SM-III Plus Installation and Operation Manual

ADDENDUM

ADDENDUM

November 19, 2007   

Changes to the Broadcast Tools® SM-III with version 1.16 firmware.  Please check the label
on U4 for the correct firmware version.

Restore timing setup:

The SM III Plus restore time delay is set via SW 2, the first six positions of the dipswitch
and Jp-1.  The default for this jumper is installed.  This provides TWO second resolutions.
To provide longer time resolution, remove and stow Jp-1, which will provide 20 second res-
olution.  The switches are set at the factory for off.  Each switch has a digit value as shown
in the two tables below.  For the factory default setting.  Please note the table below refers
to the restore time delay in seconds.

Restore Delay

Two (2) Second Resolution Table

SW-2 Switch Position and Jp-1 installed.

1

2

3

4

5

6

7

8

Digit Value

1

2

4

8

16

32

Note Note
1

EXAMPLES:    

1 = 2 seconds

ON 

OFF

OFF

OFF

OFF

OFF

1 + 2 = 3 x 2 = 6 seconds

ON 

ON 

OFF

OFF

OFF

OFF

1 + 2 + 4 = 7 x 2 = 14 seconds

ON 

ON 

ON 

OFF

OFF

OFF

32 x 2 = 64 seconds, or 
1 minute and 4 seconds

OFF

OFF

OFF

OFF

OFF

ON 

Restore is turned OFF.

OFF

OFF

OFF

OFF

OFF

OFF

Restore Delay

Twenty (20) Second Resolution Table

SW-2 Switch Position and Jp-1 removed.

1

2

3

4

5

6

7

8

Digit Value

1

2

4

8

16

32

Note  Note
1

EXAMPLES:    

1 = 20 seconds

ON 

OFF  OFF  OFF  OFF  OFF 

1 + 2 = 3 x 20 = 60 seconds or
1 minute 

ON 

ON 

OFF OFF

OFF

OFF

1 + 2 + 4 = 7 x 20 = 140 seconds 

ON 

ON 

ON 

OFF

OFF

OFF

or 2 minutes and 20 seconds
32 x 20 = 640 seconds or 10 

OFF  OFF  OFF  OFF  OFF  ON 

minutes and 40 seconds.
Restore is turned OFF.

OFF  OFF  OFF  OFF  OFF  OFF 

ADDENDUM

November 19, 2007   

Changes to the Broadcast Tools® SM-III with version 1.16 firmware.  Please check the label
on U4 for the correct firmware version.

Restore timing setup:

The SM III Plus restore time delay is set via SW 2, the first six positions of the dipswitch
and Jp-1.  The default for this jumper is installed.  This provides TWO second resolutions.
To provide longer time resolution, remove and stow Jp-1, which will provide 20 second res-
olution.  The switches are set at the factory for off.  Each switch has a digit value as shown
in the two tables below.  For the factory default setting.  Please note the table below refers
to the restore time delay in seconds.

Restore Delay

Two (2) Second Resolution Table

SW-2 Switch Position and Jp-1 installed.

1

2

3

4

5

6

7

8

Digit Value

1

2

4

8

16

32

Note Note
1

EXAMPLES:    

1 = 2 seconds

ON 

OFF

OFF

OFF

OFF

OFF

1 + 2 = 3 x 2 = 6 seconds

ON 

ON 

OFF

OFF

OFF

OFF

1 + 2 + 4 = 7 x 2 = 14 seconds

ON 

ON 

ON 

OFF

OFF

OFF

32 x 2 = 64 seconds, or 
1 minute and 4 seconds

OFF

OFF

OFF

OFF

OFF

ON 

Restore is turned OFF.

OFF

OFF

OFF

OFF

OFF

OFF

Restore Delay

Twenty (20) Second Resolution Table

SW-2 Switch Position and Jp-1 removed.

1

2

3

4

5

6

7

8

Digit Value

1

2

4

8

16

32

Note  Note
1

EXAMPLES:    

1 = 20 seconds

ON 

OFF

OFF

OFF

OFF

OFF

1 + 2 = 3 x 20 = 60 seconds or
1 minute 

ON 

ON 

OFF

OFF

OFF

OFF

1 + 2 + 4 = 7 x 20 = 140 seconds 

ON 

ON 

ON 

OFF

OFF

OFF

or 2 minutes and 20 seconds
32 x 20 = 640 seconds or 10 

OFF

OFF

OFF

OFF

OFF

ON 

minutes and 40 seconds.
Restore is turned OFF.

OFF

OFF

OFF

OFF

OFF

OFF

NOTE 1:

SW2-7 now has two inde-
pendent functions.  
When OFF, the SM-III
switches back to input one
from input two when the
alarm is cleared or the
audio returns.
When ON it allows the
SM-III to stay at input two
after the alarm is cleared
or the audio returns.

WEBSITE:

Visit our web site for
product updates and
additional information.

NOTE 2:

SW2-8 now has two inde-
pendent functions.  
When OFF, the SM-III is
armed at start-up.
When ON, the SM-III is
NOT armed at start-up.

Содержание Silence Monitor III Plus

Страница 1: ...editions may be issued to incorporate such changes Broadcast Tools is a registered trademark of Broadcast Tools Inc Copyright 1989 2011 by Broadcast Tools Inc All rights reserved No part of this docum...

Страница 2: ...ines 5 Inspection 5 Mounting 5 Connecting user equipment 5 Configured for backup switching 5 Remote control 6 Programming Guidelines 7 Mode setup 7 Sensitivity 7 Delay timing 7 Restore delay timing 8...

Страница 3: ...If you experience these problems please research your hardware software instruction manuals or contact the man ufacturers technical support department WHO TO CONTACT FOR HELP If you have any questions...

Страница 4: ...or optional RA 1 rack shelf for mounting up to three units in 1 RU PRODUCT FEATURES Transparent stereo or dual monaural program switcher with front panel switcher transfer switch and indicator LED Dip...

Страница 5: ...ole Automation etc to LT and LT for the left channel and RT and RT for the right channel This is the nor mally closed contact of the relay switcher and the input to the SM III Connect the source BACK...

Страница 6: ...low the selected function Note ALL inputs are 5 volt TTL CMOS compatible and active low pull to ground to activate It is recommended that all cables connected to the SM III Plus be looped through ferr...

Страница 7: ...per is installed This provides TWO second resolutions To pro vide longer time resolution remove and stow Jp 1 which will provide 20 second resolution The switches are set at the factory for a 6 second...

Страница 8: ...e default for this jumper is installed This provides TWO second resolutions To provide longer time resolution remove and stow Jp 1 which will provide 20 second resolution The switches are set at the f...

Страница 9: ...et at the factory for off Each switch has a digit value as shown in the two tables below For the factory default setting Please note the table below refers to the restore time delay in seconds NOTE 1...

Страница 10: ...ity setup on either or both channels after the delay time has expired See delay dipswitch SW1 will cause the following action 1 The front panel left and right audio LED s will extinguish 2 Unit switch...

Страница 11: ...main source to the backup source of each independent mon aural channel 2 Turn on the failed audio alarm LED 1 or 2 and each relay 3 Turn on the Tripped led and relay 4 Pulse the pulse 1 open collecto...

Страница 12: ...gold overlay contacts 1 amp 30 vdc 2 x DPDT for program switcher NOTE For safety do NOT connect 120 Vac circuits to these Relays Open collectors 15 vdc 100ma each Silence delay 2 seconds to 85 minutes...

Страница 13: ...OTHER WARRANTIES OR REMEDIES TO THE MAXIMUM EXTENT PERMITTED BYAPPLICABLE LAW BROADCAST TOOLSAND ITS SUPPLIERS DISCLAIMALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPL...

Страница 14: ...h version 1 16 firmware Please check the label on U4 for the correct firmware version Restore timing setup The SM III Plus restore time delay is set via SW 2 the first six positions of the dipswitch a...

Страница 15: ...lence Sensor Delay Selection Switches Timing Operation Selection Jumpers Silence Sensor Audio Restoration Function Selection Switches Input 1 Input 2 Switcher Output 131 State Street Sedro Woolley WA...

Страница 16: ...ernal Power Supply PS 15VDC 15VDC 5VDC Time Delay Restore and Mode XFER Remote XFer Mute Remote Mute Auto Remote Auto Reset Remote Reset Sonalert Left Valid Audio Right Left AudioAlarm Right Ext Alarm...

Отзывы: