53-1004106-15 Installation Guide
Brocade
®
X6-4 Director Hardware Installation Guide
HA enabled, Heartbeat Up, HA State synchronized
4. Enter all remaining commands from the serial console for the active CP blade, unless otherwise indicated. For more
information about commands, refer to the
Brocade Fabric OS Command Reference Manual
.
5. If the active CP blade is faulty, automatic failover to the standby CP blade should have occurred. Perform the following
steps:
a) Confirm that the standby CP blade is active using the
haShow
command.
b) Power off the faulty CP blade by loosening the captive screws on both ejector handles on the blade using a No. 1
Phillips screwdriver. This disconnects power from the blade. The spring-loaded captive screws will pop out from the
slot .63 cm (.25 in.) when fully disengaged.
c) Log on to the now active CP blade.
d) Skip to Step 8.
If automatic failover has not occurred, manually fail over the faulty blade by loosening the captive screws on both
ejector handles. As the screws loosen, the blade fails over and the amber status LED will illuminate. Log on to the
standby CP blade, and skip to Step 8.
6. If both CP blades are healthy and you want to replace the standby CP blade, log on to the active CP blade and skip to
Step 8.
7. If both CP blades are healthy and you want to replace the active CP blade, log on to the active CP blade and run the
following steps:
a) Run the
haFailover
command to make the standby CP blade the active blade. The currently active CP blade
becomes the standby blade. Wait until the status LED on the currently active CP blade is no longer illuminated.
b) Confirm the completion of the failover by running the
haShow
command.
c) Log on to the new active CP blade.
8. Run
firmwareShow
to note the firmware version of the active CP blade.
The
firmwareshow
command will display a warning message if the firmware versions on the two CP blades are not
the same.
WARNING: The local CP and remote CP have different versions
of firmware, please retry firmwaredownload command.
Chassis_1:admin>
9. Run
haDisable
from the active CP blade to prevent failover or communication between the CP blades during the
replacement.
Replacing a Control Processor Blade
Use the following procedures in this section to replace CP blades:
•
Hot-swap procedure. Use this procedure to replace a single CP blade or both CP blades, one at a time, while the
device power is on. The device continues to operate while replacing a blade if the redundant blade is active and
failover does not occur.
•
Cold-swap procedure. Use this procedure to replace CP blades after removing power to the device.
Replacing a CP Blade: Hot-Swap Procedure
Use this procedure to replace CP blades, one at a time, while the device power is on. The device continues to operate
while replacing a blade if the redundant blade is active and failover does not occur. You can prevent failover by entering
the
haDisable
command.
To replace both CP blades with power off, see
53-1004106-15
127