2022/01/06 

 FT1020G3 Quick Operation Guide 

 

Page 

4

 of 

6

 

10 

– TO ACKNOWLEDGE FAULT 

1.  Press Menu

 

Button

.  

2. 

Select “Building Officer” Login then Key Enter Access Code. 

3.  Scroll to the 

FAULT ACKNOWLEDGE

 menu (

H6

) by pressing 

or 

 Button/s then press 

 

to Accept   

4.  Scroll to check the list of faults by pressing 

or 

 Button/s then press 

 to Accept 

5.  All faults must be individually acknowledged one by one. 
6.  When a fault is corrected before it has been acknowledged, the text "Serviced" is added after the 

time, still has to be acknowledged to remove it on the display. 

7.  When a fault is corrected / serviced and acknowledged, it will disappear from the list (H6). 

8. 

If no furthers checks required, press the 

 

button repeatedly back to main screen

.

 

 

11 

– TO CHECK FAULTS INFORMATION 

1. 

Refer to Operation Manual FT1020G3 Rev 2.4,

 check for the fault and resolution 

process. 

FAULT: 24V for external equipment output x, Control Unit xx 

Page: 62 

FAULT: 24V for routing equipment, Control Unit xx 

Page: 62 

FAULT: 24V out, output unit xxxxxx 

Page: 62 

FAULT: Alert annunciation unit xx, Control Unit xx  

Page: 62 

FAULT: Battery not connected, Control Unit xx 

Page: 62 

FAULT: Battery, technical number xxxxxx 

Page: 62 

FAULT: Battery zone xxx address xx 

Page: 63 

FAULT: Charger, Control Unit xx 

Page: 63 

FAULT: Charging external power supply, Control Unit xx 

Page: 63 

FAULT: Charging output unit xxxxxx 

Page: 63 

FAULT: Checksum MMI program, Control Unit xx 

Page: 63 

FAULT: Checksum system program, Control Unit xx 

Page: 63 

FAULT: Control unit xx has no contact with Control Unit xx, network x 

Page: 63 

FAULT: Cut-off loop x, Control Unit xx SCI nn <-> SCI nn 

Page: 63 

FAULT: Detector removed zone xxx address xx 

Page: 64 

FAULT: Earth fault (plus), Control Unit xx 

Page: 64 

FAULT: Earth fault (minus), Control Unit xx 

Page: 64 

FAULT: Earth fault, technical number xxxxxx 

Page: 64 

FAULT: Expansion board x, Control Unit xx 

Page: 64 

FAULT: Expansion board x, loop x, Control Unit xx 

Page: 64 

FAULT: External fuses, Control Unit xx 

Page: 64 

FAULT: External power supply, Control Unit xx 

Page: 64 

FAULT: External presentation unit xx, Control Unit xx 

Page: 64 

FAULT: Extinguishing system, Control Unit xx 

Page: 64 

FAULT: Factory settings, Control Unit xx 

Page: 65 

FAULT: Fan xx, technical number xxxxxx 

Page: 65 

FAULT: FB Silence switch, Control Unit xx 

Page: 65 

FAULT: Fire brigade panel xx, Control Unit xx 

Page: 65 

FAULT: Fuse on COM loop x, Control Unit xx 

Page: 65 

FAULT: High current, COM loop X, Control Unit xx 

Page: 65 

FAULT: High current consumption, Control Unit xx 

Page: 65 

FAULT: Interlocking input AAA-PP 

Page: 66 

FAULT: Internal short circuit COM loop x, Control Unit xx 

Page: 66 

Содержание firetracker FT1020G3 FDCIE

Страница 1: ...NT Alarm devices must be silenced before pressing Reset button Press and hold the Button for 1 second until the Fire Alarm Panel starts its reset sequence The system will now automatically reset all alarms Alarms may re trigger in the system if the alarm condition is still present Wait for 30 seconds and try again 4 TO DISABLE ISOLATE AN ACTIVE ALARM IMPORTANT Alarm devices must be silenced before...

Страница 2: ... Zone or Zone address menu B1 by pressing or Button s then press to Accept 5 Use the softkey to toggle between Zone 000 disable Zone and Zone 000 address 00 dis 6 Type in the zone number or the zone address number as required then press to Accept The zone or zone address that is disabled will be indicated by 7 Automatic Re enable a If Automatic re enable time not required scroll to highlight No th...

Страница 3: ... 2 Select Building Officer Login then Key Enter Access Code 3 Scroll to the Present System Status menu H4 by pressing or Button s then press to Accept 4 Scroll to Event Log menu U7 by pressing or Button s then press to Accept 5 Scroll by pressing or Button s then press to Accept to select event Log Alarm Interlocking Log General event log 6 If no furthers checks required press the button repeatedl...

Страница 4: ...ne xxx address xx Page 63 FAULT Charger Control Unit xx Page 63 FAULT Charging external power supply Control Unit xx Page 63 FAULT Charging output unit xxxxxx Page 63 FAULT Checksum MMI program Control Unit xx Page 63 FAULT Checksum system program Control Unit xx Page 63 FAULT Control unit xx has no contact with Control Unit xx network x Page 63 FAULT Cut off loop x Control Unit xx SCI nn SCI nn P...

Страница 5: ...ge 69 FAULT Sensor zone xxx address xx technical number xxxxxx Page 70 FAULT Short circuit loop x Control Unit xx SCInn SCInn Page 70 FAULT Site specific data SSD Control Unit xx Page 70 FAULT Site specific data alert annunciation unit xx Control Unit xx Page 70 FAULT Site specific data external presentation unit xx Control Unit Page 70 FAULT Supervised input x Expansion Board x Control Unit xx Pa...

Страница 6: ... instructions and other relevant operational procedures Software download Restart Perform Monthly test H1 Disable or re enable H2 Set Calendar and Clock H3 Present System Status H4 Service H5 Acknowledge Faults H6 Perform Zone Test Test Mode H7 Maintenance H8 Interlocking Outputs and Inputs H9 Change Password H10 ...

Отзывы: