FT1020G3 Quick Operation Guide
Page
4
of
6
10
– TO ACKNOWLEDGE FAULT
1. Press Menu
Button
.
2.
Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the
FAULT ACKNOWLEDGE
menu (
H6
) by pressing
or
Button/s then press
to Accept
4. Scroll to check the list of faults by pressing
or
Button/s then press
to Accept
5. All faults must be individually acknowledged one by one.
6. When a fault is corrected before it has been acknowledged, the text "Serviced" is added after the
time, still has to be acknowledged to remove it on the display.
7. When a fault is corrected / serviced and acknowledged, it will disappear from the list (H6).
8.
If no furthers checks required, press the
button repeatedly back to main screen
.
11
– TO CHECK FAULTS INFORMATION
1.
Refer to Operation Manual FT1020G3 Rev 2.4,
check for the fault and resolution
process.
FAULT: 24V for external equipment output x, Control Unit xx
Page: 62
FAULT: 24V for routing equipment, Control Unit xx
Page: 62
FAULT: 24V out, output unit xxxxxx
Page: 62
FAULT: Alert annunciation unit xx, Control Unit xx
Page: 62
FAULT: Battery not connected, Control Unit xx
Page: 62
FAULT: Battery, technical number xxxxxx
Page: 62
FAULT: Battery zone xxx address xx
Page: 63
FAULT: Charger, Control Unit xx
Page: 63
FAULT: Charging external power supply, Control Unit xx
Page: 63
FAULT: Charging output unit xxxxxx
Page: 63
FAULT: Checksum MMI program, Control Unit xx
Page: 63
FAULT: Checksum system program, Control Unit xx
Page: 63
FAULT: Control unit xx has no contact with Control Unit xx, network x
Page: 63
FAULT: Cut-off loop x, Control Unit xx SCI nn <-> SCI nn
Page: 63
FAULT: Detector removed zone xxx address xx
Page: 64
FAULT: Earth fault (plus), Control Unit xx
Page: 64
FAULT: Earth fault (minus), Control Unit xx
Page: 64
FAULT: Earth fault, technical number xxxxxx
Page: 64
FAULT: Expansion board x, Control Unit xx
Page: 64
FAULT: Expansion board x, loop x, Control Unit xx
Page: 64
FAULT: External fuses, Control Unit xx
Page: 64
FAULT: External power supply, Control Unit xx
Page: 64
FAULT: External presentation unit xx, Control Unit xx
Page: 64
FAULT: Extinguishing system, Control Unit xx
Page: 64
FAULT: Factory settings, Control Unit xx
Page: 65
FAULT: Fan xx, technical number xxxxxx
Page: 65
FAULT: FB Silence switch, Control Unit xx
Page: 65
FAULT: Fire brigade panel xx, Control Unit xx
Page: 65
FAULT: Fuse on COM loop x, Control Unit xx
Page: 65
FAULT: High current, COM loop X, Control Unit xx
Page: 65
FAULT: High current consumption, Control Unit xx
Page: 65
FAULT: Interlocking input AAA-PP
Page: 66
FAULT: Internal short circuit COM loop x, Control Unit xx
Page: 66