CO ALARM SPECIFICATIONS 

 

Gas Detection at Typical Temperature and 
Humidity Ranges: 

 

The CO Alarm is not 

formulated to detect CO levels below 30 ppm 
typically. UL tested for false alarm resistance to 
Methane (500 ppm), Butane (300 ppm), 
Heptane (500 ppm), Ethyl Acetate (200 ppm), 
Isopropyl Alcohol (200 ppm) and Carbon 
Dioxide (5000 ppm). Values measure gas and 
vapor concentrations in parts per million.

 

Required Alarm Levels: 

 

Before 10% COHb 

exposure at levels of 30% to 70% Relative 
Humidity (RH):

• 400 ppm CO between 4 and 15 minutes
• 150 ppm CO between 10 and 50 minutes
• 70 ppm CO between 60 and 240 minutes

The unit is designed not to alarm when exposed 
to a constant level of 30 ppm for 30 days.

 

Audible Alarm: 

 

85dB minimum at 10 feet

 

Power: 

 

Powered by 120V AC. When power 

is on, green light shines continuously. Digital 
Display: Dash lit by READY.

 

Display Accuracy: 

 

Accuracy is +100% -40% 

of actual concentration of CO at 50% RH +/-
5% RH and 73˚F +/- 4˚F (23˚+/- 2˚C).

 

Peak CO Reading: 

 

Digital Display shows the 

highest level of CO (ppm) detected since the 
Peak memory was last cleared. 

 

Malfunction: 

 

Yellow light shines continuously. 

Red light flashes. Horn chirps twice a minute. 
Digital Display will read “Err”.

 

Dimensions: 

 

5.83" x 3.32" x 1.6" (Approx.)

 

Supply Voltage: 

 

120V AC 60Hz

.085A Standby .087A Alarm

 

During Alarm: 

 

CO Alarm horn sounds while the 

red light flashes rapidly. Digital Display: Shows 
CO levels in ppm.

 

Warranty: 

 

5-year limited warranty.

 

Standards: 

 

Underwriters Laboratories Inc. 

Single and Multiple Station carbon monoxide 
alarms UL2034.

According to Underwriters Laboratories Inc. 
UL2034, Section 1-1.2: “Carbon monoxide 
alarms covered by these requirements are 
intended to respond to the presence of carbon 
monoxide from sources such as, but not limited 
to, exhaust from internal-combustion engines, 
abnormal operation of fuel-fired appliances, 
and fireplaces. CO alarms are intended to alarm 
at carbon monoxide levels below those that 
could cause a loss of ability to react to the 
dangers of Carbon Monoxide exposure.” This 
CO Alarm monitors the air, and is designed to 
alarm before CO levels become life threatening. 
This allows you precious time to leave the 
house and correct the problem. This is only 
possible if alarms are located, installed, and 
maintained as described in this manual.

Содержание CO2120PDN

Страница 1: ...MODEL CO2120PDN User s Manual 120V Plug In Carbon Monoxide Alarm With Digital Display and Silence Feature M06 1045 000 6 99 120V AC 60 Hz 085A Standby 087A Alarm With Peak CO Level Display ...

Страница 2: ...O After an Alarm 10 Using the Silence Feature 11 CHAPTER 4 TESTING AND MAINTENANCE 12 CHAPTER 5 WHAT YOU NEED TO KNOW ABOUT CO 13 What is CO 13 Symptoms of CO Poisoning 13 Potential Sources Of CO In The Home 14 How Can I Protect My Family 15 CHAPTER 6 UNDERWRITERS LABORATORIES INC UL2034 16 CHAPTER 7 TROUBLESHOOTING GUIDE 17 CHAPTER 8 GENERAL LIMITATIONS OF CO ALARMS 18 LIMITED WARRANTY BACK COVER...

Страница 3: ...r a potential problem after any alarm Failure to do so can result in injury or death WARNING This CO Alarm can not operate without continuous electricity It does not operate during a power failure WARNING NEVER ignore your Carbon Monoxide Alarm if it alarms Refer to What To Do If Your CO Alarm Alarms for more information Failure to do so can result in injury or death WARNING Test the CO Alarm once...

Страница 4: ...per million or ppm within a specified time measured in minutes When the unit is in alarm mode the Digital Display will show the levels of CO measured in parts per million present This Carbon Monoxide Alarm features a permanently installed sensor three colored indicator lights and an 85 dB alarm horn It also has a silence feature to temporarily quiet the alarm horn Malfunction Warning This unit per...

Страница 5: ...isplay a reading It will only display levels of carbon monoxide 30 ppm or higher 70 or higher The unit is calibrated to sound an alarm before 240 minutes have passed when exposed to this level 150 or higher The unit is calibrated to sound an alarm before 50 minutes have passed when exposed to this level At this level an average healthy adult may feel headache within 90 minutes 400 or higher The un...

Страница 6: ...uring Alarm Malfunction Green light ON Yellow light ON Red light FLASHES Horn chirps about twice a minute Digital Display Err During Normal Test All three lights flash briefly Horn pattern repeats twice 4 beeps pause 4 beeps pause Digital Display 888 Using the Silence Feature in Alarm Green light ON Yellow light OFF Red light FLASHES Horn silent for 4 minutes Refer to Using the Silence Button for ...

Страница 7: ...ws CLr NOTE The peak CO level will be saved even after a power interruption until you clear it The CO alarm will automatically switch back to READY immediately after you check or clear the peak CO level Examples of when to use the Peak CO Feature To check if CO was detected while you were away on vacation To check the highest level of CO recorded during an alarm especially if you were not home whe...

Страница 8: ...memory was last cleared Malfunction Yellow light shines continuously Red light flashes Horn chirps twice a minute Digital Display will read Err Dimensions 5 83 x 3 32 x 1 6 Approx Supply Voltage 120V AC 60Hz 085A Standby 087A Alarm During Alarm CO Alarm horn sounds while the red light flashes rapidly Digital Display Shows CO levels in ppm Warranty 5 year limited warranty Standards Underwriters Lab...

Страница 9: ...m the furnace or fuel burning heat source In a Multi level Home Install at least one CO Alarm near or within each separate sleeping area For added protection install at least one CO Alarm on each level of the home If you have a basement install that CO Alarm at the top of the basement stairs For added protection install an additional CO Alarm at least 20 feet 6 meters away from the furnace or fuel...

Страница 10: ...resh air returns or open windows Blowing air may prevent CO from reaching the sensors In direct sunlight In outlets covered by curtains or other obstruction WARNING This CO Alarm is designed for use inside a single family home or apartment It is not meant to be used in common lobbies hallways or basements of multi family buildings unless working CO Alarms are also installed in each family living u...

Страница 11: ...til the unit sounds 4 beeps pause 4 beeps The sequence should last 5 6 seconds During testing the green yellow and red lights flash This is normal 888 will appear on the Digital Display 4 While testing the unit have a family member check that the horn can be easily heard from the sleeping areas The unit should be located where it can wake you if it alarms at night 5 Find the pair of self adhesive ...

Страница 12: ...d appliance technician to investigate for sources of CO from fuel burning equipment and appliances and inspect for proper operation of this equipment If problems are identified during this inspection have the equipment serviced immediately Note any combustion equipment not inspected by the technician and consult the manufacturers instructions or contact the manufacturers directly for more informat...

Страница 13: ...tern 4 beeps a pause 4 beeps etc Press and hold the Test Silence button until the horn is silent The initial Silence cycle will last approximately 4 minutes NOTE After the initial 4 minute Silence cycle the CO Alarm re evaluates present CO levels and responds accordingly If CO levels remain potentially dangerous or start rising higher the horn will start sounding again While the detector is silenc...

Страница 14: ...When testing step away when horn starts sounding REGULAR MAINTENANCE To keep the CO Alarm in good working order Test it every week using the Test Silence button Vacuum the CO Alarm cover at least twice a year using the soft brush attachment Test the Alarm again after vacuuming CAUTION DO NOT spray cleaning chemicals or insect sprays directly on or near the CO Alarm DO NOT paint over the CO Alarm D...

Страница 15: ...ymptoms Medium Exposure Throbbing headache drowsiness confusion fast heart rate Extreme Exposure Convulsions unconsciousness heart and lung failure Exposure to Carbon Monoxide can cause brain damage death CAUTION Some individuals are more sensitive to CO than others including people with cardiac or respiratory problems infants unborn babies pregnant mothers or elderly people can be more quickly an...

Страница 16: ...of fuel appliances caused by outdoor conditions such as Wind direction and or velocity including high gusty winds Heavy air in the vent pipes cold humid air with extended peri ods between cycles Negative pressure differential resulting from the use of exhaust fans Several appliances running at the same time competing for limited fresh air Vent pipe connections vibrating loose from clothes dryers f...

Страница 17: ...inspections of all fuel burning appliances Check appli ances for excessive rust and scaling Also check the flame on the burner and pilot lights The flame should be blue A yellow flame means fuel is not being burned completely and CO may be present Keep the blower door on the fur nace closed Use vents or fans when they are available on all fuel burning appli ances Make sure appliances are vented to...

Страница 18: ...ay cause headaches in average healthy adults after 35 minutes but can cause death after 2 hours IMPORTANT This CO Alarm measures exposure to CO over time It alarms if CO levels are extremely high in a short period of time or if CO levels reach a certain minimum over a long period of time The CO Alarm generally sounds an alarm before the onset of symptoms in average healthy adults Why is this impor...

Страница 19: ...Limited Warranty for details CO Alarm goes back into alarm 4 minutes after you press the Test Silence button CO levels still indicate a potentially dangerous situation Refer to Chapter 3 If Your CO Alarm Alarms for details on how to respond to an alarm If anyone is feeling ill EVACUATE your home immediately CO Alarm alarms frequently even though no high levels of CO are revealed in an investigatio...

Страница 20: ...s or has been drinking alcoholic beverages This is especially true if the door is closed or only partly open Even persons who are awake may not hear the alarm horn if the sound is blocked by distance or closed doors Noise from traffic stereo radio television air conditioner or other appliances may also prevent alert persons from hearing the alarm horn This CO Alarm is not intended for people who a...

Страница 21: ...not cover normal wear of parts or damage resulting from any of the following negligent use or misuse of the product use on improper voltage or current or use contrary to the operating instructions disassembly repair or alteration by anyone other than BRK Brands Inc Further the warranty does not cover acts of God such as fire flood hurricanes and tornadoes BRK Brands Inc shall not be liable for any...

Отзывы: