Site Sentinel™ 4 Installation and Operation Manual

INSTALLATION

Installation

Silence Sensor Inputs

Connect your unbalanced monaural or stereo audio source to the terminals labeled
SSLT, SSRT and AGND.  The level should be between -10 and +24 dbu.  The input
impedance is approximately 22K ohms.  When the SSLT/RT input has audio applied
and the silence sensor is activated, the front panel SS led is illuminated.  If the SS led
is out, the signal is too low and if it’s flashing, it is in an alarm condition (if enabled).  

TEMPerature Probe Input 

Insert the OPTIONAL temperature probe (25 foot cable) mini (3.5mm) plug in to the
rear panel jack labeled “TEMP” -67°F to +257°F (-55°C TO +125°C).  

NOTE: Please limit the total length of cable to 50 feet.  Please contact the factory
for the proper extension cable.  The temperature probe should only be installed or
removed with the power supply disconnected from the Site Sentinel™ 4.

Power Controller Relay

The jumpers are set to provide the relay common (wiper) on the terminal labeled
(PCJP).  Please refer to the “Fractional Schematic” in the appendix for more jumper
options. 

NETWORK connector

Connect one end of the supplied CAT5 (straight or x-over) cable to the desired ETH-
ERNET (WAN/LAN) port. 

PWR 7.5 VDC (Power) connector

Connect the supplied 7.5 volt DC only 1 amp power supply cord in to the  Site
Sentinel™ 4’s power jack (center positive) labeled “PWR 7.5 VDC”, then plug the
transformer in to a source of 120 vac 60Hz.  Verify that the front panel green
(PWR/HB) power led is illuminated.

Web Setup and Operation

Ethernet “Quick Start” guide

CAUTION!  If you are not familiar with Ethernet enabled equipment, it may
be useful to contact your IT department, network administrator or network
consultant for assistance.  Assigning an IP address already in use by another
device may cause problems with your network!

Instructions for changing the IP address of the computer that will be used for the
configuration of this product are given here. Note that these instructions are specif-
ically for computers with the Windows XP operating system. For setup using other
operating systems, refer to the appropriate OS user’s manual.

CAUTION!

NEVER DOWNLOAD
FIRMWARE UPDATES
OR CHANGES TO
THE XPORT WEB-
SERVER UNLESS
INSTRUCTED TO DO
SO BY BROADCAST
TOOLS®.  DOING SO
DELETES ALL SOFT-
WARE AND VOIDS
ALL WARRANTIES
FROM BROADCAST
TOOLS®, INC.

WEBSITE:

Visit our web site for
product updates and
additional information.

Содержание Site Sentinel 4

Страница 1: ...Copyright 1989 2018 by Broadcast Tools Inc All rights reserved No part of this document may be reproduced or distributed without permission Visit www broadcasttools com for important product update i...

Страница 2: ...DC POWER connector 10 Web Setup Operation 11 Ethernet Quick Start Guide 12 Opening the LOGIN Web Page 13 Login Web Page 14 Monitor Control Web Page 15 User Setup Web Page 16 Temperature Setup page 17...

Страница 3: ...fail without warning Do not use this product in applications where a life threatening condition could result due to failure Serious injury or death can occur if a command channel is activated while yo...

Страница 4: ...ment If you would like more information about Broadcast Tools products you may reach us at Broadcast Tools Inc 131 State Street Sedro Woolley WA 98284 1540 USA Voice 360 854 9559 Fax 866 783 1742 Inte...

Страница 5: ...ion 10 volt meter ing analog channels while each of the four optically isolated status logic channels may be configured for 5 to 24 volts DC wet or dry contact closures status logic monitoring The fou...

Страница 6: ...nd that you connect your Site Sentinel 4 to a UPS system While all operating and user parameters are stored in non volatile EEPROM brownout con ditions and lightning induced spikes can disable or dama...

Страница 7: ...anel connections Name Type Description PF 2 1mm Jack Power Failure power jack optically isolated 5 12 VDC power supply optional MTR 1 4 Connector Metering analog inputs one thru four Top MGND Connecto...

Страница 8: ...Metering analog input samples may be elevated several hundred volts above ground on some external equipment Permanent damage may occur to the Site Sentinel 4 and or external equipment if a high voltag...

Страница 9: ...era tion The factory default is DRY Switch relay contact open collector with jumpers between 1 2 and 3 4 In the DRY configuration the A terminal is ground while the B terminal is the cathode of the op...

Страница 10: ...for more jumper options NETWORK connector Connect one end of the supplied CAT5 straight or x over cable to the desired ETH ERNET WAN LAN port PWR 7 5 VDC Power connector Connect the supplied 7 5 volt...

Страница 11: ...ernet Quick Start guide Step 1 Open the control panel by clicking on the start menu click on settings then click on Control Panel Note that the control panel shown is in Classic View If con trol panel...

Страница 12: ...ep 4 On the Local Area Connection Properties page double click on Internet Protocol TCP IP to display properties Step 5 Before making any changes to the network settings write down the cur rent settin...

Страница 13: ...r supply to the product s power jack labeled PWR 7 5 VDC Verify that the green PWR HB LED is ON and the left LINK LED above the NET Network RJ 45 connector is illuminated Ethernet NETWORK port LED ind...

Страница 14: ...in screen displays the Username and Password entry points You may view the password by checking the Show Password box After you have successfully logged in the Monitor Control page will be displayed D...

Страница 15: ...I O setup page Status Displays the condition of the four status logic inputs Relays Allows the user with admin or monitor control access to control each relay for its displayed function Silence Sensor...

Страница 16: ...pages if authorized make your selection under the left hand Navigation column Eight Usernames and Passwords may be configured for up to three access levels 1 Admin allows complete product configuratio...

