Troubleshooting/Specifications

Problem

Cause

Correction

Engine is running, but no AC 

output is available.

  1.  One of the circuit breakers is open.
  2.  Poor connection or defective cord set.
  3.  Connected device is bad. 

  4.  Red LED light is steady. Generator is 

overloaded or overheated. 

  1.  Reset circuit breaker.
  2.  Check and repair.

  3.  Connect another device that is in 

good condition. 

  4. See

 Generator

 

Capacity

. Press 

MAIN RESET button on control 

panel.

Engine runs well at no-load but 

“bogs down” when loads are 

connected.

  1.  Generator is overloaded.

  1. See 

Generator Capacity

.

Engine will not start; starts and 

runs rough or shuts down when 

running.

  1.  Fuel valve is in off ( ) position.
  2.  Low oil indicator light comes on. Low 

oil level.

3.  Dirty air cleaner.

  4.  Out of fuel.
  5.  Spark plug wire not connected to 

spark plug.

  6.  Flooded with fuel.
  7.  Battery not connected or discharged.

  1.  Turn fuel valve to on ( ) position.
  2.  Fill crankcase to proper level or 

place generator on level surface.

  3.  Clean or replace air cleaner.
  4.  Fill fuel tank.
  5.  Connect wire to spark plug. 

  6.  Wait 5 minutes and re-crank engine.
  7.  Connect or charge battery.

Engine shuts down and CO 

shutdown system LED blinks red 

(•• ••).

  1.  Generator improperly located.

  1.  Move generator to an open, 

outdoor area. Air out premises (e.g. 

open windows and doors) before 

reoccupying. See 

Carbon Monoxide 

(CO) Shutdown System.

For all other issues, see a Briggs & Stratton authorized dealer.

Specifications

Rated Wattage*  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,700 

Starting Wattage**  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,500

AC Current at 230 Volts   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.1 Amps

Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Hz

Phase  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single Phase

Displacement  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224 cc

Spark Plug Gap  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.7-0.8 mm 

Fuel Capacity  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.25 Liters

Oil Capacity  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6 Liters

Sound Pressure @ 7 m§  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74 dBA

* Generator rated in accordance with CSA (Canadian Standards Association) standard C22.2 No. 100-14, Motors and Generators. 
**Per Briggs & Stratton 628K.
§ Measured sound values in accordance to AS/NZS 3010:2017, Electrical Installations - Generating Sets

Содержание 030807

Страница 1: ...Number ______________________________ Revision ___________________________________ Serial Number _______________________________ Date Purchased _____________________________ Copyright 2020 Briggs Stra...

Страница 2: ...rating compatible electrical lighting appliances tools and motor loads The generator s revolving field is driven by a single cylinder engine To move generator press button and pull handle out Press bu...

Страница 3: ...r 10 seconds InfoHub Portable Wireless App Download the InfoHub Portable App to pair the Bluetooth enabled generator to your approved Android or iOS smartphone and follow the in app instructions The g...

Страница 4: ...engine Check oil level with dipstick Maintenance Cover Remove to gain access to the choke lever spark plug and air cleaner Oil Drain Plug Drain engine oil here Oil Fill Cap Dipstick Check and add eng...

Страница 5: ...hutdown due to carbon monoxide accumulation around the generator or a CO shutdown system fault occurred Circuit Breaker A push to reset circuit breaker is provided to protect the generator against ele...

Страница 6: ...N o t f o r R e p r o d u c t i o n 6 BRIGGSandSTRATTON com au Exhaust muffler Point away from home Features and Controls...

Страница 7: ...ll be exposed to carbon monoxide gas Operate portable generator only outdoors at least 6 1 m from occupied spaces with exhaust pointed away to reduce the risk of carbon monoxide accumulating Install b...

Страница 8: ...generator must be at least 1 5 m from any structure overhang trees shrubs or vegetation over 30 5 cm in height Do not place portable generator under a deck or other type of structure that may confine...

Страница 9: ...h Altitude for 1524 m and above WARNING Fuel and its vapors are extremely flammable which could cause burns or fire resulting in death or serious injury Do not refuel during operation Do not smoke dur...

Страница 10: ...over and position the choke lever to the middle position The e choke will automatically turn the choke off once the generator starts Reinstall maintenance cover NOTICE If engine starts but fails to ru...

Страница 11: ...Equipment only 12 Volt DC Receptacle The maximum current available for the 12 Volt DC receptacle is 60 Watts 5 Amps A DC circuit breaker protects this receptacle from overloads If an overload occurs t...

Страница 12: ...e to consider starting watts in generator capacity Carbon Monoxide CO Shutdown System Automatically shuts down the engine when harmful levels of carbon monoxide accumulate around the generator or a CO...

Страница 13: ...uel leaks Clean any accumulated debris Keep area around muffler free from any debris Use a soft bristle brush to loosen caked on dirt or oil Use a damp cloth to wipe exterior surfaces clean NOTICE Imp...

Страница 14: ...il into oil fill opening to the point of overflowing 6 Replace and tighten dipstick NOTICE Do not attempt to crank or start engine before it has been properly serviced with recommended oil This could...

Страница 15: ...d tighten screws 10 Reinstall the maintenance cover and hand tighten the cover screws Service Spark Plug Changing the spark plug will help your engine to start easier and run better 1 Loosen the two m...

Страница 16: ...iner Then run the engine until it stops from lack of fuel WARNING Fuel and its vapors are extremely flammable and explosive which could cause burns fire or explosion resulting in death or serious inju...

Страница 17: ...not connected or discharged 1 Turn fuel valve to on position 2 Fill crankcase to proper level or place generator on level surface 3 Clean or replace air cleaner 4 Fill fuel tank 5 Connect wire to spar...

Страница 18: ...N o t f o r R e p r o d u c t i o n 18 BRIGGSandSTRATTON com au Notes...

Страница 19: ...N o t f o r R e p r o d u c t i o n 19 Notes...

Страница 20: ...e commercial use In Australia Our goods come with guarantees that cannot be excluded under the Australian Consumer Law You are entitled to a replacement or refund for a major failure and for compensat...

Отзывы: