Technical Manual
FT420
– Iss 2.4
17
2.2 Main Control Board SUB880
The Main Control Board supports all the system controls and terminations. The field wiring for the
common FT420 outputs/inputs and the first 4 zone circuits are terminated on SUB880, refer to the
standard FT420 Block Wiring Diagram in Figure 39 page 76. The board layout is shown in Figure 2.
Figure 2 Main Control Board Layout (SUB880)
The board jumper settings and ancillary terminations are listed on Table 5 and Table 6 respectively.
Table 5 Main Control Board Jumper Settings
Designator
Description
Jumper
Status
Function
Factory
Default
JP1, JP2
Alarm device
selection.
ON
24V output to control the electronic sounders
Default
OFF
Dry-contact output to control the speaker circuits
JP3
Microprocessor
reset
ON
Set the system into reset state
OFF
Release reset for normal operations
Default