Страница 17: ...tempera ture or metering inputs to configure Temperature Label Used to identify the temperature probe Alarms High This option enables the High Temp email alarms Email Addresses The High boxes labeled...

Страница 18: ...is deadband This option specifies the hysteresis used when evaluating alarm conditions Hysteresis prevents alarms from toggling excessively when temperature is at the set point This is due to normal f...

Страница 19: ...to configure Metering input selection Select the metering inputs one thru four for configuration Meter Label Used to identify the metering input source Metering Units Label in engineering units such a...

Страница 20: ...allows the user to enable up to four different email addresses for low alarms Alarms Exit This option enables the emailing after exiting an alarm Log Device This enables the email logging of each met...

Страница 21: ...he user to select the I O setup configura tion pages Status input selection Select the status inputs one thru four for configu ration Input Status Messages Used to identify the status input source for...

Страница 22: ...s applied to the input WET or no closure when configured for DRY it s considered OFF when voltage IS applied WET or completed closure set to DRY to the input it considered ON NOTE When the Normal sign...

Страница 23: ...pages Relay label Used to identify the device Action State Determines how each relay will function The relays may be configured for one of three states 1 Independent ON and OFF operation 2 Pulse with...

Страница 24: ...are out of tolerance Enable Enables the selected input to monitor for each relay Action When meter status silence sensor power failure or temperature input number is in condition delay xx seconds then...

Страница 25: ...ates 1 Pulse with user configured pulse length from 0 to 9999 ms 2 Toggle ON OFF one button operation 3 Reboot One button operation Alarms OFF This option enables email alarms with an ON relay Email A...

Страница 26: ...when the silence sensor exits an alarm condition along with up to four email alarms Email Addresses The EXIT boxes labeled 1 2 3 4 allows the user to enable up to four different email addresses for EX...

Страница 27: ...long with up to four email alarms Email Addresses The ENTER boxes labeled 1 2 3 4 allows the user to enable up to four different email addresses for ENTER alarms Alarms Exit When checked generates an...

Страница 28: ...wer failure input changes state before an alarm is activated Alarm LED User defined color of LED on the Monitor and Control page when in an alarm condition NOTE After any item has been changed you MUS...

Страница 29: ...rk left to right when configuring a schedule event To select a cell just click in the cell box and it will transform the background will be yellow and you should have either drop down boxes or checkbo...

Страница 30: ...uler Select Pulse or Toggle from the Event drop down box on the Scheduler Setup Page to configure this item Then from the Device drop down box select the relay you wish to con trol The Pulse duration...

Страница 31: ...t dates or day months To select the Date for an Exact Date type choose the month and day from the two drop down boxes under Date To select the date for a Day Months type choose the months and days of...

Страница 32: ...com voice 360 854 9559 fax 866 783 1742 32 Site Sentinel 4 Installation and Operation Manual WEB SETUP Web Setup and Operation Email Network Setup Web Page WEBSITE Visit our web site for product updat...

Страница 33: ...enter the following items before an email can be suc cessfully sent SMTP Server Address SMTP Port SMTP Return Address SMTP Host ID SMTP username and SMTP password must be supplied if authentication i...

Страница 34: ...e Traps is checked otherwise trap messages are sent based on the device and enabled alarms NTP Time Server Address Enter the NTP address here Default pool ntp org NTP Port Normally 123 Default 123 NTP...

Страница 35: ...must navigate your web browser to the new IP address Send Test Email Press this button to send a test email When the email has completed an alert box will pop up indicating the status of the email an...

Страница 36: ...ys if the alarm is entering or exiting an alarm condition Date Displays what date the alarm was logged Time Displays what time the alarm was logged NOTE With the admin access level the user may contro...

Страница 37: ...3 1742 37 Site Sentinel 4 Installation and Operation Manual WEB SETUP About Web Page The About Web Page displays the product name firmware version numbers and Broadcast Tools Web site link WEBSITE Vis...

Страница 38: ...internal 5 VDC source DRY Open collector contact clo sures to ground or external logic source Power Failure input Optically isolated 5 to 12 VDC 15 ma center positive 2 1mm x 5 5mm coax type Connecto...

Страница 39: ...NO OTHER WARRANTIES OR REMEDIES TO THE MAXIMUM EXTENT PERMITTED BYAPPLICABLE LAW BROADCAST TOOLSAND ITS SUPPLIERS DISCLAIMALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IM...

Страница 40: ...ions EN55022 1998 IEC CSPIR22 1993 Radiated RF emissions 30MHz 1000MHz Conducted RF Emissions Telecom Lines 150KHz 30MHz FCC Part 15 Subpart B Class B IEC 1000 3 2 A14 2000 IEC 1000 3 3 1994 Electroma...

Страница 41: ...9 2009 by Broadcast Tools Inc All Rights Reserved K1 METERING INPUTS STATUS INPUTS K2 K3 K4 CGnd Power 7 5VDC Unbalanced Stereo Silence Sensor Input 10dbu 24dbu Status Input Configuration Jumpers Powe...

Страница 42: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 42 Site Sentinel 4 Installation and Operation Manual APPENDIX B...

Страница 43: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 43 Site Sentinel 4 Installation and Operation Manual APPENDIX C Front and Rear Chassis...

Страница 44: ...tors K1 K2 K3 K4 Monitor Control CPU Factory Default JP Status 1 VCC JP VCC JP VCC JP Status 2 Status 3 Status 4 Plug in EuroBlock Connectors DRY Allows Contact Closures Switch or Open Collector WET A...

Страница 45: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Site Sentinel 4 Installation and Operation Manual 45 APPENDIX E...

Отзывы: