Operation & Installation Manual RFP V2 Series
MA225 Rev 1
19 of 50
3.6
RFP V2 Compatible Equipment
3.6.1
New Smoke / Heat Alarms
Smoke / Heat Alarm
Part No:
Photoelectric Smoke Alarm for Residential Panels
EIB650iWX
Heat Alarm for Residential Panels
EIB603CX
3.6.1
Other Equipment
Options
Part No:
RED MCP C/W RES.+ BB RESET + BROOKS GLASS
MRCSRR
Zone Output Relay Card (Z1-Z6)
SUB365
Relay / 12V output card
SUB600
Mimic Panel 24 – 72 LED's
Custom build
Note: Limit is 2 x MRCSRRs, Any sounder, strobe or combo per zone
3.6.2
Discontinued Alarms
Smoke / Heat Alarm:
Part No.
Replacement
Brooks ionisation smoke alarm
EIPFSICX6
No Replacement
Brooks photo-electric smoke alarm
EIPFSPCX6
EIB650iWX
Brooks heat alarm
EIPFSTCX6
EIB603CX
Note: If Discontinued Smoke/Heat Alarms already exist in a building, they can still
be used provided they are not over 10 years old. Do not mix new and old Alarms.
3.7
Power Supply
The primary and standby supplies are calculated to suit the system alarm and
standby requirements. If the primary power supply fails, the secondary supply will
provide sufficient current to maintain the system fully operational for a period
determined by number of Smoke / Heat Alarms and any added options.
A battery capacity calculation of RFP V2 with all the Smoke / Heat Alarms and
ancillary devices must be carried out to determine the battery size. The battery
capacity must meet the requirements of AS3786. Refer to Table 6, page 36 to
calculate the battery capacity.
3.7.1
Primary Power Supply / Battery Charger
The primary power supply for RFP V2 series is fully regulated switch mode power
supply 15V
DC
/ 50W. Nominal output is adjusted to14.5V
DC
(13.8V
DC
on the battery
terminals), maximum current 3.4A @ 14.5V. The power supply is capable of
supplying the max. alarm current of the RFP system without relying on battery.
Note: Power supply voltage output can be adjusted (if required) to the nominal
voltage using a potentiometer on the power supply PCB.
3.7.2
Standby Supply
The secondary supply is one or two 12V Sealed Lead Acid Batteries which under
normal operating conditions will be continuously charged by the primary power
supply. Battery capacity is dependent on the number of Smoke / Heat Alarms fitted.
Up to 2 X 15AH batteries connected in parallel can be fitted within the standard
enclosure.