![Briggs & Stratton 12KW Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/briggs-and-stratton/12kw/12kw_installation-and-operation-manual_2811103015.webp)
15
The concrete slab/pad must meet the requirements below
and the generator must be anchored with the anchors
of
Anchor Types
1 or 2.
Anchor Types
1. Qty (3) 3/8” SS ITW RED HEAD LDT, Anchor embedded
2 ½” (63.5mm) in 3000 psi concrete. 3” (76.2mm) from
the edge minimum, 6” (152.4mm) spacing minimum.
2. Qty (3) 3/8” SS Powers/Dewalt Power Stud +SD2
Anchor embedded 2 ½” (63.5mm) in 3000 psi concrete.
3” (76.2mm) from the edge minimum, 6” (152.4mm)
spacing minimum.
There are three 7/16” hole locations (A) in the base of the
generator in which to anchor the unit.
Concrete Slab/Pad Types
PAD DIMENSIONS
WIND
RATING
MPH
PAD
MODEL
Width
Length
Thickness
CONCRETE
SPEC
Up to 140 Pre-cast
Pad
(contact
dealer)
29in
(736.6mm)
32in
(812.8mm)
3in
(76.2mm)
3000 PSI
140 to 175 Pre-cast
Pad
(contact
dealer)
29in
(736.6mm)
32in
(812.8mm)
4in
(101.6mm)
3000 PSI
140 to 175 Poured
30in
(762mm)
32in
(812.8mm)
5in
(127.6mm)
3000 PSI
These items are available at your local service dealer.
NOTICE
Unless mandated by local or state codes to
achieve wind rating, a concrete slab/pad is not required
Panel Attachment in Wind Rated Areas
To achieve a wind rating of 140 mph and above, (2) 1/4-20
Screws (B) are included and must be installed in the bottom
of the front panel.
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (A) and electrical inlet
locations (B) are shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet can be enlarged or supplemented to accommodate a
maximum conduit size of 1-½ inches. Make sure that the
installed conduit(s) enter the unit in zone (C) as shown in the
drawing that follows so that they correctly enter the electrical
box and do not interfere with the roof or any other component
of the generator.
Not for
Reproduction
Содержание 12KW
Страница 40: ...40 Diagrams and Schematics Wiring Diagram and Schematic N o t f o r R e p r o d u c t i o n ...
Страница 83: ...83 Diagramas y Esquemas Diagrama y esquema de cableado N o t f o r R e p r o d u c t i o n ...
Страница 128: ...128 Diagrammes et schémas Diagramme de câblage N o t f o r R e p r o d u c t i o n ...
Страница 130: ...N o t f o r R e p r o d u c t i o n ...
Страница 131: ...N o t f o r R e p r o d u c t i o n ...
Страница 132: ...N o t f o r R e p r o d u c t i o n ...