WARNINGS

These instructions should be read by:

The specifying engineer.

The installation engineer.

The user.

The service engineer.

Failure to follow  these instructions may result in risk of

         personal injury or damage to the equipment.

Damage due to a failure to follow these instructions will 

         invalidate the warranty.

The appliance must be serviced by qualified engineers

         in compliance with local regulations.

The appliance must be switched off and disconnected from

         the power supply before any work is carried out.

There are no user controls inside the appliance casing.

Do not place anything on top of the appliance.

An air gap of at least 300mm should be allowed at the front 

         and rear of the unit to ensure a clear airflow. 

Do not disconnect the appliance from  the supply under load.

For internal use only. Do not use out of doors.

Extension cables should be correctly rated for the load,fully

         unwound and never run through water or over sharp edges.

Always transport and store in an upright position.

Maximum operating temperature 35 C.

Minimum operating temperature 21 C.

Specifications:

The MCM280 is a Mono-block portable air conditioning unit.

It is connected to  a 13 Amp. 230Vac. 50Hz (60Hz on selected models)power supply and comes 

fitted with a fused uk moulded plug.

It is recommended that the supply to the machine should be protected by a 30mA RCD

PDF created with pdfFactory trial version 

www.pdffactory.com

Содержание MCM280

Страница 1: ...PRODUCT MANUAL MCM280 PORTABLE AIR CONDITIONER MCM280 PDF created with pdfFactory trial version www pdffactory com ...

Страница 2: ...appliance An air gap of at least 300mm should be allowed at the front and rear of the unit to ensure a clear airflow Do not disconnect the appliance from the supply under load For internal use only Do not use out of doors Extension cables should be correctly rated for the load fully unwound and never run through water or over sharp edges Always transport and store in an upright position Maximum op...

Страница 3: ...d be noted that the compressor will not start if the fans are not running or the ambient temperature is below 21 C The compressor is fitted with a start delay timer and will not run for 3 minutes from activation of the cooling switch This device is designed to protect the compressor from repeated start stop cycles Allow a minimum of 10 minutes for the unit to start cooling During the cooling proce...

Страница 4: ...Discharge hoses Exhaust discharge Operation and controls Power on lamp Fans on rocker switch Variable fan speed controller Cooling on rocker switch Thermostat Tank full lamp PDF created with pdfFactory trial version www pdffactory com ...

Страница 5: ...echanism is operating correctly and the drain hose is present and in good condition 3 Regularly inspect the mains cable and plug for signs of damage or wear Do not operate the machine with a damaged mains cable 4 Check that the castors are running freely and that the breaking mechanisms are working correctly Troubleshooting guide SHOULD YOU CONTINUE TO EXPERIENCE PROBLEMS PLEASE CONTACT THE SUPPLI...

Страница 6: ...35 Exploded view 2 11 12 24 30 31 32 33 34 36 1 3 4 5 6 7 8 9 10 13 14 15 16 17 18 19 20 21 22 23 25 34 26 27 28 29 PDF created with pdfFactory trial version www pdffactory com ...

Страница 7: ... BW0201230 GALVANISED DRIPTRAY POA 21 BW030201 1500 DUCT C W PLASTIC COLLAR POA 22 FA010317 EVAPORATOR FAN POA 23 BW0201231 FRONT TOP PANEL POA 24 EL020423 MODULAR TERMINAL BLOCK POA 25 EL030111 55uf CAPACITOR POA 26 EL030704 INDICATOR LIGHT POA 27 EL030109 0 1 ROCKER SWITCH POA 28 EL030145 SPEED CONTROLLER WITH KNOB POA 29 EL030414 THERMOSTAT WITH KNOB POA 30 BW0201233 ELECTRICS PLATE POA 31 EL03...

Страница 8: ...N 23 MCM280 16 WIRING DIAGRAM 13 12 Thermostat 13 9 9 Termination crimp White Blue Yellow Red EC Evaporator Fan 04 03 16 Control Panel Electrics Panel Condenser fan Cooling on Tank full lamp Power lamp Microswitch Compressor Blue Brown C S R 6 5 4 3 2 1 E N L 10v DC control lead 230v Power fly lead EC Fan Controller Connector Block Rear Connector Block Motor Fly lead Relay 6531 8 230 0300 Capacito...