cations

 

 

                             NOMINAL OUTPUT  

STEAM 

APPROX. 

 

BOILER INPUT 

 

 

OUTPUT  

SHIP WT.

 

MODEL MBH 

(KW)

 

MBH (KW)* 

BHP* 

LBS./HR** (KG) 

LBS. (KG)

 

EB-75 

3,200 (938) 

2,560 (750) 

75 

2,639 (1,197) 

5,810 (2,635)

 

EB-100 

4,200 (1,230) 

3,360 (984) 

100 

3,463 (1,570) 

7,110 (3,225)

 

EB-125 

5,250 (1,538) 

4,200 (1,230) 

125 

4,329 (1,963) 

8,300 (3,765)

 

EB-150 

6,300 (1,845) 

5,040 (1,476) 

150 

5,195 (2,356) 

8,420 (3,819)

 

EB-175 

7,325 (2,146) 

5,860 (1,717) 

175 

6,041 (2,740) 

11,175 (5,069)

 

EB-200 

8,500 (2,490) 

6,800 (1,992) 

200 

7,010 (3,179) 

11,305 (5,128)

 

EB-240 

10,000 (2,930) 

8,000 (2,344) 

240 

8,247 (3,740) 

14,455 (6,557)

NOTES: * 

 

Nominal output based on boiler industry standard of 80% of input. Actual combustion effi ciencies will be fuel dependent.

                  **  Lbs. steam per hour from and at 212° F.

L.

 Internal water-cooled 

fur nace with low heat 
release rate.

M.

 Steam boilers with 

extra large drum with high 
steam release area ensure 
stable water level and dry 
steam.

N.

 Pressurized design: 

inner fi reside casing con-
structed of heavy gauge 
steel, completely seal-
welded, lined with high 
temperature insulation 
and refractory.

J

F

A

E

C

I

B

D

N

L

K

D

M

Quality Construction Features:

A.

 Water side   or steam side interior  ac cessible 

for clean 

out and inspection, front and rear 

open ings, upper and lower drums.

B.

 Large volume water leg down comers pro-

mote rapid internal circulation, temperature 
equalization and effi cient heat transfer.

C. 

Boiler tube and furnace area access panels: 

heavy gauge steel casing with 2

 

high tem-

perature ceramic fi ber and insulation, bolted 
and tightly sealed to boiler frame.

D.

 Flame observation port at rear of boiler.

E.

 Single side access; combustion chamber, tubes and 

burner head are completely accessible from one side 
simplifying maintenance and minimizing fl oor space.

F.

 Minimum sized fl ue vent. 

G.

 Control panel: all controls installed with connections 

to terminal strip. 

H.

 Forced draft, fl ame retention head type burner. Effi -

cient combustion of oil or gas, plus quiet operation. 

I.

 Heavy steel boiler frame, built and stamped in accor-

dance with the appropriate ASME Boiler Code.

J.

 Heavy gauge steel boiler jacket with rust-resistant 

zinc coating and enamel fi nish, insulated with 1½

 

fi berglass to ensure exceptionally cool outer surface.

K.

 Bryan bent water tubes are flexible, individually 

replaceable without welding or rolling. Never more 
than two tube configurations. 

G

H

• True “fl exible water tube” design

• High quality steam for heat 
 or process

• Pressurized fi ring for maximum 

performance

Содержание EB-200-W-FDGO

Страница 1: ...Form No 8100 1 06 Bryan Flexible Water Tube EB Series Steam Water Boilers 3 200 000 to 10 000 000 BTUH Forced draft gas oil or dual fuel fired Water Boiler EB 200 W FDGO Originators of the Flexible Water Tube design BRYAN BOILERS ...

Страница 2: ... M Quality Construction Features A Waterside orsteamsideinterior accessible for cleanout and inspection front and rear openings upper and lower drums B Large volume water leg downcomers pro mote rapid internal circulation temperature equalization and efficient heat transfer C Boilertubeandfurnaceareaaccesspanels heavy gauge steel casing with 2 high tem perature ceramic fiber and insulation bolted ...

Страница 3: ...es to maximum fire side heat transfer and overall boiler efficiency Thermal blend water return Bryan s unique thermal blend return blends cold or cooler return water with warmer boiler water blending it to design operating temperatures An injector tube directsthe mixed waterflowthroughthedowncomerto the lower header and heating surfaces at a temperature abovepossiblecondensingconditions Thisreduce...

Страница 4: ...6 6 35 15 25 15 25 50 8 52 7 121 92 81 28 228 60 Steam Heating Processing Boilers DIMENSIONS in inches cm A B C D E F G H I J K L Boiler Length Width Height Gas Supply Clearance Min Tube Floor to Model of Outside Over Overall Train Nozzle Return Flue Flue for Servicing Removal Flow Number Jacket Jacket Jacket Length Connection 15 psi 150 psi Conn Size Location Burner Clearance Nozzle EB 75 S 75 55...

Отзывы: