Programming
GB
59-273 390.4 04.10 Fh
0-10 V / Relay module CISP C
21
6.
Programming
6.1
Settings table
• Only the most important parameters for the module CISP C are
listed in the table!
• In order to get to the setting levels: End User (E), Start-up (l)
and Specialist (F), press button OK.; After this, press for appro-
ximately 3 s the Information button, select the reqired level
with the rotating knob and acknowledge with the button OK.
Detailed information for programming of the integrated system
controller LMU 74 and setting tables with programmable parame-
ters are contained int he installation manual of the boiler.
Table 2: Setting the parameters
Function
Prog.-
No.
Setting
level
1
Standard
value
Modified
value
Configuration
Relay output K2
Default | Message output | Alarm output | operation mes-
sage | External transformer | Heating circuit pump HC2 |
circulation pump | Gate veil function | Pump hydraulic
bypass | feed pump Q8 | Basic function K2 | TWW-charging |
threshold analoguous signal RelCl | Exhaust gas flap | coll-
ector pump | fan switch-off
5920
I
Fan shutdown
rsp. Basic
function K2
Relay output 1 RelCl
Default | Message output | Alarm output | operation mes-
sage | External transformer | Heating circuit pump HC2 |
circulation pump | Gate veil function | Pump hydraulic
bypass | feed pump Q8 | Basic function K2 | TWW-charging |
threshold analogue signal RelCl | Exhaust gas flap | collec-
tor pump | fan switch-off
5922
F
Alarm output
Relay output 2 RelCl
Default | Message output | Alarm output | operation mes-
sage | External transformer | Heating circuit pump HC2 |
circulation pump | Gate veil function | Pump hydraulic
bypass | feed pump Q8 | Basic function K2 | TWW-charging |
threshold analoguous signal RelCl | Exhaust gas flap | coll-
ector pump | fan switch-off
5923
F
Status output
Relay output 3 RelCl
Default | Message output | Alarm output | operation mes-
sage | External transformer | Heating circuit pump HC2 |
circulation pump | Gate veil function | Pump hydraulic
bypass | feed pump Q8 | Basic function K2 | TWW-charging |
threshold analoguous signal RelCl | Exhaust gas flap | coll-
ector pump | fan switch-off
5924
F
Default
Function input RelCl
No | Modem function | Modem function inverse | Gate veil
function | Nominal value specification | Power specification
| Sensor hydraulic bypass | Feed-back exhaust gas flap |
generator lock | generator lock inverse | Generator lock
sensor
5973
I
Preselected
setpoint
resp. Prese-
lected output
Ext. Flow nominal value maximum
5975
F
100 °C
Ext. Power specification threshold
5976
F
5 %
1. E = End user; I =Commissioning; F = Specialist