Spring loaded nipple.
Filler cap.
Adding Propylene Glycol prior to first use:
1: Connect the connection hose assembly to the main cooling unit only.
2: Depress the spring loaded nipple on the male connector at the end on the hose
assembly into the base of a bucket or similar container.
3: Bleed approximately 2.5 litres of water into the bucket.
4: Remove the filler cap at the rear of the machine and add approximately 2.5 litres of
Propylene Glycol to the tank.
5: Ensure that the tank is not over filled. Over filling can cause excess water to be
expelled to the environment through the condensate pump.
6: The water tank is full when the fluid is approximately 100mm below the top of the
filler spout.
7: Replace the filler cap.
The appliance is now ready for installation and operation.
Ensure the machine is disconnected from the power supply before following this procedure.
Ensure that all local regulations are adhered to when using Propylene Glycol.
The water cooled split has a fluid capacity of approximately 10 litres when fitted with a
single 5M connection hose assembly.Each extra 5M hose assembly contains approximately
2.8 litres of water.
It is recommended that a 25% Glycol to 75% water mix is used. This can be increased to
50% when the external heat exchanger is located in a very cold environment.
Failure to add Glycol could result in costly damage to the machine and will invalidate the
warranty.
Male water connector.
Rear of main cooling unit.
SHEET 10 OF 17
Содержание MCSe 7.3-21
Страница 1: ...MCSe 7 3 PORTABLE WATER COOLED AIR CONDITIONER PRODUCT MANUAL MCSe 7 3 21 SHEET 1 OF 17 ...
Страница 14: ...41 49 42 44 45 46 39 38 40 43 50 48 External heat exchanger Spare parts SHEET 14 OF 17 ...
Страница 15: ...Spare parts Cont d SHEET 15 OF 17 ...
Страница 16: ...Wiring diagram Live circuit MCSe7 3 21 Wiring diagram Neutral and Earth circuit MCSe7 3 21 SHEET 16 OF 17 ...
Страница 17: ...QB70 water pump curve Condensate pump curve Condensate pump flow rates l h SHEET 17 OF 17 ...