5. Optimize control settings
Instruments have been configured and optimized in the factory based on standard testing
conditions. Depending on the actual process conditions such as pressure, temperature and fluid
properties, an adjustment can improve the control response.
Disclaimer
Changing the control characteristics can have a negative effect on the behaviour of the Liquid
Dosing Set. It is strongly advised to:
- Log or store the default control settings
- Ensure process variations are minimized or eliminated
- Make changes with small increments
- Request support from a trained Bronkhorst service engineer
Please refer to the specific Liquid Flow Controller manual for more details and instructions.
5.1 Changing Filter Settings
Controller speed can be increased by changing or disabling output and sensor filters.
Disabling filters, however, not only makes the instrument faster, it also makes it more sensitive to
vibrations and electrical noise.
- Write value <_> to parameter 56 – Dynamic Display Factor
(change filter)
Value 1.0E-3
default response time
Value 3.00E-3
fast response time
Value 1.0
filter OFF
- Write value <_> to parameter 57 – Static Display Factor
(change filter)
Value 1.0E-2
default response time
Value 2.0E-2
fast response time
Value 1.0
filter OFF
- Write value <_> to parameter 74 – Sensor Exponential Smoothing Filter
(change filter)
Value 0.05
slow response time
Value 0.1
default response time
Value 0.2
increased response time
Value 1.0
filter OFF
Step DDE ProPar Name
Data
Type Execute Value
Remark
1
56
117/1
Dynamic Display
Factor
Float Write 1
Disable filter
2
57
117/2
Static Display Factor Float Write
1
Disable filter
3
74
117/4
Sensor Exponential
Smoothing Filter
Float Write 1
Disable filter