4

2. C

ONTROLS

This unit is equipped with an integrated control located 
under the electrical compartment of the unit. Use the push 
button (

1

) to control the unit; the LED (

2

) will then show 

which mode the unit is in (see illustration at right and table 
below).

 

2.1 B

OOTING

 S

EQUENCE

The unit booting sequence is similar to a personal computer boot sequence. Each time 
the unit is plugged after being unplugged, or after a power failure, the unit will perform a 
30-second booting sequence before starting to operate.

During the booting sequence, the integrated defrost control LED will light AMBER for 
5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for 
the rest of the booting sequence. During this RED light phase, the unit is checking and 
resetting the motorized damper position. Once the motorized damper position completely
set, the RED light turns off and the booting sequence is done. 

NOTE: No command will be taken until the unit is fully booted.

NOTE: The integrated control 

must be turned OFF

 to use an optional main control.

If a problem occurs during the unit operation, its integrated control LED (

2

) will blink. The color 

of the blinking light depends on the type of error detected. Refer to Section 4 Troubleshooting 
on last page for further details.

1

2

VD0310

LED C

OLOR

R

ESULTS

AMBER

U

NIT

 

IS

 

ON

 L

OW

 S

PEED

GREEN

U

NIT

 

IS

 

ON

 H

IGH

 S

PEED

N

O

 

LIGHT

U

NIT

 

IS

 O

FF

 

OR

 

CONTROLLED

 

BY

 

A

 

MAIN

 

CONTROL

 

2.2 O

PTIONAL

 M

AIN

 

AND

 A

UXILIARY

 C

ONTROLS

For more convenience, this unit can also be controlled using an optional main wall 
control. Many models can be used, but only one main wall control can be connected to 
the unit.

NOTES:  1.  The integrated control 

must be turned OFF 

to use an optional main control.

 

2.  If an optional auxiliary control is used, if activated, the operation of this 

auxiliary control will override the optional main control operation.

For more information about the available controls and their operation modes, refer to the 

Main and auxiliary wall control User Guide

 (included with the ventilation unit and also 

available at www.broan.com).

Содержание ERVH100S

Страница 1: ...y guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Canada 22735 rev 01 READ AND SAVE THESE INSTRUCTIONS INSTALLER LEAVE THIS MANUAL WITH H...

Страница 2: ...mode or turn it OFF for a few hours Do not use your unit during construction or renovation of your house or when sanding drywall This type of dust may damage your system Since the electronic control...

Страница 3: ...able those parts require assembly knowledge that only manufacturer can garantee 1 SERVICE PARTS REPLACEMENT PARTS AND REPAIRS In order to ensure your ventilation unit remains in good working condition...

Страница 4: ...e taken until the unit is fully booted NOTE The integrated control must be turned OFF to use an optional main control If a problem occurs during the unit operation its integrated control LED 2 will bl...

Страница 5: ...y recovery core B Heat or energy recovery core filters 2 C Prefilter D HEPA filter E Core bracket VL0060 A B B D C E This unit needs quarterly and annual maintenances Refer to the illustration below t...

Страница 6: ...ith a soft brush attachment Wash both core filters under hot water with mild soap Rinse thoroughly and let dry completely Reinstall the recovery core with its filters and the retaining wire if present...

Страница 7: ...ore then reinstall with its filters ALL UNITS NOTE The recovery core must be reinstalled BEFORE the core bracket Discard HEPA filter and its prefilter and replace with new ones DO NOT FORGET TO WRITE...

Страница 8: ...hermistor The unit is still working but will defrost frequently Contact your installer 6 The LED of the integrated control is blinking AMBER Reset the unit by unplugging it for 30 seconds If the probl...

Страница 9: ...isterio de Recursos Naturales de Canad y la Agencia Federal de Protecci n Ambiental EPA de Estados Unidos Los productos cumplen las exigencias del programa ENERGY STAR nicamente cuando se emplean en C...

Страница 10: ...su casa o cuando se est n lijando paneles murales de yeso Este tipo de polvo puede da ar el sistema Dado que el sistema de control electr nico del aparato lleva un microprocesador el aparato podr a no...

Страница 11: ...debe usar repuestos genuinos de Broan NuTone LLC nicamente Estas piezas se han dise ado especialmente para cada unidad y se han fabricado conforme a las normas de certificaci n aplicables y un elevad...

Страница 12: ...inado NOTA El aparato no acepta ninguna instrucci n hasta que se haya puesto en marcha totalmente NOTA El control integrado debe estar apagado para poder usar el control principal opcional Si se produ...

Страница 13: ...e m s adelante para conocer las piezas interiores del aparato que se pueden desmontar 5 3 MANTENIMIENTO A N cleo de recuperaci n de calor o energ a B Filtros 2 del n cleo de recuperaci n de calor o en...

Страница 14: ...llo suave Lave los filtros del n cleo con agua caliente y un jab n suave Enjuague bien y deje que sequen completamente Vuelvaainstalareln cleoderecuperaci nysusfiltros yelalambrederetenci n sipresente...

Страница 15: ...nst lelo de nuevo con sus filtros PARA TODOS LOS APARATOS NOTA el n cleo de recuperaci n debe instalarse ANTES que el soporte del n cleo Deseche el filtro HEPA y su prefiltro y sustit yalos por nuevos...

Страница 16: ...ionando pero descongelar con frecuencia P ngase en contacto con su instalador 6 El diodo del control integrado parpadea en MBAR Reinicie el aparato desenchuf ndolo durante 30 segundos Si no hay cambio...

Отзывы: