Operation & Installation Manual RFP V2 Series
MA225 Rev 1
14 of 50
3
Residential Fire Panel
3.1
RFP V2 Specifications
Table 2 Specifications of RFP V2 residential panels
Feature
Specification
No. of zones
6, 12 or 18
Max. no. of Alarms
12 Alarms per zone
Enclosure
Zinc steel 1.5mmm powder coated oyster
RFP6 V2: 400mm H x 320mm W x 135mm D
RFP12 /18: 6800mm H x 320mm W x 135mm D
Power Supply
Input: Universal 88 – 264V
AC,
50W
Output: 13.5-16.5 V
DC
adjustable, 50W (3.4A)
Nominal: 14.5V
DC
, 13.8V
DC
on battery terminals
Standby Supply
12V SLA batteries 7-30 AH
of Alarms fitted
Battery low setting
12.0 V
DC
Key switch Operation
“ON” System ON - Charger ON
“OFF” System OFF - Charger ON
“FIRE” activates all smoke/heat alarms
System Monitoring
Separate terminals for zone wiring loop in and out to
every Alarm, monitored either by EOL device or DIP
switch setting in the last Alarm
Fault (defect) Mode
Initiated by an abnormal system condition:
* Total power loss
* Ancillary outputs (common alarm) Isolated
* Short / Open circuit line fault
* System switched off
Fault Output
1 set changeover relay contact
Alarm Outputs
12V
DC
/ 1 Amp maximum, non-supervised
1 set changeover relay contact
Panic Input
Non-supervised N/O contact - activates all Alarms
Sounder Silence Switch
Acknowledges panel sounder
Alters tone from continuous to chirp (for battery low and
zone wiring fault)
Ancillary Isolate Switch
Isolates common alarm outputs and initiate Defect
Mode
Alarm Locate Switch
Silences all Smoke/Heat Alarms except those initiating
the alarm.
1
When larger battery capacity required, up to 2 x 15AH / 12V batteries can be paralleled to double the
battery size.