PROGRAMMING 

 
Programming/setting of the 

P966

P966

P966

P9660

0

0

0

 is carried out using the 3 buttons located 

behind the transparent cover.  

 

 

 

The 

 button selects the required parameter to be changed. The 

 

 

buttons either increment or decrement a value accordingly.  

Any adjustments made are stored by the pressing and holding of the 

 button 

until the LCD shows the word “Saved!

Saved!

Saved!

Saved!” See Section 6. SAVING OF SETTINGS. 

 

Please read the 

“Notes during programming”

 before commencing with the 

following.

 

 

1A. TOROID RATIO  

Setting the Toroid Ratio will allow the “actual” Earth fault current (Io) to be 

displayed on the LCD which represents that of the current flowing through the parallel 
connected, external CT’s. If no CT’s are used, the parameter should be set to 5/5 (i.e. 
1:1).  Use this if the fault current is likely to be <5A. 

Default setting is “5/5” 

 

 

Press and hold the 

 button. The LCD displays a screen showing the 

characters “User Settings

User Settings

User Settings

User Settings” then the following screen appears…

 

 
 
 
 
 

 

 

Press either 

 or 

to set the primary value of the external CT’s. 

 

 

The digit after the forward slash “/” cannot be changed. 

 

1B. NETWORK FREQUENCY 

Default setting is “50Hz” 

 

 

Whilst in the same screen as that for the Toroid Ratio (see 1A.), press  

 

the 

 button to display the options for NETWORK FREQUENCY

NETWORK FREQUENCY

NETWORK FREQUENCY

NETWORK FREQUENCY. 

 
 
 
 
 

 

 

Press either 

 or 

to select between 50Hz or 60Hz. This should be 

set to suit the frequency of the network being monitored. 

 

Press and hold the 

 button to set the options for ““““Relay

Relay

Relay

Relay    1

1

1

1” 

” 

” 

” as described 

in the next section. 

 
2. RELAY 1 SETTING 

Default setting for Relay 1 is Manual resetting mode. 

 

 

The LCD displays the following screen. 

 

 
 
 
 
 

 
 
 
 
 

Actual LCD presentation when adjustable parameters are displayed. 

 
 
 
 
 
 
 
 
 

 

Press either 

 or 

 to select between AUTO

AUTO

AUTO

AUTO resetting or MAN

MAN

MAN

MANUAL 

resetting (after a fault has occurred).

                               

 

Press and hold the 

 button to set the options for “Relay 2” 

Relay 2” 

Relay 2” 

Relay 2” as described 

in the next section. 

 

 
 
 
 
 
 

continued on next page… 

 

INSTALLATION 

 
 
 
 
 

 

BEFORE INSTALLATION, ISOLATE THE SUPPLY. THIS PRODUCT IS 
DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS. 
ENSURE ALL ARE ISOLATED^

 

 

Remove the 

P966

P966

P966

P9660

0

0

0

 from the packaging. 

 

Lift the raised part of the side clip in order to withdraw from the housing. 
Carry this out on each side.  

 

Insert the 

P966

P966

P966

P9660

0

0

0

 into the panel cut-out and fit the side clips back on to the 

housing.

 

 

Slide the clips towards the front of the unit until they come in to contact with 
the reverse of the panel. The unit is now secured in place.

 

 

Wire the supplied female pluggable connectors as required.

 

 

Plug the connectors into the relevant sockets on the rear of the unit.

 

 

The 

P966

P966

P966

P9660

0

0

0

 is now ready for powering and programming. 

 

 

The front window of the P9660 is supplied with a clear protective film which can be 

removed as and when necessary. 

 

 

^ When carrying out future maintenance on the product or application and it 
becomes necessary to disconnect the connectors from the product, ensure for 
the Current Transformer connector, they do not remain open circuit

they do not remain open circuit

they do not remain open circuit

they do not remain open circuit. This can 

lead to high voltages being present on this connector. 

 

 

NORMAL OPERATION 

 

 

Apply power to the unit and the green 

“Power supply”

 LED will illuminate. 

 

 

The LCD will momentarily display a welcome screen as shown…

 

 
 
 
 
 

 
 
 
 
 

 

….then after a short delay reverts to indicating the following information:

 

 
 
 
 
 
 

 

 

TEST MODE 

 
 

 

Press and hold the

 

 button and both relays will energise. The LCD will 

display the characters 

“TEST”

 and the product part number (as below). The 

LCD backlight and red 

“Trip”

 LED will flash.

 

 
 
 
 
 

 
 
 

 

Release the 

 button and the relay(s) will remain energised if set to Manual 

reset or de-energise if set to Auto reset.

 

 
 
 
 

 

Press the 

 to de-energise relay(s) which are set to Manual reset. The 

LCD will revert back to Normal operation. The LCD backlight and red 

“Trip

” LED will stop flashing. 

 

Testing should be carried out on a regular basis to check the integrity of the 

P9660. 
 

DO NOT use this product to provide a means of isolating circuits in 
order to work on when placed in the “TEST”

“TEST”

“TEST”

“TEST” mode. This should only be 

done by means of operating isolators, circuit breakers or other 
methods of removing power in this application. 

 

 

 

 

 

 

I

O

 

  

0.00

A    

 

 

Installation work must be carried

out by qualified personnel.

 

Actual Earth 
fault current 

 

 

TEST

 

TYPE: P9660 

Ver: X.X

 

TOROID RATIO 
 

5 / 5 

 

RELAY 

CONFIGURATION 

 
            AUTO         
           

MAN 

 

Digits which 
can be adjusted 

TYPE: P9660

 

Ver: X.X 

 

Model No. 

 
 

Version 

 

TOROID RATIO 
 

5 / 5 

 

NETWORK FREQUENCY 

 

50Hz 

60Hz 

 