17
Faults
Remark
Reason
Solution
IPM module output circuit temperature
sensor failure
EE14
The sensor output is abnormal
Check the instrument panel or replace
Protection against excessively high IPM
module temperatures
EE15
Check the instrument panel or replace
Protection of PFC module
EE16
Check the instrument panel or replace
DC fan error
EE17
Check the instrument panel or replace
IPM module input circuit temperature sensor
failure
EE18
Check the instrument panel or replace
Protection against excessively high PFC
module temperatures
EE19
Check the instrument panel or replace
Electrical power failure
EE20
The supply voltage is too variable
Check the instrument panel or replace
Software check error
EE21
The compressor runs outside of preset steps
Check the instrument panel or replace
Current detection circuit fault
EE22
Abnormal amplification of the output voltage
Check the instrument panel or replace
Compressor switch fault
EE23
Check the instrument panel or replace
Ambient temperature thermometer control
unit failure
EE24
Compressor phase error
EE25
1. Badly connected wiring,
2. Connection of one or two phases
Monitor the controller
Defrosting symbol, heater check is lit
Defrosting of glass
8.2 Other Malfunctions and Solutions (No display on LED wire controller)
Malfunctions
Observing
Reasons
Solution
Heat pump is
not running
LED wire controller
no display.
No power supply
Check cable and circuit breaker if
it is connected
LED wire controller.
displays the actual time.
Heat pump under standby status
Startup heat pump to run.
LED wire controller
displays the actual
water temperature.
1. Water temperature is reaching
to setting value, HP under con-
stant temperature status.
2. Heat pump just starts to run.
3. Under defrosting.
1. Verify water temperature
setting.
2. Startup heat pump after a few
minutes.
3. LED wire controller should
display „Defrosting“.
Water temperature is cooling
when HP runs under heating
mode
LED wire controller displays
actual water temperature and no
error code displays.
1. Choose the wrong mode.
2. Figures show defects.
3. Controller defect.
1. Adjust the mode to proper
running
2. Replace the defect LED wire
controller, and then check the
status after changing the running
mode, verifying the water inlet
and outlet temperature.
3. Replace or repair the heat
pump unit
Short running
LED displays actual water
temperature, no error code
displays.
1. Fan NO running.
2. Air ventilation is not enough.
3. Refrigerant is not enough.
1. Check the cable connections
between the motor and fan, if
necessary, it should be replaced.
2. Check the location of heat
pump unit, and eliminate all ob-
stacles to make good air venti-
lation.
3 Replace or repair the heat pump
unit.
water stains
Water stains on heat pump unit.
1. Concreting.
2. Water leakage.
1. No action.
2. Check the titanium heat
exchanger carefully if it is any
defect.
Too much ice on evaporator
Too much ice on evaporator.
1. Check the location of heat
pump unit, and eliminate all ob-
stacles to make good air venti-
lation.
2. Replace or repair the heat
pump unit.