Operation & Installation Manual RFP V2 Series
MA225 Rev 1
20 of 50
Note: When two batteries are used, it must be connected in parallel to increase the
battery backup time. All Brooks residential panels are 12V systems.
3.8
Termination of Field Wiring
All field wiring enters the panel via knock-outs on either top or rear of the cabinet and
is then terminated on the Termination Board SUB357B. An optional zone output card
SUB365 may also be connected utilising the same ribbon cable between the main
and termination boards.
Figure 7 RFP V2 Termination Board
The PCB layout of the new SUB357B is shown in Figure 7 above. Terminals are
provided to terminate two batteries, when only one battery is used, it can be
terminated in any of the two battery sets provided.
3.8.1
Smoke/Heat Alarm Inputs
The termination board is clearly labelled for positive supply (+), negative supply (-)
and interconnect (I) for Zone 1 to Zone 6 for RFP6. When RFP12 or RFP18 are
required, same additional termination boards SUB357B are added for zone 7-12 and
zone 13-18.
The RFP V2 is supplied with End-Of-Line device (EOL) SUB360 connected to every
zone however, when Smoke/Heat Alarms are connected to a zone, the EOL should
be moved to the last Alarm in the zone. The new EIB650iWX and EIB603CX
interface board SUB1012 has built-in EOL. The built-in EOL can replace the
hardwired SUB360 by setting the DIP switch position S3, refer to Table 5 Page 27
for correct DIP switch setting.
Note: EOL device SUB360 should not be used if the DIP switch is used to set the
Alarm to be the last Alarm in a zone and vice versa. This will lead to a zone fault.
3.8.2
Mains Voltage Input
The 230V
AC
mains cable terminates at the mains isolating switch located on the
inside rear of the cabinet then to the switch mode power supply.
3.8.3
Battery Input
Battery Leads are already connected to the termination board to connect the lead
acid battery. Ensure correct fitting of the battery, connect the Black lead to the
negative terminal and the Red lead to the positive terminal. When the battery