![Brooks BOWS020W Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/brooks/bows020w/bows020w_operation-and-technical-manual_2818774012.webp)
OWS Standalone Manual
MA380 - Rev. 2.4
11
Designator
Type
No.
Label
Pin
Description
10
-
11
TRIGGER
+
Monitored trigger input. Connected to the N/O alarm
contact in the CIE or any N/O clean contact. EOL
resistor:
47kΩ 0.
5 Watt 1%.
12
-
TB2
Screw
terminals
1
24Vdc
(Supply)
+
20 – 30Vdc, 80mA – 120mA
2
-
3
EVAC
STROBE
+/-
Monitored bi-polarity visual warning output. 20-30V,
<=1A. Normal polarity for alert and reverse polarity
for evacuation.
EOL
resistor: 47kΩ 0.
5 Watt 1%.
4
-/+
5
BUZZER
+
Open collector output < 100mA @ 24V.
Drives the buzzer on the main display
6
-
7
FAULT O/C
NO
Wiring fault output. Dry-contact 30V @ 5A
Connects to a programmable input in the CIE.
Relay is normally energised
8
COM
9
NC
10
STDBY
+
Connected to Brooks amplifiers to reduce quiescent
current consumption. When the logic is high (5V),
amplifier output is disabled.
11
TX PRI
+
Transformer input. <100V RMS.
Connected to transformer primary coil output.
Maximum current based on amplifier type.
12
1
13
SPEAKER
+
Monitored speaker output.
Connected to the speaker line or the optional zone
splitter board SUB999.
EOL resistor: 47kΩ 0.
5 Watt 1%.
14
-
CON7
Screw
terminals
1
RS485
A
RS485 interface.
Connected to optional remote microphone with PA
zone selections e.g. PA-8, PA-16.
2
B
3
0V
CON12
Molex 3 Pin
Header
1
RS232
TX
RS232 interface.
TX – PC RX, RX – PC TX, 0V – PC GND. Used for
digital voice message programming.
2
0V
3
RX
CON15
IDC header,
2X10
N/A
I/O
EXPANSION
N/A
PA Expansion Interface.
Connect to the first OWS 4 Zone Splitter Board
CON14
IDC header,
2X5
N/A
DISPLAY /
KEYBOARD
+
IDC connector to the main display board.
CON13
IDC header,
2X10
N/A
N/A
Not used.
3.3.3 On-Board LED indications
In addition to the LED indicators on the front display, other indicators are provided on the OWS main
control board as shown in Table 5. The status of the fault indicators is determined by the number of
flashes of each LED. The flash rate provides further indication of the fault type e.g. whether the wiring
fault in the speaker circuit is open or shot circuit, etc.
11
Available only in Brooks series of amplifiers to minimise the quiescent current.
12
Not available in the standard standalone series of Brooks OWS
Содержание BOWS020W
Страница 24: ...OWS Standalone Manual MA380 Rev 2 4 23 5 BLOCK Wiring Diagrams Figure 12 F646B Iss 6 Standalone 20W OWS...
Страница 25: ...OWS Standalone Manual MA380 Rev 2 4 24 Figure 13 F647A Iss 8 OWS 60W Interfaced to CIE...
Страница 26: ...OWS Standalone Manual MA380 Rev 2 4 25 Figure 14 F647B Iss 8 OWS 60W Standalone...
Страница 27: ...OWS Standalone Manual MA380 Rev 2 4 26 Figure 15 F648A Iss 6 OWS 120W Interfaced to CIE...
Страница 28: ...OWS Standalone Manual MA380 Rev 2 4 27 Figure 16 F648B Iss 9 OWS 120W Standalone...
Страница 29: ...OWS Standalone Manual MA380 Rev 2 4 28 Figure 17 F649A Iss 6 OWS 250W Interfaced to CIE...
Страница 30: ...OWS Standalone Manual MA380 Rev 2 4 29 Figure 18 F649B Iss 6 OWS 250W Standalone...
Страница 31: ...OWS Standalone Manual MA380 Rev 2 4 30 Figure 19 F649C Iss 7 OWS 500W Interfaced to CIE...
Страница 32: ...OWS Standalone Manual MA380 Rev 2 4 31 Figure 20 Remote Desktop Microphone PA 1 PA 8 and PA 16 F626 Issue 4...