3.6 Zone Inputs
3.6.1 Zone Input Specifications
Table 28 Zone Input Circuit Specifications
Item
Description
Number of zones per CIE
4 - 20 zones
Maximum number of detectors per zone
0
– 40, including MCPs
Maximum number of detectors per CIE
0
– 800, including MCPs
Maximum number of detectors in alarm per zone
Up to 2, including MCPs, heat or smoke detectors.
Maximum alarm current per zone
51mA
Typical Zone quiescent current
5mA
Typical zone input resistance in alarm condition per zone
560 Ohm
3.6.2 Compatible actuating devices
The compatible devices are listed on Table 29.
Table 29 Compatible Actuating Devices
Part No.
Manufacturer
Description
2324
Panasonic
Conventional detector base
4350
Panasonic
Conventional multi detector
12
4352
Panasonic
Conventional photoelectric smoke detector
4452
Panasonic
Conventional photoelectric smoke detector (new)
4375
Panasonic
Heat detector fixed temperature 60
⁰
4376
Panasonic
Heat detector fixed temperature 80
⁰
6295
Panasonic
Conventional enclosed heat detector 60 degrees
6296
Panasonic
Conventional enclosed heat detector 80 degrees
6297
Panasonic
Conventional enclosed heat detector 100 degrees
6298
Panasonic
Conventional enclosed heat detector 120 degrees
4318
Panasonic
Conventional combination heat detector Type A/B
MRCSRR
Cooper
MCP
The alarm resistance of the Panasonic conventional detector is determined by the detector base
(560Ω)
3.6.3 Zone Input Connection
The typical wiring of zone input circuit is shown Figure 14.
Figure 14 Typical Zone Input Circuit
12
4350 and 4352 are obsoleted, 4352 is replaced by 4452.