53-1004106-15 Installation Guide
Brocade
®
X6-4 Director Hardware Installation Guide
Slot 1 (CP0, active): Firmwaredownload command has completed successfully. Use firmwareshow to verify the
firmware versions.
7. Ensure that you are still logged on to the standby CP blade (the blade for which you just changed the firmware level)
and type
reboot
. The reboot of the standby CP will initiate a
firmwarecommit
to the secondary partition and log
you out.
Chassis_1: admin> reboot
Broadcast message from root (ttyS0) Fri Jun 17 14:49:45 2016...
The system is going down for reboot NOW !!
INIT: Switching to runlevel: 6
INIT: Sending processes the TERM signal Chassis_1:admin> HAMu Heartbeat down, stop FSS
Unmounting all ##exiting due to signal: 9, pending signals: 0x20000, 0x0
ilesystems.
Please stand by while rebooting the system...
Restarting system.
The system is coming up, please wait...
.
.
.
Fri Jun 17 14:53:13 2016: Doing firmwarecommit now.
Please wait ...
Fri Jun 17 14:55:27 2016: Firmware commit completes successfully.
Validating the filesystem ...
Fri Jun 17 22:36:05 2016: Doing firmwarecommit now.
Please wait ...
Fri Jun 17 22:36:48 2016: Firmware commit completes successfully.
2016/06/17-14:56:50, [SULB-1004], 908, SLOT 2 | CHASSIS, INFO, Switch, Firmwarecommit has completed.
2010/06/17-14:56:50, [SULB-1036], 909, SLOT 2 | CHASSIS, INFO, Switch, The new Version: Fabric OS
[version]
2010/06/17-14:56:50, [SULB-1002], 910, SLOT 2 | CHASSIS, INFO, Switch, Firmwaredownload command has
completed successfully.
NOTE
The time stamp on the co-CPU may not be in sync with the main CPU on the blade. This is not a cause for
concern.
8. Log back on to the standby CP blade and enter
firmwareDownloadStatus
on the standby CP blade to validate a
successful commit. This may take 10 minutes.
9. If you are upgrading through several levels of the Fabric OS, repeat Step 5 through Step 8 as often as necessary
based on the path outlined in the preceding table. Otherwise, proceed to Step 10.
10. Log out of the standby CP blade and log on to the active CP blade.
11. Proceed to the procedures for "Completing the replacement."
Replacing a CP Blade: Cold-Swap Procedure
Use this procedure to replace both CP blades while the device power is off. You must power off the device to replace both
CP blades.
To replace a single CP blade while the device power is on, see
Replacing a CP Blade: Hot-Swap Procedure
.
53-1004106-15
133