Brivo Allegion AD400 Скачать руководство пользователя страница 2

© 2018 Brivo Systems LLC. All rights reserved.

P-MAN-PUB-Allegion AD400 

Configuration Guide 1.0

2

Allegion AD400 Configuration Guide

Introduction

The following figure illustrates the Brivo Onair - Allegion topology:

Required Components

Brivo ACS6000-E or ACS300-E controller with firmware 5.2.10 or higher
Allegion Panel Interface Module (PIM400-485)
Allegion AD400 Wireless Lock
Hand Held Device (HHD) 
Schlage Utility Software (SUS)

Содержание Allegion AD400

Страница 1: ...Planning Before You Begin 3 Wiring ACS6000 E ACS300 E to Allegion PIM 3 Configuration III Overview of Configuration Process 4 Couple a PIM400 485 unit to the HHD 4 Update the PIM400 485 firmware 4 Configure the PIM400 485 unit 4 Couple an AD400 Wireless Lock to the HHD 5 Update the AD400 Wireless Lock firmware 6 Configure an AD400 Wireless Lock 6 Linking an AD400 Wiress Lock and a PIM400 485 Unit ...

Страница 2: ...Configuration Guide Introduction The following figure illustrates the Brivo Onair Allegion topology Required Components Brivo ACS6000 E or ACS300 E controller with firmware 5 2 10 or higher Allegion Panel Interface Module PIM400 485 Allegion AD400 Wireless Lock Hand Held Device HHD Schlage Utility Software SUS ...

Страница 3: ...ide can be found inside the box with the lock 3 Video How to Install Schlage AD400 Series Wireless Lock 4 Install Schlage Utility Software SUS and download the latest PIM400 485 and AD400 firmware from SUS to the Hand Held Device 5 Confirm that the ACS6000 E ACS300 E panel system is connected tothe Brivo Onair account and is operational Wiring the ACS6000 E ACS300 E to the Allegion Panel Interface...

Страница 4: ...nect the HHD to the PIM400 485 using the HH USB cable The PIM400 485 will be displayed on the HHD screen 2 Open the Schlage Utility Software SUS The default username is administrator and password is 123456 a Select Device Options b When the password window appears do not select anything 3 On the PIM400 485 press and hold the LINK 1 button Then press the LINK 2 button three times 4 In the SUS selec...

Страница 5: ...h Door PIM 1 0 0 9 PIM 2 1 10 19 PIM 3 2 20 29 PIM 4 3 30 39 9 Set the Wake On Radio to enabled and keep the time at 5 seconds The default is disabled 10 It is recommended to enable door cache mode so the lock will open the door for previously granted credentials in the event of a communication failure Couple an Allegion AD400 Wireless Lock to the Hand Held Device HHD 1 Connect the HHD to the lock...

Страница 6: ...nfiguring the PIM400 485 8 Write down the Door Lock Address for your AD400 Wireless Lock This address will be required when configuring the AD400 Wireless Lock within Brivo Onair Linking an AD400 Wireless Lock and a PIM400 485 Unit Note To proceed the PIM400 485 unit must be in Link Mode see above 1 Hold down the inside lever of the AD400 Wireless Lock 2 While holding down the lever present a cred...

Страница 7: ...rface Module Note Within Brivo Onair a PIM400 485 unit is identified as an Allegion Gateway 1 Scroll over the Setup link The sub navigation menu displays 2 From the sub navigation menu scroll over the Sites Doors tab and click Control Panels from the dropdown list The Control Panels List page displays 3 Select the desired control panel to which you wish to associate the Allegion PIM400 485 4 Scrol...

Страница 8: ...ration Guide 1 0 8 Allegion AD400 Configuration Guide 7 Choose Allegion Gateway The PIM400 485 unit is listed as a Gateway within Brivo Onair 8 Enter a Location if desired 9 Select the Allegion Gateway Address from the dropdown list 10 When finished click Save Wireless Gateway ...

Страница 9: ...Interface Module 1 Scroll over the Setup link The sub navigation menu displays 2 From the sub navigation menu scroll over the Sites Doors tab and click Control Panels from the dropdown list The Control Panels List page displays 3 Select the Control panel with the associated PIM you want to delete 4 Click on the Allegion Gateway Device you wish to delete The Device Details page displays 5 Click on ...

Страница 10: ...Control Panel and click Next 7 Select the Allegion Gateway Device from the Board dropdown list 8 Selection the Allegion Gateway Address from the Node Address dropdown list 9 If desired check the Enable Privacy Mode radio button to have the AD400 Wireless Lock use Privacy Mode functionality 10 If desired check the Door Ajar Enabled radio button to have the Allegion AD400 Lock Device report door aja...

Страница 11: ... sub navigation menu scroll over the Sites Doors tab and click Site Directory 3 Click on the site which has the associated Allegion AD400 lock you wish to edit 4 Click on the Allegion Lock Device you wish to edit 5 Click Edit Door The Edit Device page displays 6 After you have finished making changes click Save Door You are returned to the Device Details page Deleting an Allegion AD400 Lock Device...