background image

IF THE CO ALARM SOUNDS

Actuation of this device indicates the presence of carbon monoxide

(CO) which can kill you. If the CO Alarm sounds 4 beeps:

1. Immediately move to fresh air — outdoors or by an open door or 

window. Check that all persons are accounted for. Do not re-enter the 

premises or move away from the open door/window until the 

emergency services responders have arrived, the premises have

been 

aired out, and your alarm remains in its normal condition.

2. Call your local emergency services, fire department, or 911.

_____________________________________________

1

2

3

INTRODUCTION

Thank you for choosing BRK Brands, Inc. for your Smoke and Carbon

Monoxide Alarm needs. You have purchased a state-of-the-art Smoke &

CO Alarm designed to provide you with early warning of a fire or Carbon

Monoxide. 

Key features include:

Smoke & Carbon Monoxide Combination Alarm.

One alarm protects

against two deadly household threats.

Most Accurate Carbon Monoxide Sensor* 

Advanced electrochemical

CO sensor technology.

Intelligent Sensing Technology

designed to help reduce unwanted or

nuisance alarms.

Smart Interconnect

can be interconnected to BRK Smoke Alarms. 

One interconnect wire carries both smoke and CO alarm signals.

Single Button Test/Silence

eliminates confusion. Depending on what

mode the alarm is in, pushing the button provides different functions

such as testing the alarm, silencing the alarm, re-testing the alarm when

in silence and clearing the Latching feature.

Two Silence Features. 

Temporarily silence low battery chirp for up to

eight hours before replacing low battery or silence an unwanted alarm

for several minutes.

Two Latching Features.

Alarm Latch: Easily identifies initiating alarm

even after alarm condition has subsided. Low Battery Latch: Identifies

which unit is in low battery condition.

Perfect Mount System

includes a gasketless base for easy installation

and a new mounting bracket that keeps the alarm secure over a wide

rotation range to allow for perfect alignment.

End of Life Signal.

Provides audible and visual confirmation alarm

needs to be replaced.

*

As compared to other sensing technologies

© 2015 BRK Brands, Inc.  All rights reserved.  Distributed by 

BRK Brands, Inc., 3901 Liberty Street Road, Aurora, IL 60504-8122 U.S.A.

Consumer Affairs: (800) 323-9005 

www.brkelectronics.com   •   www.firstalert.ca

FIRE SAFETY TIPS

Follow safety rules and prevent hazardous situations: 1) Use smoking

materials properly. Never smoke in bed. 2) Keep matches or lighters

away from children; 3) Store flammable materials in proper containers; 

4) Keep electrical appliances in good condition and don’t overload electri-

cal circuits; 5) Keep stoves, barbecue grills, fireplaces and chimneys

grease- and debris-free; 6) Never leave anything cooking on the stove

unattended; 7) Keep portable heaters and open flames, like candles,

away from flammable materials; 8) Don’t let rubbish accumulate.

Keep alarms clean, and test them weekly. Replace alarms immediately 

if they are not working properly. Smoke Alarms that do not work cannot

alert you to a fire. Keep at least one working fire extinguisher on every

floor, and an additional one in the kitchen. Have fire escape ladders or

other reliable means of escape from an upper floor in case stairs are

blocked.

BASIC SAFETY INFORMATION

•   Dangers, Warnings, and Cautions alert you to important 

operating instructions or to potentially hazardous situations. 

Pay special attention to these items.

      •   This Smoke/CO Alarm is approved for use in single-family

residences. It is NOT designed for marine or RV use.

•   This combination Smoke/Carbon Monoxide Alarm has two sep-

arate alarms. The CO Alarm is not designed to detect fire 

or any other gas. It will only indicate the presence of carbon

monoxide gas at the sensor. Carbon monoxide gas may be

present in other areas. The Smoke Alarm will only indicate the

presence of smoke that reaches the sensor. The Smoke Alarm

is not designed to sense gas, heat or flames.

All BRK

®

and First Alert

®

Smoke Alarms conform to regulatory

requirements, including ULC S531 and are designed to detect 

particles of combustion. Smoke particles of varying number and 

size are produced in all fires.

Ionization technology is generally more sensitive than photelectric

technology at detecting small particles, which tend to be pro-

duced in greater amounts by flaming fires, which consume com-

bustible materials rapidly and spread quickly. Sources of these fires

may include paper burning in a wastebasket, or a grease fire in the

kitchen.

Photoelectric technology is generally more sensitive than ionization

technology at detecting large particles, which tend to be produced

in greater amounts by smoldering fires, which may smolder for

hours before bursting into flame. Sources of these fires may include 

cigarettes burning in couches or bedding.

For maximum protection, use both types of Smoke Alarms on each

level and in every bedroom of your home.

4

5

6

INSTALLATION

WHERE TO INSTALL THIS ALARM

Minimum coverage for Smoke Alarms

, as recommended by the

National Fire Protection Association (NFPA), is one Smoke Alarm on

every floor, in every sleeping area, and in every bedroom (See

“Regulatory Information For Smoke Alarms” for details on the NFPA 

recommendations).

For CO Alarms,

the National Fire Protection Association (NFPA) 

recommends that a CO Alarm should be centrally located outside of

each separate sleeping area in the immediate vicinity of the bedrooms.

For added protection, install additional CO Alarms in each separate 

bedroom, and on every level of your home.

In general, install combination Smoke and Carbon Monoxide

Alarms:

•     On every level of your home, including finished attics and basements.

•     Inside every bedroom, especially if people sleep with the door partly

or completely closed.

•     In the hall near every sleeping area. If your home has multiple 

sleeping areas, install a unit in each. If a hall is more than 12 meters

(40 feet) long, install a unit at each end.

•     At the top of first-to-second floor stairs.

•     At the bottom of the basement stairs.

•     For additional coverage, install Alarms in all rooms, halls, and storage

areas, where temperatures normally remain between 4.4 C and

37.8

o

C (40

o

F and 100

o

F).

Recommended Placement

•     When installing on the wall, the top edge of Smoke Alarms should

be placed between 102 mm (4 inches) and 305 mm (12 inches)

from the wall/ceiling line.

•     When installing on the ceiling, place the alarm as close to the 

center as possible.

•     In either case, install at least 102 mm (4 inches) from where the 

wall and ceiling meet. See “Avoiding Dead Air Spaces” for more

information.

NOTE:

For any location, make sure no door or other obstruction could

keep carbon monoxide or smoke from reaching the Alarm.

Installing Smoke/CO Alarms in Mobile Homes

For minimum security install one Smoke/CO Alarm as close to each

sleeping area as possible. For more security, put one unit in each room.

Many older mobile homes (especially those built before 1978) have little

or no insulation. If your mobile home is not well insulated, or if you are

unsure of the amount of insulation, it is important to install units on

inside walls only.

This equipment should be installed in accordance with CAN/ULC S553 or

NFPA (National Fire Protection Association) 72 and 101. National Fire

Protection Association, One Batterymarch Park, Quincy, MA 02269-9101

U.S.A.  Additional local building and regulatory codes may apply in your

area. Always check compliance requirements before beginning any instal-

lation.

WHERE THIS ALARM SHOULD NOT BE INSTALLED

Do NOT locate this Smoke/CO Alarm:

•     In garages, kitchens, furnace rooms, crawl spaces and unfinished

attics. Avoid extremely dusty, dirty or greasy areas.

•     Where combustion particles are produced. Combustion particles

form when something burns. Areas to avoid include poorly ventilated

kitchens, garages, and furnace rooms. Keep units at least 6 meters

(20 feet) from the sources of combustion particles (stove, furnace,

water heater, space heater) if possible. In areas where a 6 meter

(20-foot) distance is not possible – in modular, mobile, or smaller

homes, for example – it is recommended the Smoke/CO Alarm be

placed as far from these fuel-burning sources as possible. The

placement recommendations are intended to keep these Alarms at 

a reasonable distance from a fuel-burning source, and thus reduce

“unwanted” alarms. Unwanted alarms can occur if a Smoke/CO

Alarm is placed directly next to a fuel-burning source. Ventilate 

these areas as much as possible.

•     Within 1.5 meters (5 feet) of any cooking appliance. In air streams

near kitchens. Air currents can draw cooking smoke into the smoke

sensor and cause unwanted alarms. 

•     In extremely humid areas. This Alarm should be at least 3 meters

(10 feet) from a shower, sauna, humidifier, vaporizer, dishwasher,

laundry room, utility room, or other source of high humidity.

•     In direct sunlight.
•     In turbulent air, like near ceiling fans or open windows. Blowing air

may prevent CO or smoke from reaching the sensors.

•     In areas where temperature is colder than 4.4

o

C (40

o

F) or hotter

than 37.8

o

C (100

o

F). These areas include non-airconditioned crawl

spaces, unfinished attics, uninsulated or poorly insulated ceilings,

porches, and garages.

•     In insect infested areas. Insects can clog the openings to the 

sensing chamber.

•     Less than 305 mm (12 inches) away from fluorescent lights. 

Electrical “noise” can interfere with the sensor.

•     In “dead air” spaces. See “Avoiding Dead Air Spaces”.

AVOIDING DEAD AIR SPACES

“Dead air” spaces may prevent smoke from reaching the Smoke/CO

Alarm. To avoid dead air spaces, follow installation recommendations

below.

On ceilings,

install Smoke/CO Alarms as close to the center of the 

ceiling as possible. If this is not possible, install the Smoke/CO Alarm 

at least 102 mm (4 inches) from the wall or corner.

For wall mounting

(if allowed by building codes), the top edge of

Smoke/CO Alarms should be placed between 102 mm (4 inches) and 

305 mm (12 inches) from the wall/ceiling line.

On a peaked, gabled, or cathedral ceiling,

install the first Smoke/CO

Alarm within 0.9 meters (3 feet) of the peak of the ceiling, measured 

horizontally. Additional Smoke/CO Alarms may be required depending

on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for

details on requirements for sloped or peaked ceilings.

Continued...

BEFORE YOU BEGIN INSTALLATION

This unit is designed to be mounted on any standard wiring junction

box up to a 10 cm (4-inch) size, on either the ceiling or wall. Read

“Where to Install This Alarm” and “Where This Alarm Should Not Be

Installed ” before you begin installation.

      • Make sure the alarm is not receiving excessively noisy power.

Examples of noisy power could be major appliances on the

same circuit, power from a generator or solar power, light dim-

mer on the same circuit or mounted near fluorescent lighting.

Excessively noisy power may cause damage to your Alarm.

NOTE:

A qualified appliance technician is defined as “a person, firm, 

corporation, or company that either in person or through a representative,

is engaged in and responsible for the installation, testing, servicing, or

replacement of heating, ventilation, air conditioning (HVAC) equipment,

combustion appliances and equipment, and/or gas fireplaces or other

decorative combustion equipment.”

1    Mounting Bracket
2    Mounting Slot and Screw

*

3    Locking Pins (break out of

bracket)

4    Hot (Black) AC Wire
5    Neutral (White) AC Wire
6    Interconnect Wire (Orange)
7    Lever to Open Battery

Compartment

8    Swing-Out Battery

Compartment

9    Quick-Connect Power

      

*

Not Included

PARTS OF THIS SMOKE/CO ALARM

Tools you will need:

Standard Flathead screwdriver, wire strippers.

ELECTRICAL SHOCK HAZARD. Turn off power to the area where you

will install this unit at the circuit breaker or fuse box before beginning

installation. Failure to turn off the power before installation may

result in serious electrical shock, injury or death.
To install this unit:

1.   Remove the mounting bracket from the base. Position the screw 

slots on the mounting bracket over the screws in the junction box. 

Tighten the screws.

Improper wiring of the power connector or the wiring leading to the

power connector will cause damage to the Alarm and may lead to a

non-functioning Alarm.

2.   Using wire nuts, connect the power connector to the AC power.

3.   Plug the power connector into the back of the Smoke/CO Alarm.

4.   Position the base of the Smoke/CO Alarm over the mounting bracket

and turn. The Alarm will remain secure over a wide rotation range to

allow for perfect alignment. When wall mounting, this will allow fine-

tuning on the positioning to compensate for out of aligned wall studs

and to keep the wording level. The Alarm can be positioned over the

bracket every 120°. Rotate the Alarm until aligned properly.

5.   Check all connections.

STAND ALONE ALARM ONLY:

•     Connect the white wire on the power connector to the neutral

wire in the junction box.

•     Connect the black wire on the power connector to the hot wire

in the junction box.

•     Tuck the orange wire inside the junction box. 

It is used for 

interconnect only.

INTERCONNECTED ALARMS ONLY:

Strip off about 1/2” of the plastic coating on the orange 

interconnect wire on the power connector.

•     Connect the white wire on the power connector to the neutral

wire (usually white) in the junction box.

•     Connect the black wire on the power connector to the hot wire

(usually black) in the junction box.

•     Connect the orange wire on the power connector to the inter-

connect wire in the junction box. Repeat for each unit you are

interconnecting. Never connect the hot or neutral wires in the

junction box to the orange interconnect wire. Never cross hot

and neutral wires between interconnected Alarms.

SPECIAL REQUIREMENTS FOR INTERCONNECTED ALARMS

•   Failure to meet any of the above requirements could damage

the units and cause them to malfunction, removing your 

protection.

      •   AC and AC/DC Smoke/CO Alarms can be interconnected.

Under AC power, all units will alarm when one senses smoke

or CO. When power is interrupted, only the AC/DC units in

the series will continue to send and receive signals.  

AC powered Smoke/CO Alarms will not operate. See “Smart

Interconnect” Feature.

Interconnected units can provide earlier warning of a Smoke/CO 

problem than stand-alone units, especially if the problem starts in a

remote area of the dwelling. If any unit in the series senses Smoke/CO,

all units will alarm. To determine which Smoke/CO Alarm initiated an

alarm, refer to the table.

During an Alarm:

On Initiating Alarm(s)  –  Red LED(s) flashes (flash) rapidly
On All Other Alarms  –  Red LED is Off

After an Alarm (Latching):

On Initiating Alarm(s)  –  Red LED(s) On for 2 seconds/Off for 2 seconds
On All Other Alarms  –  Green LED(s) On, Red LED(s) is Off

Compatible Interconnected Units

Interconnect units within a single family residence only. Otherwise all

households will experience unwanted alarms when you test any unit 

in the series. Interconnected units will only work if they are wired to

compatible units and all requirements are met. This unit is designed 

to be compatible with: 

First Alert

®

BRK

®

Models

SC9120BA, SC9120A, CO5120BNA,

SA520CNA, SC7010BA; 

BRK

®

Auxiliary Device Model

RM4 (Relay

Module).

Interconnected units must meet ALL of the following requirements:

• A maximum of 18 compatible BRK Electronics

® 

Smoke, Heat or

CO Alarms may be interconnected. No more than 12 of the 18 can

be Smoke Alarms per NFPA 72.

• The same fuse or circuit breaker must power all interconnected

units.

• The total length of wire interconnecting the units should be 

less than 300 meters (1000 feet). This type of wire is commonly

available at Hardware and Electrical Supply stores.

• All wiring must conform to all local codes and the Canadian

Electrical Code, CSA 22.1.

6.   Make sure the Smoke/CO Alarm is receiving AC power. Under normal

operation, the green indicator light will shine continuously. If the green

power indicator light does not light, TURN OFF POWER TO THE

JUNCTION BOX and recheck all connections. If all connections are

correct and the green power indicator still does not light when you

restore the power, the unit should be replaced immediately.

7.   

ACTIVATING THE BATTERY BACK-UP

      

Activate the battery back-up by removing the “Pull to Activate

Battery Back-Up” tab. You do not need to open the battery 

compartment and reposition the battery during installation. 

DO NOT

remove the battery activation tab until AC power is turned on to

conserve battery power.

8.   

Single Station Alarms:

Test each Alarm. Press and hold the

Test/Silence button until you hear the acknowledge “chirp” or the

unit alarms. 

Interconnected Alarms:

Press and hold the Test/Silence button

until the unit alarms. All interconnected Alarms should sound. The

other Alarms sounding only tests the interconnect signal between

Alarms. It does not test each Alarm’s operation. 

You must test each

Alarm individually to check if the Alarm is functioning properly.

If any unit in the series does not alarm during testing, TURN OFF POWER,

REMOVE BATTERIES, and recheck connections. If it does not alarm

when you restore power, replace it immediately.

A. Unswitched 120VAC       

B. To Additional Alarms,

60 Hz source                   

Maximum = 18 Alarms

1. Smoke/CO Alarm

2. Ceiling or Wall

3. Power Connector

4. Wire Nut

5. Junction Box

6. Neutral Wire

(White)

7. Interconnect Wire

(Orange)

8. Hot Wire (Black)

STAND ALONE ALARM ONLY:

•     If you are only installing one unit, restore power to the junction box.

INTERCONNECTED ALARMS ONLY:

•     If you are interconnecting multiple Smoke/CO Alarms, repeat

Step 1-5 for each Smoke/CO Alarm in the series. When you are

finished, restore power to the junction box.

ELECTRICAL SHOCK HAZARD. Do not restore power until all 

Alarms are completely installed. Restoring power before installa-

tion is complete may result in serious electrical shock, injury or

death.

HOW TO INSTALL THIS SMOKE/CO ALARM

INSTALLATION, Continued

1.  Test/Silence Button: Press

and hold to activate test, 

or to silence the alarm.

2.  POWER Light (GREEN)/

SMOKE ALARM Light (RED)

3.  CO ALARM Light (RED)
4.  Battery Drawer
5.  (Behind the Cover) Alarm

Horn: 85dB audible alarm 

for test, alarm, and unit 

malfunction warning.

HOW YOUR SMOKE/CO ALARM WORKS

The optional locking features are designed to discourage unauthorized

removal of the battery or alarm. It is not necessary to activate the locks

in single-family households where unauthorized battery or alarm

removal is not a concern.

These Smoke/CO Alarms have two separate locking features: one locks

the battery compartment, and the other locks the Smoke/CO Alarm to the

mounting bracket. You can choose to use either feature independently, or

use them both.

Tools you will need:

• Needle-nose pliers or utility knife 

• Standard/Flathead screwdriver.

USING THE OPTIONAL LOCKING FEATURES

THE BATTERY COMPARTMENT LOCK

TO LOCK THE BATTERY COMPARTMENT:

Do not lock the battery compartment until you have activated the battery

and tested the battery back-up.
1.   Activate the battery back-up by removing

the “Pull to Activate Battery Back-Up” tab.

Push and hold the test button on 

the Smoke/CO Alarm’s cover until the

alarm sounds: continuous beeping; then

4 beeps, pause, 4 beeps.

If the unit does not alarm during

testing, DO NOT lock the battery

compartment! Install a new battery

and test again. If it still does not

alarm, replace the Smoke/CO

Alarm immediately.

2.   Using needle-nose pliers or a utility

knife, detach one locking pin from the

mounting bracket.

3.   Push the locking pin

through the black dot on

the label on the back of

the Smoke/CO Alarm.

THE MOUNTING BRACKET LOCK

TO ACTIVATE THE BRACKET LOCK:

1.   Using needle-nose pliers, detach one locking pin from the mounting

bracket.

2.   Insert the locking pin into the lock located on the base as shown in

the diagram.

3.   When you attach the Smoke/CO Alarm to the mounting bracket, the

locking pin’s head will fit into a notch on the bracket.

TO DEACTIVATE THE BRACKET LOCK:

ELECTRICAL SHOCK HAZARD. Turn off the power to the area

where the Smoke/CO Alarm is installed before removing it from the

mounting bracket. Failure to turn off the power first may result in

serious electrical shock, injury or death.

Always discharge the branch circuit before servicing an AC or

AC/DC Smoke/CO Alarm. First, turn off the AC power at the circuit

breaker or fuse box. Next, remove the battery from Smoke/CO

Alarms with battery back-up. Finally, press and hold the test button.

1.   Insert a flathead screwdriver between the mounting bracket pin and

the mounting bracket.

2.   Pry the Smoke/CO Alarm away from the bracket by turning both the

screwdriver and the Smoke/CO Alarm counterclockwise (left) 

at the same time.

TO PERMANENTLY REMOVE

THE BRACKET LOCK:

Insert the flathead screwdriver

between the locking pin and the

lock, and pry the pin out of the

lock.

TO UNLOCK THE BATTERY COMPARTMENT:

Once the Smoke/CO Alarm is installed, you must disconnect it from the AC

power before unlocking the battery compartment.

ELECTRICAL SHOCK HAZARD. Turn off the power to the area where 

the Smoke/CO Alarm is installed before removing it from the mounting

bracket. Failure to turn off the power first may result in serious electrical

shock, injury or death.

1.   Remove the Smoke/CO Alarm from the mounting bracket. If the unit is

locked to the bracket, see the section “To Deactivate the Locking

Feature.”

2.   Disconnect the power connector by gently prying it away from the back

of the Smoke/CO Alarm.

3.   Insert a flathead screwdriver under the head of the

locking pin, and gently pry it out of the battery 

compartment lock. (If you plan to relock the 

battery compartment, save the locking pin.) 

4.   To relock the battery compartment, close the

battery door and reinsert the locking pin in the

lock.

5.   Reconnect the power connector to the back of the Smoke/CO Alarm,

reattach the Smoke/CO Alarm to the mounting bracket, and restore the

power.

When replacing the battery, always test the Smoke/CO Alarm before 

relocking the battery compartment.

Mounting Bracket Lock

Battery Drawer Lock

Locking Pin

IF YOUR SMOKE/CO ALARM SOUNDS

WHAT TO DO IF SMOKE IS DETECTED

• If the unit alarms and you are not testing the unit, it is warning

you of a potentially dangerous situation that requires your

immediate attention. NEVER ignore any alarm. Ignoring the

alarm may result in injury or death.

      • Never disconnect the AC power to quiet an unwanted alarm.

Disconnecting the power disables the Alarm so it cannot

sense smoke. This will remove your protection. Instead, open

a window or fan the smoke away from the unit. The Alarm will

reset automatically.

      • If the unit alarms get everyone out of the house immediately.

• ELECTRICAL SHOCK HAZARD: Attempting to disconnect the

power connector from the unit when the power is on may result

in electrical shock, serious injury or death.

When an interconnected system of AC powered units is in alarm, 

the alarm indicator light on the unit(s) that initiated the alarm will blink

rapidly. It will remain OFF on any remaining units.

If the unit alarms, get everyone out of the dwelling immediately.

If the unit alarms and you are certain that the source of smoke is not a

fire—cooking smoke or an extremely dusty furnace, for example—open a

nearby window or door and fan the smoke away from the unit. Use the

Silence Feature to silence the Alarm. This will silence the alarm, and

once the smoke clears the unit will reset itself automatically.

WHAT TO DO IN CASE OF FIRE

•     Don’t panic; stay calm. Follow your family escape plan.

•     Get out of the house as quickly as possible. Don’t stop to get

dressed or collect anything.

•     Feel doors with the back of your hand before opening them. 

If a door is cool, open it slowly. Don’t open a hot door. Keep doors 

and windows closed, unless you must escape through them.

•     Cover your nose and mouth with a cloth (preferably damp). 

Take short, shallow breaths.

•     Meet at your planned meeting place outside your home, 

and do a head count to make sure everybody got out safely.

•     Call the Fire Department as soon as possible from outside. 

Give your address, then your name.

•     Never go back inside a burning building for any reason.

•     Contact your Fire Department for ideas on making your home safer.

Alarms have various limitations. See "General Limitations of

Smoke/CO Alarms" for details.

“SMART INTERCONNECT” FEATURE

This Alarm includes "Smart Interconnect" which enables the Alarm to be

interconnected with other BRK Smoke, Heat, and "Smart Interconnect"

CO Alarms. When smoke is detected, all Alarms will sound the smoke

horn pattern. When CO is detected, "Smart Interconnect" Alarms will

sound the CO horn pattern. Alarms that do not have the "Smart

Interconnect" Feature will remain silent during a CO alarm.

If you hear the alarm horn sound 3 beeps, pause, 3

beeps and the RED SMOKE light is flashing, smoke has

been detected. Evacuate everyone from the building.

Using the Optional Locking Features (Continued)

•     Connect this unit ONLY to other compatible units. See “How

To Install This Smoke/CO Alarm” for details. Do not connect 

it to any other type of alarm or auxiliary device. Connecting

anything else to this unit may damage it or prevent it from

operating properly.

•     The battery compartment resists closing unless a battery is

installed. This warns you the unit will not operate under DC

power without a battery.

•     Do not stand too close to the unit when the alarm is sounding.

It is loud to wake you in an emergency. Exposure to the horn

at close range may harm your hearing. 

•     Do not paint over the unit. Paint may clog the openings to the

sensing chambers and prevent the unit from operating proper-

ly.

Both locking features use locking pins, molded into the mounting bracket. Using needle nose pliers or a utility knife, remove one or both pins, depending on

which locking features you use.

WHAT YOU WILL SEE AND HEAR WITH THIS ALARM

Under Normal Operations

Horn:

Silent

Power/Smoke LED:

AC Power (LED Green); Battery Power (LED off)

CO LED:

Off

When You Test the Alarm

Horn:

continuous beeping

Power/Smoke LED:

Flashes Red in sync with the horn pattern

CO LED:

Off, followed by

Horn:

4 beeps, pause, 4 beeps

Power/Smoke LED:

AC Power (LED Green); Battery Power (LED off)

CO LED:

Flashes Red in sync with the horn pattern

If Battery Becomes Low or is Missing

Horn:

chirps once a minute

Power/ Smoke LED:

Low Battery latch is now engaged. (See

Latching Features note below.) Green LED On for 2 

seconds/Off for two seconds.

CO LED:

Off

If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)

Horn:

3 chirps every minute

Power/Smoke LED:

Green LED 3 Flashes approx. once a minute

CO LED:

Off

Alarm has reached its End of Life

Horn:

5 chirps every minute

Power/Smoke LED:

Green LED 5 Flashes approx. once a minute

CO LED:

Off

Alarm Levels of CO are Detected

Horn:

4 beeps, pause, 4 beeps

Power/Smoke LED:

AC Power (LED Green); Battery Power (LED off)

CO LED:

During Alarm: Flashes Red in sync with the horn pattern.

After Alarm: Flashes Red On for 2 seconds/Off for 2 seconds.

CO Alarm Latch is now engaged. (See LATCHING FEATURES

section for details).

Smoke is Detected

Horn:

3 beeps, pause, 3 beeps

Power/Smoke LED:

During Alarm: Flashes Red in sync with the horn

pattern. After Alarm: Flashes Red On for 2 seconds/Off for 2

seconds. Smoke Alarm Latch is now engaged. (See LATCH-

ING FEATURES section for details).

CO LED:

Off

Smoke Alarm is Silenced

Horn:

Off

Power/Smoke LED:

Flashes Red

CO LED:

Off

CO Alarm is Silenced

Horn:

Off

Power/Smoke LED:

AC Power (LED Green); Battery Power (LED

off)

CO LED:

Flashes Red

Latching Features Note: Without AC Power and running on battery

only, Low Battery Latch or Alarm Latch are only engaged for about

15 minutes to conserve power. Low Battery Latch and Alarm Latch

do not operate with a missing battery and no AC Power.

USING THE SILENCE FEATURES

Never remove the batteries to quiet an unwanted alarm. Removing

the batteries disables the alarm and removes your protection.

The Silence Feature is intended to temporarily silence the horn while

you identify and correct the problem. Do not use the Silence Feature in

emergency situations. It will not correct a CO problem or extinguish a

fire.

The Silence Feature can temporarily quiet an unwanted alarm for several

minutes. You can silence this Smoke/CO Alarm by pressing the Test/ 

Silence button on the alarm cover until you hear an acknowledge chirp.

After the Test/Silence button is released, the Red LED blinks during the

silence mode.

SILENCING THE LOW BATTERY WARNING

This Silence Feature can temporarily quiet the low battery warning

“chirp” for up to 8 hours if AC power is present. Press the Test/Silence

button on the Alarm cover until you hear the acknowledge “chirp”.

Once the low battery warning “chirp” silence feature is activated, the unit

continues to flash the green light once a minute for 8 hours. After 

8 hours, the low battery “chirp” will resume. The Alarm will continue to

operate as long as AC power is supplied. Note, if battery is missing or

dead, Low Battery Silence cannot be activated and alarm with continue

to chirp approximately once per minute. However, 

replace the batteries

as soon as possible,

to maintain protection in event of a power outage.

To deactivate this feature: 

Press the Test/Silence button again. 

The unit will go into Test Mode and the low battery warning will resume

(LED flashes and unit sounds “chirp” once a minute).

To silence Alarms in an interconnected series:

To silence an interconnected series of Smoke/CO Alarms, you must

press the Test/Silence button on the initiating alarm (The unit with the

flashing red light; the red light will be off on all other Alarms.). If you

press the Test/Silence on any other Alarm, it will only silence that unit,

not the whole interconnected series.

When the Smoke Alarm is

Silenced

When the CO Alarm is 

Silenced

The Smoke Alarm will remain

silent for up to 10 minutes, then

return to normal operation.
If the smoke has not cleared–or

continues to increase–the device

will go back into alarm.

The CO alarm will remain silent

for up to 4 minutes.
After 4 minutes, if CO levels

remain potentially dangerous the

horn will start sounding again.

SILENCING THE END OF LIFE SIGNAL

This silence feature can temporarily quiet the End of Life warning “chirp”

for up to 2 days. You can silence the End of Life warning “chirp” by

pressing the Test/Silence button. The horn will chirp, acknowledging that

the End of Life silence feature has been activated.

After approximately 2 days, the End of Life “chirp” will resume. After

approximately 2-3 weeks the End of Life warning cannot be silenced.

USER’S MANUAL

Smoke & Carbon

Monoxide Alarm

AC Powered Smoke &

Carbon Monoxide Alarm

with Battery Back-up,

Silence Feature and

Latching Alarm

Model SC9120BA &

SC9120A

Input: 120V AC 

~

, 60Hz, 0.09A

IMPORTANT! PLEASE READ CAREFULLY AND SAVE.

This user’s manual contains important information about your Alarm’s

operation. If you are installing the Alarm for use by others, you must

leave this manual—or a copy of it—with the end user.
M08-0121-014   K1   10/15   Printed in Mexico

LISTED to 

CSA 6.19-01

and 

ULC S531

STANDARDS

ELECTRICAL SHOCK HAZARD. Turn off the power to the area

where the Smoke/CO Alarm is installed before removing it from

the mounting bracket. Failure to turn off the power first may

result in serious electrical shock, injury or death.

•     This unit will not alert hearing impaired residents. It is 

recommended that you install special units which use

devices like flashing strobe lights to alert hearing impaired

residents.

•     Installation of this unit must conform to the electrical codes 

in your area; CSA 22.1 Canadian Electrical Code or NFPA 70,

and any other local or building codes that may apply. Wiring

and installation must be performed by a licensed electrician.

Failure to follow these guidelines may result in injury or 

property damage.

•     This unit must be powered by a 24-hour, 120V AC pure sine

wave 60 Hz circuit. Be sure the circuit cannot be turned off 

by a switch, dimmer, or ground fault circuit interrupter.

Failure to connect this unit to a 24-hour circuit may prevent it

from providing constant protection. Unit may be connected to

an arc fault circuit interrupter.

•     This Smoke/CO Alarm must have AC or battery power to 

operate. If AC power fails and the battery is dead or missing,

the alarm cannot operate.

•     Never disconnect the power from an AC powered unit to 

stop an unwanted alarm. Doing so will disable the unit and

remove your protection. In the case of a true unwanted 

alarm, use the Silence Feature (if equipped), open a window

or fan the smoke away from the unit. The alarm will reset

automatically when it returns to normal operation. Never

remove the batteries from a battery operated unit to stop an

unwanted alarm (caused by cooking smoke, etc.). Instead

open a window or fan the smoke away from the unit. The

alarm will reset automatically.

“ALARM-MOVE TO FRESH AIR”

If you hear the CO alarm horn and the CO red light is flashing,

move everyone to a source of fresh air. 

DO NOT remove the batteries

!

M08-0121-014_M08-0121-006.E_SC9120A_BA_V5.0  15-10-16  11:24 AM  Page 1

Отзывы: