Renovent HR Medium/Large 2nd edition Augustus 2007
21
Putting into operation
Chapter 6
6.6 Readouts settings
As standard the current position of the multiple switch and the
connected output volume are shown (Operational mode). On
the left the position of the multiple switch (position 1, 2 or 3) is
shown and to the right of the dot the volume of the output fan
is shown.
a = Setting the multiple switch
b = Volume output fan
6.6.1 Reading out settings by the user
The user can read out other relevant data using keys "
+
” and “
-
”
VWHSWRVWHS6WHSQXPEHUVDUHQRWVKRZQRQWKHGLVSOD\
6HHWKHWDEOHRIVHFWLRQIRUXVHUUHDGRXWZKHQQRNH\LV
operated during 5 minutes, the display automatically returns
to operational mode. Key “
+
” can be used to scroll through the
PHQXNH\³
-
” always takes you back to step 0. Modifying set-
tings is not possible in this situation.
6.6.2 Reading out settings by the installer
A more comprehensive readout programme is available for the
installer. Pressing keys “
F
” and “
OK
” during 3 seconds calls up
all installer data. In this menu the values cannot
EHPRGL¿HG
Activating this menu always calls up step no. 7 (see table be-
ORZSUHVVLQJNH\FDOOVXSWKHLQVWDOOHUDQGXVHUGDWDDQG
pressing key "-" takes you back to step no. 1.
After 5 minutes this menu automatically disappears and the
display will show the operational situation again.
,QWKHHYHQWRIDQHUURUWKHHUURUFRGHDSSHDUVRQWKHGLVSOD\
see also chapter 7.
5422-0
>3s
User
Step
number
Readout
(example)
Description
Remark
installer
No.1
2,200
Current position/outlet volume [m
3
/h]
No.2
C 0
Message code operating condition
C0 = No message
C3 = The input fan runs in constant pressure mode
C6 = The output fan runs in constant pressure mode
& &RUUHFWLRQPD[LPXPDLUÀRZ
No.3
bP.1
Bypass status
(only if mounted)
0 = bypass valve shut, 1 = bypass valve automatic
2 = input at minimum
No.4
tP.9
Temperature from atmosphere [°C]
At negative temperature (below 0°C) then readout tP.9.
No.5
tS.21
Temperature from indoors [°C]
No.6
In.0
n.a.
No.7
u
.156
Current input volume [m
3
/h]
No.8
U
.156
Current output volume [m
3
/h]
No.9
t.180
Current pressure input duct [Pa]
No.10
A.180
Current pressure output duct [Pa]
No.11
u0.0
Status frost protection
0 = none, 1 - 4 = imbalance, 5 = input fan off
No.12
St.9
Temperature to atmosphere [°C]
(Sensor not connected as standard)
If not connected St.75
No.13
Pt.18
Temperature to indoors [°C]
(Sensor not connected as standard)
If not connected Pt.75