Brocade 6520 Hardware Reference Manual
7
53-1002705-01
Installation and safety considerations
2
DRAFT: BROCADE CONFIDENTIAL
•
The ambient air temperature does not exceed 40
°
C (104
°
F) while the switch is operating.
lists the acceptable environmental ranges for both operating and nonoperating (such as
during transportation or storage) conditions.
Rack considerations
For successful installation and operation of the switch in a rack, ensure the following rack
requirements are met:
•
The rack must be a standard EIA rack.
•
A rack space that is two rack units (2U) high; 8.90 cm (3.50 inches) high and 48.3 cm (19
inches) wide.
•
The equipment in the rack is grounded through a reliable branch circuit connection and
maintain ground at all times. Do not rely on a secondary connection to a branch circuit,
such as a power strip.
•
Airflow and temperature requirements are met on an ongoing basis, particularly if the
switch is installed in a closed or multirack assembly.
•
The additional weight of the switch does not exceed the rack’s weight limits or unbalance
the rack in any way.
•
The rack is secured to ensure stability in case of unexpected movement, such as an
earthquake.
Recommendations for cable management
The minimum bend radius for a 50 micron cable is 2 inches under full tensile load and 1.2 inches
with no tensile load.
Cables can be organized and managed in a variety of ways, for example, using cable channels on
the sides of the rack or patch panels to minimize cable management. Following is a list of
recommendations:
TABLE 2
Environmental requirements
Condition
Acceptable during operation
Acceptable During Non-Operation
Ambient
Temperature
0º to 40º C (32º to 104º F)
-25º to 70º C (-13º to 158º F)
Humidity
10% to 85% RH non-condensing, at
40º C (104º F)
10% to 90% RH non-condensing, at 70º C
(158º F)
Altitude
0 to 3 km (9,842 feet) above sea level
0 to 12 km (39,370 feet) above sea level
Shock
20 G, 6 ms, half-sine wave
33 G, 11 ms, half-sine wave, 3/eg Axis
Vibration
0.5 G sine, 0.4 gms random, 5-500 Hz
2.0 G sine, 1.1 gms random, 5-500 Hz
Air flow
Maximum - 186.89 cmh (110 cfm)
Nominal - ??.?? cmh (?? cfm)
NOTE: Airflow can be Forward or Reverse
depending on purchased option
NA
Heat dissipation
843.03 BTU/hr (no optics configuration)
1556.36 BTU/hr (fully populated port
configuration)
NA