53-1004106-15 Installation Guide
Brocade
®
X6-4 Director Hardware Installation Guide
WWN Card Replacement Task Guide
This section contains a guide to more complete, detailed steps in this section for installing or replacing WWN cards when
the device is running (hot-swap) or must be powered off (cold-swap). References are provided to more detailed WWN
removal and installation steps for further information.
NOTE
Contact Brocade Technical Support for the replacement WWN cards. Brocade Support will provide
replacements. Brocade Support requires the
supportSave
data so that the replacement cards can be
programmed before shipping to your site.
Replacing WWN Cards (Hot-Swap)
Use this procedure to replace WWN cards with system power on. You can use this procedure to replace one WWN card
assembly at a time while the power is on. To replace both cards, follow all steps for one card, and then repeat the same
steps to replace the other card assembly.
1. Save settings and system data and order replacement WWN card(s) by following all steps under
2. Replace a card by following all steps under
. Repeat these steps to replace the second WWN
card if necessary.
3. Verify WWN card operation using the steps under
.
Replacing WWN Cards (Cold-Swap)
Use this procedure to replace WWN cards with system power off. You can use this procedure to replace one or both
WWN cards.
1. Save settings and system data and order the replacement WWN card by following all steps under
2. Replace the card by following all steps under
3. Verify WWN card operation using the steps under
.
Time and Items Required
If there is a need to replace one or both WWN cards, allow approximately 20 minutes. See
The following items are needed to replace the WWN cards:
•
Electrostatic discharge (ESD) grounding strap
•
No. 1 Phillips screwdriver
•
Workstation computer
Using the wwnrecover Utility
The
wwnrecover
utility permits a recovery of WWN card data in the event of corruption. Recovery is not possible if
hardware issues prevent access to either WWN card or if the primary and backup copy of the license ID on either card is
corrupted.
Identical data must be maintained on each WWN card at all times so that if one card fails, the system can use the other
card to provide valid system operation. To maintain data and ensure its integrity, the system audits both WWN cards one
hour after the first system boot-up, every 24 hours after boot-up, and any time a WWN card is inserted to compare the
critical data.
53-1004106-15
141